Skip to main content

TYPES OF GROUND RELAYS

There are three basic types of relays that are used for ground relaying; overcurrent relays, distance relays, and pilot relays. Ground relays are almost always completely independent of phase relays, even though any fault current, including ground fault current, will flow through one or more of the phase relays. The ground relays, however, can be provided with much greater sensitivity to the zero-sequence currents by using higher tap settings. This means that the ground relays will pick up much faster than phase relays for a fault involving the ground.

1) OVERCURRENT RELAYS:
Directional or non-directional overcurrent relays are widely used at most voltage levels because of their low cost and reliable service record. Many relay engineers prefer an overcurrent relay with an inverse or very inverse time-current characteristic. This means that the pickup will be very fast for close-in faults and delayed for faults at the end of the transmission line.

This delay makes coordination with adjacent lines relatively easy because of the rapid change in fault current for the more remote faults. The ground relay must coordinate with bus differential relays, as well as ground relays on any outgoing lines at the remote end.

In systems with multiple grounds, which is usually the case, the ground overcurrent relays will need to be directional relays. The ground relays in a looped system must be coordinated all around the loop in both directions, in exactly the same way that phase relays are coordinated. This is a cut and try process.
Instantaneous overcurrent relays are usually applied to supplement the ground fault protection when overcurrent relays are used. Instantaneous ground relays can reduce the fault clearing time to about one cycle in many cases, for faults on a large fraction of the line length.

2) DISTANCE RELAYS:
Directional ground distance relays are responsive to impedance or reactance between the relay and the fault. These relays, although more expensive than overcurrent relays, can provide almost instantaneous protection for most of the line length. For many years, distance relays were not widely used for ground protection due to the inherent problem of measuring zero-sequence impedance or reactance in the presence of a fault. Ground faults usually involve fault resistance of widely varying magnitude. This may prevent the relay from responding to a ground fault. Some relay engineers back up ground distance relays with overcurrent relays to make sure that all faults are recognized in a timely way. Many of the problems associated with ground distance relays have been solved by newer devices, making this a good alternative where overcurrent or directional overcurrent coordination is a problem.

3) PILOT RELAYS:
Pilot relaying is used for ground protection in special cases where the other methods are inadequate for reasons of security or dependability. Pilot relays use either directional comparison or phase comparison to determine if the fault is within the protected zone. This might be a good solution for a three-terminal line, for example, where other types of relays are difficult to coordinate. Pilot relaying is sometimes selected on the more important lines because of the high speed and security offered by the pilot schemes. Some engineers argue that pilot relays are not required for ground fault protection, but should be used where stability or other considerations make it necessary to have both terminals of the transmission line tripped at the same time.

Comments

Popular posts from this blog

PRIMARY SECONDARY AND TERTIARY FREQUENCY CONTROL IN POWER SYSTEMS

Primary, Secondary and Tertiary Frequency Control in Power Systems Author: Engr. Aneel Kumar Keywords: frequency control, primary frequency control, automatic generation control (AGC), tertiary control, load-frequency control, grid stability. Frequency control keeps the power grid stable by balancing generation and load. When generation and demand drift apart, system frequency moves away from its nominal value (50 or 60 Hz). Grids rely on three hierarchical control layers — Primary , Secondary (AGC), and Tertiary — to arrest frequency deviation, restore the set-point and optimize generation dispatch. Related: Power System Stability — causes & mitigation Overview of primary, secondary and tertiary frequency control in power systems. ⚡ Primary Frequency Control (Droop Control) Primary control is a fast, local response implemented by generator governors (dro...

Breaker Schemes in Substations

Breaker Schemes in Substations — Types, Design, Advantages, Disadvantages, and Comparison Author: Engr. Aneel Kumar Figure 1: Infographic overview of breaker schemes commonly used in substations. Introduction The breaker scheme or busbar arrangement in a substation defines how incoming feeders, outgoing feeders, and power transformers are connected to the bus. The choice of scheme has a direct impact on system reliability, maintainability, safety, and cost . A simple bus scheme is economical but vulnerable to outages, while advanced schemes such as breaker-and-a-half or double-bus/double-breaker provide very high reliability but at much higher cost and design complexity. Engineers select breaker schemes considering fault tolerance, maintenance needs, space requirements, expansion possibilities, protection coordination, and capital investment . Below, we explain eac...

SYMMETRICAL COMPONENT ANALYSIS

Unbalanced three phase systems can be split into three balanced components, namely Positive Sequence (balanced and having the same phase sequence as the unbalanced supply), Negative Sequence (balanced and having the opposite phase sequence to the unbalanced supply) and Zero Sequence (balanced but having the same phase and hence no phase sequence). These are known as the Symmetrical Components or the Sequence Components and are shown in figure 2.10. The phase components are the addition of the symmetrical components and can be written as follows.  a = a 1 + a 2 + a 0 b = b 1 + b 2 + b 0 c = c 1 + c 2 + c 0 The unknown unbalanced system has three unknown magnitudes and three unknown angles with respect to the reference direction. Similarly, the combination of the 3 sequence components will also have three unknown magnitudes and three unknown angles with respect to the reference direction. Thus the original unbalanced system effectively has 3 complex unknown quan...

TYPES OF ELECTRIC LOADS

Devices that are connected to the power system are referred to as electrical loads. Toasters, refrigerators, bug zappers, and so on are considered electrical loads. There are three types of electrical loads. They vary according to their leading or lagging time relationship between voltage and current. The three load types are resistive, inductive, and capacitive. Each type has specific characteristics that make them unique. Understanding the differences between these load types will help explain how power systems can operate efficiently. Power system engineers, system operators, maintenance personnel, and others try to maximize system efficiency on a continuous basis by having a good understanding of the three types of loads. They understand how having them work together can minimize system losses, provide additional equipment capacity, and maximize system reliability. The three different types of load are summarized below. 1) RESISTIVE LOAD: The resistance in a wire (i.e., cond...

SOLIDLY GROUNDED NEUTRAL SYSTEMS

Solidly grounded systems are usually used in low voltage applications at 600 volts or less. In solidly grounded system, the neutral point is connected to earth. Solidly Neutral Grounding slightly reduces the problem of transient over voltages found on the ungrounded system and provided path for the ground fault current is in the range of 25 to 100% of the system three phase fault current.. However, if the reactance of the generator or transformer is too great, the problem of transient over voltages will not be solved. While solidly grounded systems are an improvement over ungrounded systems, and speed up the location of faults, they lack the current limiting ability of resistance grounding and the extra protection this provides. To maintain systems health and safe, Transformer neutral is grounded and grounding conductor must be extend from the source to the furthest point of the system within the same raceway or conduit. Its purpose is to maintain very low impedance to ground faults so...

ESSENTIAL ELEMENTS OF DIESEL POWER PLANT

FUEL SUPPLY SYSTEM OF DIESEL POWER PLANT It consists of storage tank, strainers, fuel transfer pump and all day fuel tanks. The fuel oil is supplied at the plant site by rail or road. The oil is stored in the storage tank. From the storage tank, oil is pumped to smaller all day tank at daily or short intervals. From this tank, fuel oil is passed through strainers to remove suspended impurities. The clean oil is injected into the engine by fuel injection pump. AIR INTAKE SYSTEM OF DIESEL POWER PLANT This system supplies necessary air to the engine for fuel combustion. It consists of pipes for the supply of fresh air to the engine manifold. Filters are provided to remove dust particles from air which may act as abrasive in the engine cylinder. Because a diesel engine requires close tolerances to achieve its compression ratio, and because most diesel engines are either turbocharged or supercharged, the air entering the engine must be clean, free of debris, and as cool as possible. ...

ADVANTAGES AND DISADVANTAGES OF CORONA EFFECT IN TRANSMISSION LINES | ELECTRICAL ENGINEERING GUIDE

Advantages and Disadvantages of Corona Effect in Power Systems In high-voltage overhead transmission lines , the corona effect plays a critical role in system performance. Corona occurs when the air around a conductor becomes ionized due to high electric stress. While often seen as a drawback because of power losses and interference , it also provides certain engineering benefits . This article explains the advantages and disadvantages of corona effect in detail, with examples relevant to modern electrical power systems. ✅ Advantages of Corona Effect Increase in Virtual Conductor Diameter Due to corona formation, the surrounding air becomes partially conductive, increasing the virtual diameter of the conductor. This reduces electrostatic stress between conductors and minimizes insulation breakdown risks. Related Reading: Electrostatic Fields in High Voltage Engineering Reduction of Transient Surges Corona acts like a natural cushion for sudden ...