Skip to main content

GENERATOR ROTOR PROTECTION

There are several different types of rotor protection, each type guarding the rotor from a particular type of fault. From this viewpoint, the protection against unbalanced loading, using negative sequence relays, can be considered a type of rotor protection since the effect of negative sequence currents is likely to result in rotor damage.

1) SHORTED FIELD WINDING PROTECTION

Shorted turns in the generator field winding have the potential for distorting the field across the air gap, as illustrated in Figure 1. This is due to the unsymmetrical ampere turns of mmf in different parts of the field winding. If the air gap flux is badly distorted, there can be much distorted forces acting on the rotor, since the forces vary as the square of the flux density.
Once there are unequal forces on opposite sides of the rotor, there is tendency for the rotor to warp. The unbalanced force can be very large, as much as 50 to 100 tons, tending to warp the rotor. In some cases the rotor may be displaced enough to contact the stator iron core.

Figure 1: Field flux pattern with shorted field
Another effect of the unbalanced forces on the rotor is severe vibration, which may cause damage to bearings. The machine can be spared from serious damage by vibration detectors, which can alarm the operator or trip the unit. The mechanism that causes the shorted winding is often due to grounding of the winding at two different places.

2) GROUNDED FIELD WINDING

The field winding of a synchronous machine is usually floating with respect to ground. A single ground fault, therefore, does not draw any fault current, although it does stress the insulation in portions of the winding. The real danger is a second ground, which can set up significant forces. Dual grounds can also draw very large currents and may cause extensive damage to the field conductor and rotor steel. The best way to prevent this from occurring is to detect the first ground, thereby preventing a more serious chain of events. The generator main and field breakers should be tripped on the occurrence of the first ground. The exception is in attended stations, where the unit trip may be delayed until a more convenient time to schedule the repair. During this period, any unusual vibration should immediately trip the unit. It is best to not trip the turbine following a rotor ground fault and tripping of the generator and field. The rotor has better cooling when running at rated speed, and the excess heat is carried away as the generator continues to run for several minutes at rated speed. Allowing the unit to coast down also introduces the danger of aggravated vibration due to natural modal frequencies of vibration, which may be worse due to the rotor distortion.

There are several methods of detecting a rotor circuit ground. The methods, shown in Figure 2, are summarized as

1. Potentiometer method
2. AC injection method
3. DC injection method

Figure 2: Methods of detecting field winding grounds. (a) Potentiometer method. (b) AC injection method. (c) DC injection method.
The POTENTIOMETER METHOD measures the voltage to ground of a center tapped resistor, connected across the exciter output voltage. If some point in the winding becomes grounded, there will be a potential between that point and the point to which the voltage relay is connected.

The only problem is that, should a point very close to the center of the winding become grounded, the center tapped potentiometer would not detect it. To check that this has not happened, a manual switch is arranged to move the test point from the center to some other point along the resistor. The operator can check this periodically to ensure that the system is sound.

A better method is the AC INJECTION METHOD, which connects an AC voltage to the field winding through a capacitor. Should any point on the field winding become grounded, the circuit will be complete and the relay will trip. This system has no blind point. There is a disadvantage, however, in that some current will flow through the capacitance from the field winding to the rotor body, through the rotor body, the bearings, and to ground. This has the potential of causing erosion of the metal in the bearings.

A still better method is the DE INJECTION METHOD. The de output of the transformer-rectifier unit is connected to bias the positive side of the field circuit to a negative voltage relative to ground. A ground at any point on the field winding will complete the circuit to the grounded side of the relay. The relay is a sensitive current relay in this case, but must not be so sensitive that it will trip due to normal insulation leakage current. The current through the relay is limited by the high impedance of the rectifier.

A special problem is presented in the case of the brushless exciter. This exciter is an alternator-rectifier exciter that is physically on the rotor and rotating at synchronous speed.

The field for the alternator is stationary. The basis of the design is that there is no need for brushes between the field winding and the casing of the machine. In this type of exciter, there is usually no access to the field circuit; therefore, the previous types of ground detectors will not work. The only portion of the excitation system that is accessible to the outside is the field of the alternator exciter. Any severe fault oil the field winding will require excess field current, hence excess excitation for the alternator rectifier. The backup is a vibration monitor that can take action if a severe field winding fault occurs.

3) OPEN FIELD WINDING

Field winding open circuits are rare, but prompt action is required when an open occurs because it will be accompanied with arcing that can do great damage to the rotor iron. An open circuit that does not involve ground will cause a sudden drop in field current that can be detected by a loss-of-field relay.

4) OVERHEATING OF THE FIELD WINDING

The temperature of the field winding can be monitored by an ohmmeter type of detector that measures the winding resistance of the field. Such an instrument is often calibrated in temperature, rather than ohms, for a direct estimation of the winding temperature.

Comments

Popular posts from this blog

PRIMARY SECONDARY AND TERTIARY FREQUENCY CONTROL IN POWER SYSTEMS

Primary, Secondary and Tertiary Frequency Control in Power Systems Author: Engr. Aneel Kumar Keywords: frequency control, primary frequency control, automatic generation control (AGC), tertiary control, load-frequency control, grid stability. Frequency control keeps the power grid stable by balancing generation and load. When generation and demand drift apart, system frequency moves away from its nominal value (50 or 60 Hz). Grids rely on three hierarchical control layers — Primary , Secondary (AGC), and Tertiary — to arrest frequency deviation, restore the set-point and optimize generation dispatch. Related: Power System Stability — causes & mitigation Overview of primary, secondary and tertiary frequency control in power systems. ⚡ Primary Frequency Control (Droop Control) Primary control is a fast, local response implemented by generator governors (dro...

CASCADED TRANSFORMERS METHOD FOR GENERATING AC HIGH VOLTAGE

High-Frequency AC High Voltage Generation Using Cascaded Transformers Author: Engr. Aneel Kumar Figure 1: Infographic representation of cascaded transformers method for generating high AC voltages. Introduction In high voltage engineering , generating very high alternating current (AC) voltages is essential for testing equipment like insulators, circuit breakers, power cables, and other apparatus. One common and effective method for producing such voltages is the cascaded transformers method . This technique uses a series connection of specially designed test transformers , where the secondary of one transformer feeds the primary of the next. In this way, voltages are built up step by step, achieving levels in the range of hundreds of kilovolts (kV) or even megavolts (MV). Working Principle The principle of cascaded connection relies on the fact that each...

ADVANTAGES AND DISADVANTAGES OF CORONA EFFECT IN TRANSMISSION LINES | ELECTRICAL ENGINEERING GUIDE

Advantages and Disadvantages of Corona Effect in Power Systems In high-voltage overhead transmission lines , the corona effect plays a critical role in system performance. Corona occurs when the air around a conductor becomes ionized due to high electric stress. While often seen as a drawback because of power losses and interference , it also provides certain engineering benefits . This article explains the advantages and disadvantages of corona effect in detail, with examples relevant to modern electrical power systems. ✅ Advantages of Corona Effect Increase in Virtual Conductor Diameter Due to corona formation, the surrounding air becomes partially conductive, increasing the virtual diameter of the conductor. This reduces electrostatic stress between conductors and minimizes insulation breakdown risks. Related Reading: Electrostatic Fields in High Voltage Engineering Reduction of Transient Surges Corona acts like a natural cushion for sudden ...

REVERSING DIRECTION OF ROTATION OF UNIVERSAL MOTOR

The direction of rotation of a universal motor can be changed by either: (i) Reversing the field connection with respect to those of armature; or (ii) By using two field windings wound on the core in opposite directions so that the one connected in series with armature gives clockwise rotation, while the other in series with the armature gives counterclockwise rotation. The second method, i.e, the two field method is used in applications such as motor operated rheostats and servo systems. This method has somewhat simpler connections than the first method. For simple applications like portable drills etc. manual switches are frequently used for reversing the direction of rotation of the motor. Figure  1 (a and b) shows how a DPDT (Double Pole Double Throw) switch and a three position switch may be used for reversing the direction of rotation of single field and double field type of motors respectively. Figure 1 Reversing of a universal motor (a) Armature re...

Advantages of Per Unit System in Power System Analysis | Electrical Engineering

  Advantages of Per Unit System in Power System Analysis In electrical power engineering, the per unit (p.u.) system is one of the most widely used techniques for analyzing and modeling power systems. It is a method of expressing electrical quantities — such as voltage, current, power, and impedance — as fractions of chosen base values rather than their actual numerical magnitudes. This normalization technique provides a universal language for system calculations, minimizing errors, simplifying transformer modeling, and enabling consistency across multiple voltage levels. Because of these benefits, the per unit system is essential in fault analysis, load flow studies, transformer testing, and short-circuit calculations . ⚡ What is the Per Unit System? The per unit system is defined as: Q u a n t i t y ( p u ) = A c t u a l   V a l u e B a s e   V a l u e Quantity_{(pu)} = \dfrac{Actual \ Value}{Base \ Value} Q u an t i t y ( p u ) ​ = B a se   ...

PRINCIPLE OF OPERATION OF UNIFIED POWER FLOW CONTROLLER UPFC

UPFC consist of two back to back converters named VSC1 and VSC2, are operated from a DC link provided by a dc storage capacitor. These arrangements operate as an ideal ac to ac converter in which the real power can freely flow either in direction between the ac terminals of the two converts and each converter can independently generate or absorb reactive power as its own ac output terminal. Figure: Basic UPFC scheme One VSC is connected to in shunt to the transmission line via a shunt transformer and other one is connected in series through a series transformer. The DC terminal of two VSCs is coupled and this creates a path for active power exchange between the converters. VSC provide the main function of UPFC by injecting a voltage with controllable magnitude and phase angle in series with the line via an injection transformer. This injected voltage act as a synchronous ac voltage source. The transmission line current flows through this voltage source resulting in reactive an...

Types of Transmission Towers in Saudi Electricity Company (SEC) – NGSA Standards

 The Kingdom of Saudi Arabia (KSA) is rapidly expanding its energy infrastructure projects to meet the growing demand for electricity. At the heart of this growth lies the high voltage transmission network , which delivers reliable power from generation plants to cities, industries, and remote areas. To ensure safety and efficiency, the Saudi Electricity Company (SEC) follows strict NGSA (National Grid Saudi Arabia) standards for designing and selecting transmission towers . These lattice steel towers are engineered to withstand extreme desert conditions, high wind loads, and long transmission spans. In this article, we will explore the different types of transmission towers in Saudi Arabia , their applications, and how they contribute to the power transmission system design . Why Transmission Towers Are Crucial in Power Grid Development Every kilometer of transmission line construction requires careful planning. The right tower design ensures: Stable support for 69k...