Skip to main content

THREE PHASE TRANSFORMER WINDING CONNECTIONS

A three-phase transformer bank can be easily created by using three single-phase transformers. The two sides of these three transformers can be either connected in a wye or a delta configuration, thus allowing four possible types of connections. These are:

• WYE WYE:

With the wye-wye (Y-Y) connection, the secondary side is in phase with the primary circuit, and the ratio of primary to secondary voltage is the same as the ratio of turns in each of the phases. A possible connection is shown in Figure 1. Power distribution circuits supplied from a wye-wye bank often create series disturbances in communication circuits (e.g., telephone interference) in their immediate vicinity. One of the advantages of this connection is that when a system is changed from a delta to a four-wire wye to increase system capacity, existing transformers can be used.
Figure 1 Y-Y transformer with 0° phase shift between the primary and the secondary sides. 

• WYE-DELTA:

In the Y-Δ connection, there is a 30° phase angle shift between the primary and secondary sides. The phase angle difference can be made either lagging or leading, depending on the external connections of the transformer bank.

The case with the primary side lagging is shown in Figure 2, and the case with the primary side leading is shown in Figure 3. The transformation ratio is times the ratio of turns in each of the phases.
Figure 2 Y-Δ transformer with the primary side lagging the secondary side by 30°.
Figure 3 Y-Δ transformer with the primary side leading the secondary side by 30°.

• DELTA-WYE:

With the Δ-Y connection, the neutral of the secondary wye can be grounded and single-phase loads connected across the phase and the neutral conductor.

Three-phase loads are connected across the phases. The phasor relationship between the primary and the secondary sides is shown in Figure 4. The transformation ratio is 1/√3 times the ratio of turns in each of the phases.
Figure 4 Δ-Y transformer with the primary side leading the secondary side by 30°.

• DELTA-DELTA:

The Δ-Δ connection does not cause a phase shift between the primary and the secondary sides. The phasor relationship of this transformer is shown in Figure 5. The transformation ratio is equal to the ratio of the turns in each of the phases. There is no problem from third-harmonic over voltage or telephone interference because such disturbances get trapped in the delta and do not pass into the lines.
Figure 5 Δ-Δ transformer with 0° phase shift between the primary and the secondary sides.
Although these four configurations are the most common ones used, other arrangements are possible, including:

• OPEN-DELTA:

An advantage of the Δ-Δ connection is that if one of the single- phase transformers becomes damaged or is removed for maintenance, the remaining two can be operated in a so-called open-delta connection. Because the currents in each of the two remaining transformers are the same as the line current, each transformer carries times the current it was carrying in the closed-delta connection. The open-delta bank continues to deliver three-phase currents and voltages in their correct phase relationship. To keep the transformers from being overloaded, however, it is necessary to reduce the line currents by approximately 1/√3 .

• SCOTT OR T-CONNECTION:

The Scott or T-connection is used when a two-phase (or a transformed three-phase) supply is needed from a three-phase system. In general, the T-connection is used for deriving a three-phase transformation, and the Scott connection is mainly used for obtaining a two-phase output. The two connections are similar in basic design. Either connection requires two specially wound single-phase transformers. The main transformer has a 50 percent tap on the primary winding, whereas the other transformer, called the teaser transformer, has an 86.6 percent tap. The main transformer is connected between two primary lines, whereas the teaser transformer is connected from the center tap of the main transformer to the third primary line. The secondary sides of the transformers provide two-phase service. A T-connection is shown in Figure 6.
Figure 6 The T connection for a three-phase to two-phase transformation.

Comments

Popular posts from this blog

BREAKDOWN VOLTAGE AND DIELECTRIC STRENGTH

An insulator or dielectric is a substance within which there are no mobile electrons necessary for electric conduction. However, when the voltage applied to such an insulator exceeds a certain value, then it breaks down and allows a heavy electric current (much larger than the usual leakage current) to flow through it. If the insulator is a solid medium, it gets punctured or cracked. The disruptive or breakdown voltage of an insulator is the minimum voltage required to break it down. Dielectric strength of an insulator or dielectric medium is given by the maximum potential difference which a unit thickness of the medium can withstand without breaking down. In other words, the dielectric strength is given by the potential gradient necessary to cause breakdown of an insulator. Its unit is volt/meter (V/m) although it is usually expressed in KV/mm. For example, when we say that the dielectric strength of air is 3 KV/mm, then it means that the maximum PD which one mm thickness of ...

EQUIPMENT OF STEAM POWER STATION

A modern steam power station is highly complex and has numerous equipment and auxiliaries. However, the most important constituents of a steam power station are: 1. Steam generating equipment 2. Condenser 3. Prime mover 4. Water treatment plant 5. Electrical equipment. 1. STEAM GENERATING EQUIPMENT: This is an important part of steam power station. It is concerned with the generation of superheated steam and includes such items as boiler, boiler furnace, super heater, economizer, air pre-heater and other heat reclaiming devices. (I) BOILER : A boiler is closed vessel in which water is converted into steam by utilizing the heat of coal combustion. Steam boilers are broadly classified into the following two types: (a) Water tube boilers (b) Fire tube boilers In a water tube boiler, water flows through the tubes and the hot gases of combustion flow over these tubes. On the other hand, in a fire tube boiler, the hot products of combustion pass through the tubes surrounded by water. Wate...

TYPES OF SINGLE PHASE MOTORS

Single phase motors are manufactured in fractional kilowatt range to be operated on single phase supply and for use in numerous applications like ceiling fans, refrigerators, food mixers, hair driers, portable drills, vacuum cleaners, washing machines, sewing machines, electric shavers, office machinery etc. Single phase motors are manufactured in different types to meet the requirements of various applications. Single phase motors are classified on the basis of their construction and starting methods employed. The main types of single phase motors are: (a) Induction motors (b) Synchronous motors (c) Commutator motors The various types of motors under each class are shown as under: Repulsion, repulsion induction and reluctance start motors are not used these days, they have been largely replaced by split phase motors with special capacitors which can be designed to perform equally well as repulsion types. In addition they offer such advantages as lower cost and trouble fr...

Advantages of Per Unit System in Power System Analysis | Electrical Engineering

  Advantages of Per Unit System in Power System Analysis In electrical power engineering, the per unit (p.u.) system is one of the most widely used techniques for analyzing and modeling power systems. It is a method of expressing electrical quantities — such as voltage, current, power, and impedance — as fractions of chosen base values rather than their actual numerical magnitudes. This normalization technique provides a universal language for system calculations, minimizing errors, simplifying transformer modeling, and enabling consistency across multiple voltage levels. Because of these benefits, the per unit system is essential in fault analysis, load flow studies, transformer testing, and short-circuit calculations . ⚡ What is the Per Unit System? The per unit system is defined as: Q u a n t i t y ( p u ) = A c t u a l   V a l u e B a s e   V a l u e Quantity_{(pu)} = \dfrac{Actual \ Value}{Base \ Value} Q u an t i t y ( p u ) ​ = B a se   ...

PRIMARY SECONDARY AND TERTIARY FREQUENCY CONTROL IN POWER SYSTEMS

Primary, Secondary and Tertiary Frequency Control in Power Systems Author: Engr. Aneel Kumar Keywords: frequency control, primary frequency control, automatic generation control (AGC), tertiary control, load-frequency control, grid stability. Frequency control keeps the power grid stable by balancing generation and load. When generation and demand drift apart, system frequency moves away from its nominal value (50 or 60 Hz). Grids rely on three hierarchical control layers — Primary , Secondary (AGC), and Tertiary — to arrest frequency deviation, restore the set-point and optimize generation dispatch. Related: Power System Stability — causes & mitigation Overview of primary, secondary and tertiary frequency control in power systems. ⚡ Primary Frequency Control (Droop Control) Primary control is a fast, local response implemented by generator governors (dro...

ELECTRIC MOTOR PRINCIPLES

The electric motor in its simplest terms is a converter of electrical energy to useful mechanical energy. The electric motor has played a leading role in the high productivity of modern industry, and it is therefore directly responsible for the high standard of living being enjoyed throughout the industrialized world. An electric motor’s principle of operation is based on the fact that a current- carrying conductor, when placed in a magnetic field, will have a force exerted on the conductor proportional to the current flowing in the conductor and to the strength of the magnetic field. In alternating current motors, the windings placed in the laminated stator core produce the magnetic field. The aluminum bars in the laminated rotor core are the current carrying conductors upon which the force acts. The resultant action is the rotary motion of the rotor and shaft, which can then be coupled to various devices to be driven and produce the output. Many types of motors are produced today. Un...

FUEL INJECTION SYSTEM OF DIESEL ENGINE

Fuel injection is a system for mixing fuel with air in an internal combustion engine. A fuel injection system is designed and calibrated specifically for the type of fuel it will handle. Most fuel injection systems are for diesel applications. With the advent of electronic fuel injection (EFI), the diesel gasoline hardware has become similar. EFI’s programmable firmware has permitted common hardware to be used with different fuels. Carburetors were the predominant method used to meter fuel before the widespread use of fuel injection. A variety of injection systems have existed since the earliest usage of the internal combustion engine. The primary difference between carburetors and fuel injection is that fuel injection atomizes the fuel by forcibly pumping it through a small nozzle under high pressure, while a carburetor relies on low pressure created by intake air rushing through it to add the fuel to the air stream. The fuel injector is only a nozzle and a valve: the power to inj...