Factors Affecting Corona in Overhead Transmission Lines

Factors Affecting Corona in Overhead Transmission Lines

Author: Engr. Aneel Kumar

Factors affecting corona discharge in transmission lines infographic
Figure 1: Infographic illustrating the factors influencing corona discharge in transmission lines.

Introduction

The corona effect in overhead transmission lines is a phenomenon that occurs when the electric field intensity around conductors exceeds a critical value, causing ionization of the surrounding air. This ionization produces bluish light, hissing sound, power loss, and ozone gas. While corona may seem undesirable, it also has a few advantages such as reducing overvoltages by absorbing surges.

Corona directly impacts power system efficiency, transmission losses, equipment life, and design cost. Therefore, engineers must understand the factors affecting corona in detail to ensure efficient and reliable design of high-voltage transmission systems.

1. Conductor Size (Diameter)

The diameter of the conductor plays a crucial role in corona formation. A larger conductor size results in lower surface electric field intensity, which increases the corona inception voltage and decreases the chances of corona discharge. This is why bundled conductors are extensively used in EHV (Extra High Voltage) and UHV (Ultra High Voltage) systems.

For example, a 400 kV line with a single conductor may produce heavy corona, but the same line using bundled conductors will experience significantly less corona discharge. This reduces corona loss, audible noise, and radio interference.

2. Spacing Between Conductors

The spacing between conductors directly influences the electric field intensity. If conductors are placed close to each other, the field intensity increases and corona is more likely. By increasing conductor spacing, the disruptive critical voltage can be raised, thus reducing corona.

However, excessive spacing is not desirable because it increases tower size, cost, and right-of-way requirements. Therefore, an optimal balance between mechanical design and electrical performance must be achieved.

3. System Voltage

Corona effect is directly proportional to system voltage. At low voltages (below 30 kV), corona is negligible. However, at 220 kV, 400 kV, and higher transmission lines, corona becomes a major consideration in design. Engineers design lines such that the operating voltage is kept well below the corona inception voltage under fair weather conditions.

If the operating voltage is too close to the critical disruptive voltage, corona becomes continuous, leading to severe power losses and interference.

4. Atmospheric Conditions

The atmospheric conditions significantly affect corona performance. In rain, fog, snow, and dust, the conductor surface becomes irregular due to moisture or particles, which reduces the corona inception voltage. This results in a higher intensity of corona discharge.

In fair weather, corona is less severe and often negligible for properly designed systems. Thus, engineers design lines considering worst-case weather scenarios.

5. Conductor Surface Condition

The surface condition of conductors is another critical factor. Smooth, polished conductors maintain uniform electric field distribution, while rough or stranded conductors intensify the electric field at certain points, leading to early corona onset.

Corrosion, dust deposition, and aging of conductors worsen this effect. This is why transmission companies prefer conductors with protective coatings and periodic maintenance to keep surfaces clean.

6. Line Frequency

The frequency of the supply system also impacts corona. Corona loss increases with frequency because ionized particles oscillate more rapidly. Since most power systems operate at 50 Hz or 60 Hz, this factor remains constant; however, HVDC systems are immune to corona loss due to frequency effects.

7. Air Density and Pressure

The air density factor (δ) depends on altitude, temperature, and pressure. At higher altitudes, the air is thinner and offers less insulation strength, reducing the corona inception voltage. This makes corona more prominent in hilly or mountainous regions compared to coastal or plain regions.

Engineers apply correction factors while designing transmission lines for different altitudes to account for this variation.

Comparative Table: Factors vs. Effect on Corona

Factor Influence on Corona
Conductor SizeLarger diameter reduces corona effect by lowering surface electric field intensity.
Conductor SpacingIncreased spacing raises corona inception voltage and reduces corona discharge.
System VoltageHigher operating voltage increases corona intensity and losses.
Atmospheric ConditionsRain, fog, snow, and dust lower inception voltage, increasing corona.
Conductor Surface ConditionRough, dirty, or corroded surfaces intensify electric fields and promote corona.
Line FrequencyCorona loss increases with frequency; HVDC is immune to this effect.
Air DensityLow air density at high altitudes reduces inception voltage, increasing corona.

Advantages of Corona

  • Reduces the severity of voltage surges and transients.
  • Acts as a natural regulator by limiting voltage peaks.
  • Provides a visible and audible warning of over-voltage conditions.

Disadvantages of Corona

  • Causes corona loss, reducing transmission efficiency.
  • Produces radio interference and audible noise.
  • Generates ozone and nitrous oxides, which deteriorate insulation.
  • Leads to power quality issues in nearby communication systems.
  • Reduce transmission line efficiency.
  • Leads to audible hissing and visual glow - undesirable in populated areas.

Conclusion

The corona effect is an inevitable phenomenon in high-voltage transmission lines, but its severity can be minimized through careful design, choice of conductor, optimal spacing, weather considerations, and maintenance. While it has certain advantages such as surge absorption, its disadvantages like power loss and interference outweigh the benefits in most cases.

By understanding the factors affecting corona, engineers can design transmission systems that balance reliability, efficiency, and cost-effectiveness, ensuring long-term stability of the power grid.

Popular posts from this blog

Auto Transformer Tap Changing

Auto Transformer Tap Changing: Working Principle, Switching Sequence and Applications Auto transformer tap changing is a practical method of adjusting transformer output voltage without unnecessarily interrupting the electrical supply. In power transmission and distribution networks, the load does not remain constant throughout the day. As load current changes, voltage drops across transformers, cables, feeders, and transmission lines also change. A tap-changing arrangement compensates for these variations by modifying the effective number of turns in the transformer winding. A reactor-type on-load tap changer uses a center-tapped reactor, selector switches, and a bypass or short-circuiting switch to transfer the load from one tap to the next. The reactor limits the circulating current during the transition, allowing the tap position to change while the transformer continues supplying the connected load. This article explains the auto transformer tap-changing working principle , switch...

PRIMARY SECONDARY AND TERTIARY FREQUENCY CONTROL IN POWER SYSTEMS

Primary, Secondary and Tertiary Frequency Control in Power Systems Author: Engr. Aneel Kumar Keywords: frequency control, primary frequency control, automatic generation control (AGC), tertiary control, load-frequency control, grid stability. Frequency control keeps the power grid stable by balancing generation and load. When generation and demand drift apart, system frequency moves away from its nominal value (50 or 60 Hz). Grids rely on three hierarchical control layers — Primary , Secondary (AGC), and Tertiary — to arrest frequency deviation, restore the set-point and optimize generation dispatch. Related: Power System Stability — causes & mitigation Overview of primary, secondary and tertiary frequency control in power systems. ⚡ Primary Frequency Control (Droop Control) Primary control is a fast, local response implemented by generator governors (dro...

Advantages of Per Unit System in Power System Analysis | Electrical Engineering

  Advantages of Per Unit System in Power System Analysis In electrical power engineering, the per unit (p.u.) system is one of the most widely used techniques for analyzing and modeling power systems. It is a method of expressing electrical quantities — such as voltage, current, power, and impedance — as fractions of chosen base values rather than their actual numerical magnitudes. This normalization technique provides a universal language for system calculations, minimizing errors, simplifying transformer modeling, and enabling consistency across multiple voltage levels. Because of these benefits, the per unit system is essential in fault analysis, load flow studies, transformer testing, and short-circuit calculations . ⚡ What is the Per Unit System? The per unit system is defined as: Q u a n t i t y ( p u ) = A c t u a l   V a l u e B a s e   V a l u e Quantity_{(pu)} = \dfrac{Actual \ Value}{Base \ Value} Q u an t i t y ( p u ) ​ = B a se   ...

Top 10 Transformer Manufacturers in the World

Top 10 Transformer Manufacturers in the World Transformers are among the most important and expensive assets in electrical generation, transmission, distribution, renewable-energy, industrial, infrastructure, and data-center projects. A power transformer changes voltage and current levels through electromagnetic induction while maintaining the system frequency. Generator step-up transformers increase generating-station voltage for efficient transmission, while grid and distribution transformers reduce voltage progressively before electricity reaches industrial, commercial, and residential consumers. The global transformer market continues to expand because of grid modernization, renewable-energy integration, industrial electrification, data-center development, replacement of aging equipment, and construction of new transmission infrastructure. One 2026 market assessment estimates that the global transformer market could grow from approximately USD 72.5 billion in 2026 to about USD 137....

Reversing the Direction of a Universal Motor: Methods and Circuit Diagram

How to Reverse the Direction of Rotation of a Universal Motor Introduction A universal motor is a high-speed electric motor that can operate on either an alternating-current or direct-current supply when designed for the applicable voltage and frequency. It is widely used in portable electric drills, grinders, vacuum cleaners, mixers, sewing machines, small machine tools, and other equipment requiring high starting torque and compact construction. The direction of rotation of a universal motor can be changed by reversing the direction of current through either the armature winding or the field winding relative to the other. The current must be reversed in only one of these windings. If the connections of both windings are reversed simultaneously, the relative direction of the field flux and armature current remains unchanged, and the motor continues rotating in the same direction. Before studying the reversing methods, readers may review the Universal Series Motors Electric Motors and...

Top 10 Power-System Protection Relays and Their Applications

A power system must continuously transport electrical energy while remaining within the thermal, mechanical, and insulation limits of generators, transformers, busbars, transmission lines, cables, motors, and switchgear. When a short circuit, insulation failure, overload, abnormal voltage, frequency disturbance, or equipment malfunction occurs, the affected section must be disconnected quickly. A delay of even a fraction of a second during a severe fault can increase equipment damage, expose personnel to danger, and threaten the stability of the wider electrical network. A protection relay monitors electrical quantities such as current, voltage, frequency, phase angle, impedance, power, and temperature. When measured values meet predefined operating criteria, the relay initiates an alarm, trips a circuit breaker, starts an automatic control action, or blocks an unsafe operation. The three basic duties of a protection relay are: Measure electrical quantities Detect abnormal or fault co...

MAIN AND PILOT EXCITER

Main Exciter The exciter (sometimes called the main exciter) is a synchronous generator that has its stator and rotor windings inverted. Its field winding is fixed in the stator, and the rotor carries the armature or AC . In addition the rotor carries the semiconductor bridge rectifier that converts the armature voltages to a two-wire DC voltage system. The AC voltages and currents in the armature are often alternating at a higher frequency than those in the main generator, e.g. 400 Hz. The higher frequency improves the speed of response of the exciter. The DC power circuit is coupled to the field of the main generator by the use of insulated conductors that pass coaxially inside the rotor of the exciter and the rotor of the main generator. This eliminates the use of slip rings, which were traditionally used before shaft mounted rectifiers were developed. A slight disadvantage of this technique is that the derivative feedback cannot be taken from the output of the exciter. Howeve...