Skip to main content

TYPES OF GROUND RELAYS

There are three basic types of relays that are used for ground relaying; overcurrent relays, distance relays, and pilot relays. Ground relays are almost always completely independent of phase relays, even though any fault current, including ground fault current, will flow through one or more of the phase relays. The ground relays, however, can be provided with much greater sensitivity to the zero-sequence currents by using higher tap settings. This means that the ground relays will pick up much faster than phase relays for a fault involving the ground.

1) OVERCURRENT RELAYS:
Directional or non-directional overcurrent relays are widely used at most voltage levels because of their low cost and reliable service record. Many relay engineers prefer an overcurrent relay with an inverse or very inverse time-current characteristic. This means that the pickup will be very fast for close-in faults and delayed for faults at the end of the transmission line.

This delay makes coordination with adjacent lines relatively easy because of the rapid change in fault current for the more remote faults. The ground relay must coordinate with bus differential relays, as well as ground relays on any outgoing lines at the remote end.

In systems with multiple grounds, which is usually the case, the ground overcurrent relays will need to be directional relays. The ground relays in a looped system must be coordinated all around the loop in both directions, in exactly the same way that phase relays are coordinated. This is a cut and try process.
Instantaneous overcurrent relays are usually applied to supplement the ground fault protection when overcurrent relays are used. Instantaneous ground relays can reduce the fault clearing time to about one cycle in many cases, for faults on a large fraction of the line length.

2) DISTANCE RELAYS:
Directional ground distance relays are responsive to impedance or reactance between the relay and the fault. These relays, although more expensive than overcurrent relays, can provide almost instantaneous protection for most of the line length. For many years, distance relays were not widely used for ground protection due to the inherent problem of measuring zero-sequence impedance or reactance in the presence of a fault. Ground faults usually involve fault resistance of widely varying magnitude. This may prevent the relay from responding to a ground fault. Some relay engineers back up ground distance relays with overcurrent relays to make sure that all faults are recognized in a timely way. Many of the problems associated with ground distance relays have been solved by newer devices, making this a good alternative where overcurrent or directional overcurrent coordination is a problem.

3) PILOT RELAYS:
Pilot relaying is used for ground protection in special cases where the other methods are inadequate for reasons of security or dependability. Pilot relays use either directional comparison or phase comparison to determine if the fault is within the protected zone. This might be a good solution for a three-terminal line, for example, where other types of relays are difficult to coordinate. Pilot relaying is sometimes selected on the more important lines because of the high speed and security offered by the pilot schemes. Some engineers argue that pilot relays are not required for ground fault protection, but should be used where stability or other considerations make it necessary to have both terminals of the transmission line tripped at the same time.

Comments

Popular posts from this blog

AUTO TRANSFORMER TAP CHANGING

Figure shows diagrammatically auto-transformer tap changing. Here, a mid-tapped auto-transformer or reactor is used. One of the lines is connected to its mid-tapping. One end, say a of this transformer is connected to a series of switches across the odd tappings and the other end b is connected to switches across even tappings. A short-circuiting switch S is connected across the auto-transformer and remains in the closed position under normal operation. In the normal operation, there is no inductive voltage drop across the auto-transformer. Referring to Figure, it is clear that with switch 5 closed, minimum secondary turns are in the circuit and hence the output voltage will be the lowest. On the other hand, the output voltage will be maximum when switch 1 is closed. Suppose now it is desired to alter the tapping point from position 5 to position 4 in order to raise the output voltage. For this purpose, short-circuiting switch S is opened, switch 4 is closed, then switch 5 is op...

COMPONENTS OF HIGH VOLTAGE DC TRANSMISSION SYSTEM

Figure: A schematic of a bipolar HVDC system identifying main components

PLUG REVERSING OF CAPACITOR START MOTORS

The capacitor start motors suffer from the disadvantage that they are not easily reversible due to the centrifugal switch connected in the auxiliary winding. The motor cannot be instantaneously reversed by simple control as the auxiliary winding remains disconnected till the motor comes near to zero speed. However, by proper design of the control circuit the motor can be made instantly reversible. This is accomplished by using an electromagnetic relay along with a special two contact centrifugal switch as shown in Figure. The circuit shown in Figure is for a small hoist using a capacitor start motor. The upper and lower limits of travel are controlled by two limit switches viz. LSU and LSD. When UP-push button is pressed, contactor U gets energized. Its contacts U 1  and U 2  energies the main winding. Closing of its contact U 3  causes relay R to get energized through the centrifugal switch contacts A—B. After the energization of relay R auxiliary winding gets ene...

BENEFITS OF UTILIZING FACTS DEVICES

The advantages of using FACTS devices in electrical transmission systems are described below. 1. MORE UTILIZATION OF EXISTING TRANSMISSION SYSTEM In all the countries, the power demand is increasing day by day to transfer the electrical power and controlling the load flow of the transmission system is very necessary this can be achieved by more load centers which can change frequently. Addition of new transmission line is very costly to take the increased load on the system; in that case FACTS devices are much economical to meet the increased load on the same transmission lines. 2. MORE INCREASED TRANSIENT AND DYNAMIC STABILITY OF THE SYSTEM The Long transmission lines are inter-connected with grids to absorb the changing the loading of the transmission line and it is also seen that there should be no line fault creates in the line / transmission system. By doing this the power flow is reduced and transmission line can be trip. By the use of FACTS devices high power t...

PRIMARY SECONDARY AND TERTIARY FREQUENCY CONTROL IN POWER SYSTEMS

Primary, Secondary and Tertiary Frequency Control in Power Systems Author: Engr. Aneel Kumar Keywords: frequency control, primary frequency control, automatic generation control (AGC), tertiary control, load-frequency control, grid stability. Frequency control keeps the power grid stable by balancing generation and load. When generation and demand drift apart, system frequency moves away from its nominal value (50 or 60 Hz). Grids rely on three hierarchical control layers — Primary , Secondary (AGC), and Tertiary — to arrest frequency deviation, restore the set-point and optimize generation dispatch. Related: Power System Stability — causes & mitigation Overview of primary, secondary and tertiary frequency control in power systems. ⚡ Primary Frequency Control (Droop Control) Primary control is a fast, local response implemented by generator governors (dro...

AC Transmission Line and Reactive Power Compensation: A Detailed Overview

  Introduction The efficient operation of modern power systems depends significantly on the management of AC transmission lines and reactive power. Reactive power compensation is a vital technique for maintaining voltage stability, improving power transfer capability, and reducing system losses. This article explores the principles of AC transmission lines, the need for reactive power compensation, and its benefits in power systems. Keywords: Reactive Power Compensation Benefits, STATCOM vs SVC Efficiency, Power Transmission Stability Solutions, Voltage Stability in Long-Distance Grids, Dynamic Reactive Power Compensation.      Fundamentals of AC Transmission Lines AC transmission lines are the backbone of modern power systems, connecting generation stations to distribution networks. They have distributed electrical parameters such as resistance ( R R R ), inductance ( L L ), capacitance ( C C ), and conductance ( G G ) along their length. These parameters influence ...

Breaker Schemes in Substations

Breaker Schemes in Substations — Types, Design, Advantages, Disadvantages, and Comparison Author: Engr. Aneel Kumar Figure 1: Infographic overview of breaker schemes commonly used in substations. Introduction The breaker scheme or busbar arrangement in a substation defines how incoming feeders, outgoing feeders, and power transformers are connected to the bus. The choice of scheme has a direct impact on system reliability, maintainability, safety, and cost . A simple bus scheme is economical but vulnerable to outages, while advanced schemes such as breaker-and-a-half or double-bus/double-breaker provide very high reliability but at much higher cost and design complexity. Engineers select breaker schemes considering fault tolerance, maintenance needs, space requirements, expansion possibilities, protection coordination, and capital investment . Below, we explain eac...