ELECTRONIC FUSES

There are many different types of electronic fuses and every manufacturer has their own solution. The principle is the same though; a sensor measures the current and some kind of controller or comparator, often a micro processor, controls a transistor, typically of a MOSFET kind. By master the opening and the closing of the MOSFET, the controller sets if the current should be cut off. Since a controller is programmable, an electronic fuse has a wide range of applications.

One controller can be in command of many MOSFET’s which individually can be put on or off remotely and has an electronic fuse state memory to know in which state it is during disconnection. Control equipment can be connected for monitoring voltage and current level.

Sometimes the electronic fuses are constructed with two MOSFET’s as seen in Figure 2.9. At start-up, the transistor M1 opens first and once steady state has been reached, M2 will be switched on. Because of the higher resistance R, the current will flow through M2 instead of M1. With this design high start-up currents are limited. M1 is kept on but due to the resistance R only a negligible part of the current will flow through it. If an overload or a current transient occurs the controller turns M2 off and the resistance prevents over currents. If the fault condition lasts longer than the programmed time-current curve allows, M1 will also be turned off and break the circuit.

Figure 2.9: A simple circuit diagram of an electronic fuse.

An electronic fuse does not have galvanic insulation and if exposed of too high currents the MOSFET become short circuited. To be able to guarantee circuit protection and to protect the MOSFET from destruction a melting fuse or a circuit breaker often is placed in series. An electronic fuse can limit relatively high currents, as long as the current through the MOSFET stays in the safe operating area.

An electronic fuse has a short trip time. Except for the time needed by the electronic control unit to create the control signal, the trip time only depends on the recombination conditions of the transistor. Since consisting of a MOSFET, an electronic fuse has a leakage current in off mode (Ileak < 10mA) and a voltage drop at ON state. The voltage drop, caused by RDS(on) of the MOSFET, results in heat losses which must be cooled off by a heat sink. The heat sink needed is often relatively expensive which results in increased cost of the electronic fuse.

Comments

Popular posts from this blog

Auto Transformer Tap Changing

Auto Transformer Tap Changing: Working Principle, Switching Sequence and Applications Auto transformer tap changing is a practical method of adjusting transformer output voltage without unnecessarily interrupting the electrical supply. In power transmission and distribution networks, the load does not remain constant throughout the day. As load current changes, voltage drops across transformers, cables, feeders, and transmission lines also change. A tap-changing arrangement compensates for these variations by modifying the effective number of turns in the transformer winding. A reactor-type on-load tap changer uses a center-tapped reactor, selector switches, and a bypass or short-circuiting switch to transfer the load from one tap to the next. The reactor limits the circulating current during the transition, allowing the tap position to change while the transformer continues supplying the connected load. This article explains the auto transformer tap-changing working principle , switch...

PRIMARY SECONDARY AND TERTIARY FREQUENCY CONTROL IN POWER SYSTEMS

Primary, Secondary and Tertiary Frequency Control in Power Systems Author: Engr. Aneel Kumar Keywords: frequency control, primary frequency control, automatic generation control (AGC), tertiary control, load-frequency control, grid stability. Frequency control keeps the power grid stable by balancing generation and load. When generation and demand drift apart, system frequency moves away from its nominal value (50 or 60 Hz). Grids rely on three hierarchical control layers — Primary , Secondary (AGC), and Tertiary — to arrest frequency deviation, restore the set-point and optimize generation dispatch. Related: Power System Stability — causes & mitigation Overview of primary, secondary and tertiary frequency control in power systems. ⚡ Primary Frequency Control (Droop Control) Primary control is a fast, local response implemented by generator governors (dro...

Advantages of Per Unit System in Power System Analysis | Electrical Engineering

  Advantages of Per Unit System in Power System Analysis In electrical power engineering, the per unit (p.u.) system is one of the most widely used techniques for analyzing and modeling power systems. It is a method of expressing electrical quantities — such as voltage, current, power, and impedance — as fractions of chosen base values rather than their actual numerical magnitudes. This normalization technique provides a universal language for system calculations, minimizing errors, simplifying transformer modeling, and enabling consistency across multiple voltage levels. Because of these benefits, the per unit system is essential in fault analysis, load flow studies, transformer testing, and short-circuit calculations . ⚡ What is the Per Unit System? The per unit system is defined as: Q u a n t i t y ( p u ) = A c t u a l   V a l u e B a s e   V a l u e Quantity_{(pu)} = \dfrac{Actual \ Value}{Base \ Value} Q u an t i t y ( p u ) ​ = B a se   ...

Top 10 Transformer Manufacturers in the World

Top 10 Transformer Manufacturers in the World Transformers are among the most important and expensive assets in electrical generation, transmission, distribution, renewable-energy, industrial, infrastructure, and data-center projects. A power transformer changes voltage and current levels through electromagnetic induction while maintaining the system frequency. Generator step-up transformers increase generating-station voltage for efficient transmission, while grid and distribution transformers reduce voltage progressively before electricity reaches industrial, commercial, and residential consumers. The global transformer market continues to expand because of grid modernization, renewable-energy integration, industrial electrification, data-center development, replacement of aging equipment, and construction of new transmission infrastructure. One 2026 market assessment estimates that the global transformer market could grow from approximately USD 72.5 billion in 2026 to about USD 137....

Reversing the Direction of a Universal Motor: Methods and Circuit Diagram

How to Reverse the Direction of Rotation of a Universal Motor Introduction A universal motor is a high-speed electric motor that can operate on either an alternating-current or direct-current supply when designed for the applicable voltage and frequency. It is widely used in portable electric drills, grinders, vacuum cleaners, mixers, sewing machines, small machine tools, and other equipment requiring high starting torque and compact construction. The direction of rotation of a universal motor can be changed by reversing the direction of current through either the armature winding or the field winding relative to the other. The current must be reversed in only one of these windings. If the connections of both windings are reversed simultaneously, the relative direction of the field flux and armature current remains unchanged, and the motor continues rotating in the same direction. Before studying the reversing methods, readers may review the Universal Series Motors Electric Motors and...

Top 10 Power-System Protection Relays and Their Applications

A power system must continuously transport electrical energy while remaining within the thermal, mechanical, and insulation limits of generators, transformers, busbars, transmission lines, cables, motors, and switchgear. When a short circuit, insulation failure, overload, abnormal voltage, frequency disturbance, or equipment malfunction occurs, the affected section must be disconnected quickly. A delay of even a fraction of a second during a severe fault can increase equipment damage, expose personnel to danger, and threaten the stability of the wider electrical network. A protection relay monitors electrical quantities such as current, voltage, frequency, phase angle, impedance, power, and temperature. When measured values meet predefined operating criteria, the relay initiates an alarm, trips a circuit breaker, starts an automatic control action, or blocks an unsafe operation. The three basic duties of a protection relay are: Measure electrical quantities Detect abnormal or fault co...

MAIN AND PILOT EXCITER

Main Exciter The exciter (sometimes called the main exciter) is a synchronous generator that has its stator and rotor windings inverted. Its field winding is fixed in the stator, and the rotor carries the armature or AC . In addition the rotor carries the semiconductor bridge rectifier that converts the armature voltages to a two-wire DC voltage system. The AC voltages and currents in the armature are often alternating at a higher frequency than those in the main generator, e.g. 400 Hz. The higher frequency improves the speed of response of the exciter. The DC power circuit is coupled to the field of the main generator by the use of insulated conductors that pass coaxially inside the rotor of the exciter and the rotor of the main generator. This eliminates the use of slip rings, which were traditionally used before shaft mounted rectifiers were developed. A slight disadvantage of this technique is that the derivative feedback cannot be taken from the output of the exciter. Howeve...