INSULATING SOLIDS

Solid insulating materials can be classified into two main categories: organic and inorganic. There are a large number of solid inorganic insulants available, including the following:

• ALUMINA: produced by heating aluminum hydroxide or oxyhydroxide; it is widely used as a filler for ceramic insulators. Further heating yields the corundum structure, which in its sapphire form is used for dielectric substrates in microcircuit applications.

• PORCELAIN: a multiphase ceramic material that is obtained by heating aluminum silicates until a mullite phase is formed. Because mullite is porous, its surface must be glazed with a high-melting-point glass to render it smooth and impervious to contaminants for use in overhead line insulators.

• ELECTRICAL-GRADE GLASSES: which tend to be relatively lossy at high temperatures. At low temperatures, however, they are suitable for use in overhead line insulators and in transformer, capacitor, and circuit breaker bushings. At high temperatures, their main application lies with incandescent and fluorescent lamps as well as electronic tube envelopes.

• MICA: a layer-type dielectric (mica films are obtained by splitting mica blocks). The extended two-dimensionally layered strata of mica prevents the formation of conductive pathways across the substance, resulting in a high dielectric strength. It has excellent thermal stability and, because of its inorganic nature, is highly resistant to partial discharges. It is used in sheet, plate, and tape forms in rotating machines and transformer coils.
Solid organic dielectrics consist of large polymer molecules, which generally have molecular weights in excess of 600. Primarily (with the notable exception of paper, which consists of cellulose that is comprised of a series of glucose units), organic dielectric materials are synthetically derived. Some of the more common insulating materials of this type include:

• POLYETHYLENE (PE): perhaps one of the most common solid dielectrics. PE is extensively used as a solid dielectric extruded insulator in power and communication cables. Linear PE is classified as a low- (0.910 to 0.925), medium- (0.926 to 0.940), or high- (0.941 to 0.965) density polymer. Most of the PE used on extruded cables is of the cross-linked polyethylene type.

• ETHYLENE-PROPYLENE RUBBER (EPR): an amorphous elastomer that is synthesized from ethylene and propylene. It is used as an extrudent on cables where its composition has a filler content that usually exceeds 50% (comprising primarily clay, with smaller amounts of added silicate and carbon black). Dielectric losses are appreciably enhanced by the fillers, and, consequently, EPR is not suitable for extra-high-voltage applications. Its use is primarily confined to intermediate voltages (< 69 kV) and to applications where high cable flexibility (due to its inherent rubber properties) may be required.

• POLYPROPYLENE: which has a structure related to that of ethylene with one added methyl group. It is a thermoplastic material having properties similar to high-density PE, although because of its lower density, polypropylene has also a lower dielectric constant. Polypropylene has many electrical applications, both in bulk form as molded and extruded insulations, as well as in film form in taped capacitor, transformer, and cable insulations.

• EPOXY RESINS: which are characterized by low shrinkage and high mechanical strength. They can also be reinforced with glass fibers and mixed with mica flakes. Epoxy resins have many applications, including insulation of bars in the stators of rotating machines, solid-type transformers, and spacers for compressed-gas-insulated bus bars and cables.

Impregnated-paper insulation is one of the earliest insulating systems employed in electrical power apparatus and cables. Although many current designs use solid- or compressed-gas insulating systems, the impregnated-paper approach still constitutes one of the most reliable insulating techniques available. Proper impregnation of the paper results in a cavity-free insulating system, thereby eliminating the occurrence of partial discharges that inevitably lead to deterioration and breakdown of the insulating system. The liquid impregnates employed are either mineral oils or synthetic fluids.

Low-density cellulose papers have slightly lower dielectric losses, but the dielectric breakdown strength is also reduced. The converse is true for impregnated systems utilizing high-density papers. If the paper is heated beyond 200°C, the chemical structure of the paper breaks down, even in the absence of external oxygen, because the latter is readily available from within the cellulose molecule. To prevent this process from occurring, cellulose papers are ordinarily not used at temperatures above 100°C.

Comments

Popular posts from this blog

Auto Transformer Tap Changing

Auto Transformer Tap Changing: Working Principle, Switching Sequence and Applications Auto transformer tap changing is a practical method of adjusting transformer output voltage without unnecessarily interrupting the electrical supply. In power transmission and distribution networks, the load does not remain constant throughout the day. As load current changes, voltage drops across transformers, cables, feeders, and transmission lines also change. A tap-changing arrangement compensates for these variations by modifying the effective number of turns in the transformer winding. A reactor-type on-load tap changer uses a center-tapped reactor, selector switches, and a bypass or short-circuiting switch to transfer the load from one tap to the next. The reactor limits the circulating current during the transition, allowing the tap position to change while the transformer continues supplying the connected load. This article explains the auto transformer tap-changing working principle , switch...

PRIMARY SECONDARY AND TERTIARY FREQUENCY CONTROL IN POWER SYSTEMS

Primary, Secondary and Tertiary Frequency Control in Power Systems Author: Engr. Aneel Kumar Keywords: frequency control, primary frequency control, automatic generation control (AGC), tertiary control, load-frequency control, grid stability. Frequency control keeps the power grid stable by balancing generation and load. When generation and demand drift apart, system frequency moves away from its nominal value (50 or 60 Hz). Grids rely on three hierarchical control layers — Primary , Secondary (AGC), and Tertiary — to arrest frequency deviation, restore the set-point and optimize generation dispatch. Related: Power System Stability — causes & mitigation Overview of primary, secondary and tertiary frequency control in power systems. ⚡ Primary Frequency Control (Droop Control) Primary control is a fast, local response implemented by generator governors (dro...

Advantages of Per Unit System in Power System Analysis | Electrical Engineering

  Advantages of Per Unit System in Power System Analysis In electrical power engineering, the per unit (p.u.) system is one of the most widely used techniques for analyzing and modeling power systems. It is a method of expressing electrical quantities — such as voltage, current, power, and impedance — as fractions of chosen base values rather than their actual numerical magnitudes. This normalization technique provides a universal language for system calculations, minimizing errors, simplifying transformer modeling, and enabling consistency across multiple voltage levels. Because of these benefits, the per unit system is essential in fault analysis, load flow studies, transformer testing, and short-circuit calculations . ⚡ What is the Per Unit System? The per unit system is defined as: Q u a n t i t y ( p u ) = A c t u a l   V a l u e B a s e   V a l u e Quantity_{(pu)} = \dfrac{Actual \ Value}{Base \ Value} Q u an t i t y ( p u ) ​ = B a se   ...

Top 10 Transformer Manufacturers in the World

Top 10 Transformer Manufacturers in the World Transformers are among the most important and expensive assets in electrical generation, transmission, distribution, renewable-energy, industrial, infrastructure, and data-center projects. A power transformer changes voltage and current levels through electromagnetic induction while maintaining the system frequency. Generator step-up transformers increase generating-station voltage for efficient transmission, while grid and distribution transformers reduce voltage progressively before electricity reaches industrial, commercial, and residential consumers. The global transformer market continues to expand because of grid modernization, renewable-energy integration, industrial electrification, data-center development, replacement of aging equipment, and construction of new transmission infrastructure. One 2026 market assessment estimates that the global transformer market could grow from approximately USD 72.5 billion in 2026 to about USD 137....

Reversing the Direction of a Universal Motor: Methods and Circuit Diagram

How to Reverse the Direction of Rotation of a Universal Motor Introduction A universal motor is a high-speed electric motor that can operate on either an alternating-current or direct-current supply when designed for the applicable voltage and frequency. It is widely used in portable electric drills, grinders, vacuum cleaners, mixers, sewing machines, small machine tools, and other equipment requiring high starting torque and compact construction. The direction of rotation of a universal motor can be changed by reversing the direction of current through either the armature winding or the field winding relative to the other. The current must be reversed in only one of these windings. If the connections of both windings are reversed simultaneously, the relative direction of the field flux and armature current remains unchanged, and the motor continues rotating in the same direction. Before studying the reversing methods, readers may review the Universal Series Motors Electric Motors and...

MAIN AND PILOT EXCITER

Main Exciter The exciter (sometimes called the main exciter) is a synchronous generator that has its stator and rotor windings inverted. Its field winding is fixed in the stator, and the rotor carries the armature or AC . In addition the rotor carries the semiconductor bridge rectifier that converts the armature voltages to a two-wire DC voltage system. The AC voltages and currents in the armature are often alternating at a higher frequency than those in the main generator, e.g. 400 Hz. The higher frequency improves the speed of response of the exciter. The DC power circuit is coupled to the field of the main generator by the use of insulated conductors that pass coaxially inside the rotor of the exciter and the rotor of the main generator. This eliminates the use of slip rings, which were traditionally used before shaft mounted rectifiers were developed. A slight disadvantage of this technique is that the derivative feedback cannot be taken from the output of the exciter. Howeve...

Top 10 Power-System Protection Relays and Their Applications

A power system must continuously transport electrical energy while remaining within the thermal, mechanical, and insulation limits of generators, transformers, busbars, transmission lines, cables, motors, and switchgear. When a short circuit, insulation failure, overload, abnormal voltage, frequency disturbance, or equipment malfunction occurs, the affected section must be disconnected quickly. A delay of even a fraction of a second during a severe fault can increase equipment damage, expose personnel to danger, and threaten the stability of the wider electrical network. A protection relay monitors electrical quantities such as current, voltage, frequency, phase angle, impedance, power, and temperature. When measured values meet predefined operating criteria, the relay initiates an alarm, trips a circuit breaker, starts an automatic control action, or blocks an unsafe operation. The three basic duties of a protection relay are: Measure electrical quantities Detect abnormal or fault co...