METHODS OF STARTING INDUCTION MOTORS

When the maximum kW rating of an induction motor is reached for direct-on-line starting, it becomes necessary to introduce an alternative method of starting the motor. There are several methods used in the oil industry. The object is to reduce the starting current drawn from the supply during all or part of the run-up period. There are two basic approaches that can be used:-

• Select special-purpose designs for the motor in which the winding arrangements are modified by external switching devices that are matched to the motor, e.g. star-delta motor and starter.

• Select conventional motors but use special external starting devices, e.g. Korndorfer starter, autotransformer starter, ‘soft-starter’ using a controlled rectifier-inverter system.

In all cases of reduced voltage starting, care must be taken to check that the motor will create sufficient torque at the reduced voltage to accelerate the load to the desired speed in as short a time as possible. Excessive run-up times must be avoided as. When the run-up time is expected to be high the manufacturer of the motor should be consulted regarding the possibility of damage and infringement of its guarantees. The following methods are the most commonly used, typically in the order shown below.

• Star-delta method.
• Korndorfer auto-transformer method.
• Soft-start power electronics method.
• Series reactor method.
• Part winding method.

Star-Delta Method Of Starting Induction Motors

A specially designed motor is used. The stator windings are arranged so that the start and finish of each phase winding in the stator is brought out to the main terminal box so that six terminals are available for connection to cables. Usually two three-core or four-core cables are used unless their conductor size becomes too large, in which case single-core cables would be used. The windings are connected externally in star for starting and delta for running. The external connections are made by using a special starter in the motor control centre which also provides control relays and current transformers that determine when the transfer from star to delta should take place.

Disadvantages of Star-Delta Method

• The windings are open-circuited during the transfer and this is not considered good practice, a delay should be incorporated to allow the flux in the motor to decay during the transfer.

• The starting current and torque are reduced to 33% of their value during the run-up period. This reduction may be too much for some applications.

• The running condition requires a delta winding connection and this has the disadvantage that harmonic currents can circulate in the windings.

Figure shows the basic circuit for a star-delta starter.



Korndorfer Auto-Transformer Method Of Starting Induction Motors

A standard design of motor is used. An external auto-transformer is connected between the main circuit breaker, or contactor, and the motor during the starting and run-up period. Figure 5.8 shows the connections that are commonly used in a balanced three-phase arrangement. The voltage ratio of the auto-transformer needs to be carefully selected. If it is too high then the full benefit is not achieved. If too low then insufficient torque will be created. The most effective ratio is usually found between 65% and 80%.

Disadvantage of Korndorfer Auto-Transformer Method

Two extra three-phase circuit breakers or contactors are necessary, thus making three in total for the motor circuit, which require space to be allocated. Retro-fitting a Korndorfer starter may therefore be difficult if space is scarce.

Figure shows the basic circuit for Korndorfer Auto-Transformer Method.



Soft-Start Power Electronics Method Of Starting Induction Motors

A standard design of motor is used. An external rectifier-inverter is connected between the main circuit breaker, or contactor, and the motor during the starting and run-up period. The starter varies the frequency and voltage magnitude of the applied three-phase supply to the motor. Upon starting the frequency and voltage are set to their lowest values, and thereafter they are slowly raised as the shaft speed increases. The intent is to operate the motor in its near-synchronous speed state for each frequency that the motor receives.

The rectifier-inverter equipment is expensive when compared with other switching and transformer methods, but it has several advantages:-

• The starting current can be limited to a value that is equal to or a little higher than the full-load current of the motor.

• The torque created in the motor during the whole run-up period can be in the order of the full-load value, and so the shape of the inherent torque-speed curve of the motor is not a critical issue for most standard designs of motors.

Series Reactor Method Of Starting Induction Motors

A standard design of motor is used. This is a simple method that requires the insertion of a series reactor during starting. The reactor is bypassed once the motor reaches its normal working speed.

Only one extra circuit breaker or contactor is required. The amount of reactance is calculated on the basis of the desired reduction of line current during starting, but the limiting factor is the reduced starting torque. The torque is reduced for two reasons, firstly because the total circuit impedance is increased and secondly the reactance-to-resistance ratio is increased.

Part Winding Method Of Starting Induction Motors

A special design of motor is used. The stator has two three-phase windings that are arranged in parallel and wound in the same slots. If the two windings are the same then on starting and during run-up one winding would provide half of the total torque at any speed. Hence one winding is used for starting and both for running. The method is not suited to small or high speed motors. With two equal windings the starting current and torque are half of their totals. This method is seldom used in the oil industry because of the preference for standard motors, and the availability of satisfactory alternative methods.

Comments

Unknown said…
hi i have a motor 750 hp can i used this method with this type of drawing (auto transformer )without any kind of restrectins or resk ,my mail is mohamed_alanany2003@yahoo.com .thanks

Popular posts from this blog

PRIMARY SECONDARY AND TERTIARY FREQUENCY CONTROL IN POWER SYSTEMS

Primary, Secondary and Tertiary Frequency Control in Power Systems Author: Engr. Aneel Kumar Keywords: frequency control, primary frequency control, automatic generation control (AGC), tertiary control, load-frequency control, grid stability. Frequency control keeps the power grid stable by balancing generation and load. When generation and demand drift apart, system frequency moves away from its nominal value (50 or 60 Hz). Grids rely on three hierarchical control layers — Primary , Secondary (AGC), and Tertiary — to arrest frequency deviation, restore the set-point and optimize generation dispatch. Related: Power System Stability — causes & mitigation Overview of primary, secondary and tertiary frequency control in power systems. ⚡ Primary Frequency Control (Droop Control) Primary control is a fast, local response implemented by generator governors (dro...

Breaker Schemes in Substations

Breaker Schemes in Substations — Types, Design, Advantages, Disadvantages, and Comparison Author: Engr. Aneel Kumar Figure 1: Infographic overview of breaker schemes commonly used in substations. Introduction The breaker scheme or busbar arrangement in a substation defines how incoming feeders, outgoing feeders, and power transformers are connected to the bus. The choice of scheme has a direct impact on system reliability, maintainability, safety, and cost . A simple bus scheme is economical but vulnerable to outages, while advanced schemes such as breaker-and-a-half or double-bus/double-breaker provide very high reliability but at much higher cost and design complexity. Engineers select breaker schemes considering fault tolerance, maintenance needs, space requirements, expansion possibilities, protection coordination, and capital investment . Below, we explain eac...

SYMMETRICAL COMPONENT ANALYSIS

Unbalanced three phase systems can be split into three balanced components, namely Positive Sequence (balanced and having the same phase sequence as the unbalanced supply), Negative Sequence (balanced and having the opposite phase sequence to the unbalanced supply) and Zero Sequence (balanced but having the same phase and hence no phase sequence). These are known as the Symmetrical Components or the Sequence Components and are shown in figure 2.10. The phase components are the addition of the symmetrical components and can be written as follows.  a = a 1 + a 2 + a 0 b = b 1 + b 2 + b 0 c = c 1 + c 2 + c 0 The unknown unbalanced system has three unknown magnitudes and three unknown angles with respect to the reference direction. Similarly, the combination of the 3 sequence components will also have three unknown magnitudes and three unknown angles with respect to the reference direction. Thus the original unbalanced system effectively has 3 complex unknown quan...

TYPES OF ELECTRIC LOADS

Devices that are connected to the power system are referred to as electrical loads. Toasters, refrigerators, bug zappers, and so on are considered electrical loads. There are three types of electrical loads. They vary according to their leading or lagging time relationship between voltage and current. The three load types are resistive, inductive, and capacitive. Each type has specific characteristics that make them unique. Understanding the differences between these load types will help explain how power systems can operate efficiently. Power system engineers, system operators, maintenance personnel, and others try to maximize system efficiency on a continuous basis by having a good understanding of the three types of loads. They understand how having them work together can minimize system losses, provide additional equipment capacity, and maximize system reliability. The three different types of load are summarized below. 1) RESISTIVE LOAD: The resistance in a wire (i.e., cond...

SOLIDLY GROUNDED NEUTRAL SYSTEMS

Solidly grounded systems are usually used in low voltage applications at 600 volts or less. In solidly grounded system, the neutral point is connected to earth. Solidly Neutral Grounding slightly reduces the problem of transient over voltages found on the ungrounded system and provided path for the ground fault current is in the range of 25 to 100% of the system three phase fault current.. However, if the reactance of the generator or transformer is too great, the problem of transient over voltages will not be solved. While solidly grounded systems are an improvement over ungrounded systems, and speed up the location of faults, they lack the current limiting ability of resistance grounding and the extra protection this provides. To maintain systems health and safe, Transformer neutral is grounded and grounding conductor must be extend from the source to the furthest point of the system within the same raceway or conduit. Its purpose is to maintain very low impedance to ground faults so...

ESSENTIAL ELEMENTS OF DIESEL POWER PLANT

FUEL SUPPLY SYSTEM OF DIESEL POWER PLANT It consists of storage tank, strainers, fuel transfer pump and all day fuel tanks. The fuel oil is supplied at the plant site by rail or road. The oil is stored in the storage tank. From the storage tank, oil is pumped to smaller all day tank at daily or short intervals. From this tank, fuel oil is passed through strainers to remove suspended impurities. The clean oil is injected into the engine by fuel injection pump. AIR INTAKE SYSTEM OF DIESEL POWER PLANT This system supplies necessary air to the engine for fuel combustion. It consists of pipes for the supply of fresh air to the engine manifold. Filters are provided to remove dust particles from air which may act as abrasive in the engine cylinder. Because a diesel engine requires close tolerances to achieve its compression ratio, and because most diesel engines are either turbocharged or supercharged, the air entering the engine must be clean, free of debris, and as cool as possible. ...

ADVANTAGES AND DISADVANTAGES OF CORONA EFFECT IN TRANSMISSION LINES | ELECTRICAL ENGINEERING GUIDE

Advantages and Disadvantages of Corona Effect in Power Systems In high-voltage overhead transmission lines , the corona effect plays a critical role in system performance. Corona occurs when the air around a conductor becomes ionized due to high electric stress. While often seen as a drawback because of power losses and interference , it also provides certain engineering benefits . This article explains the advantages and disadvantages of corona effect in detail, with examples relevant to modern electrical power systems. ✅ Advantages of Corona Effect Increase in Virtual Conductor Diameter Due to corona formation, the surrounding air becomes partially conductive, increasing the virtual diameter of the conductor. This reduces electrostatic stress between conductors and minimizes insulation breakdown risks. Related Reading: Electrostatic Fields in High Voltage Engineering Reduction of Transient Surges Corona acts like a natural cushion for sudden ...