POWER QUALITY TERMS

IMPULSE TRANSIENT, OSCILLATORY TRANSIENT, VOLTAGE DIPS, VOLTAGE SWELLS OR SURGES, OVER VOLTAGE, UNDER VOLTAGE, WAVEFORM DISTORTION OR HARMONICS, NOTCHING, NOISE

IMPULSE TRANSIENT

A sudden and short-duration disturbance caused by a very rapid change in the steady-state condition of voltage, current, or both, that is unidirectional in polarity.

Frequency range: >5 kHz (high frequency)
Duration: 30-200 uSec

LOW-FREQUENCY TRANSIENTS: <500 HZ

Duration: <30 cycles

Causes:
•Capacitor switching

Impacts:
•Tripping of ASDs and other sensitive equipment
•Voltage magnification at customer capacitors

OSCILLATORY TRANSIENT

A sudden and short-duration disturbance caused by a very rapid change in the steady-state condition of voltage, current, or both, that is bi-directional in polarity.

MEDIUM-FREQUENCY TRANSIENTS (500 HZ-2 KHZ)

Duration: < 3 cycles)

Causes:
•Traveling waves from lightning impulses
•Capacitor and circuit switching transients

Impacts:
•Failure of customer equipment

HIGH FREQUENCY TRANSIENTS >2 KHZ

Duration: < 0.5 cycle

Causes:
•Switching on secondary systems
•Lightning-induced ringing
•Local ferroresonance

Impacts:
•Radiated noise may disrupt sensitive electronic equipment
•High rate of rise oscillations may cause low-voltage power supplies to fail
•Short-duration voltage variations

VOLTAGE DIPS

Decrease between 0.1 and 0.9 pu in rms voltage or current at the power frequency for duration from 0.5 cycles to 1 minute

Causes:
•Local and remote faults

Impacts:
•Dropouts of sensitive customer equipment

VOLTAGE SWELLS OR SURGES

Increase to between 1.1 and 1.8 pu in the rms voltage or current at the power frequency for durations from 0.5 cycle to 1 min

Causes:
•Single-line-to-ground faults
•Equipment overvoltage

Impacts:
•Failure of MOVs forced into conduction
•Long-duration voltage variations

OVER VOLTAGE

Increase in the rms ac voltage greater than 110% at the power fre quency for a duration longer than 1 min.

Causes:
•Load switching off
•Capacitor switching on
•System voltage regulation

Impacts:
•Problems with equipment that require constant steady-state voltage

UNDER VOLTAGE

Decrease in the rms ac voltage to less than 90% at the power frequency for a duration longer than 1 minute

Causes:
•Load switching on
•Capacitor switching off

Impacts:
•Problems with equipment that require constant steady-state voltage, system voltage regulation

WAVEFORM DISTORTION OR HARMONICS

Nonlinear loads, such as power electronic equipment, produce non-sinusoidal current waveforms when energized with a sinusoidal voltage. They inject currents at harmonic (integer multiple of the fundamental frequency) frequencies into the system. Harmonic currents, and the voltage distortion they create as they flow through the system impedance.

Causes:
•Nonlinear loads

Impacts:
•Improper operation of sensitive equipment
•Reduction of equipment operating reliability and service life (0-100th harmonic)
•Capacitor failures or fuse blowing
•Telephone interference

NOTCHING

Periodic voltage disturbance caused by the normal operation of power electronics devices when current is commutated from one phase to another

Causes:
•Normal operation of electronic equipment

Impacts:
•Improper operation of equipment
•Equipment failure

Noise

Any unwanted electrical signals with broadband spectral content lower than 200 kHz superimposed upon the power system voltage or current in phase conductors, or found on neutral conductors or signal lines

Causes:
•Improper grounding
•Normal operation of electronic equipment
•Arcing devices
•Switching power supplies

Impacts:
•Interference with electronic devices such as microcomputer and programmable controllers

Popular posts from this blog

AUTO TRANSFORMER TAP CHANGING

Figure shows diagrammatically auto-transformer tap changing. Here, a mid-tapped auto-transformer or reactor is used. One of the lines is connected to its mid-tapping. One end, say a of this transformer is connected to a series of switches across the odd tappings and the other end b is connected to switches across even tappings. A short-circuiting switch S is connected across the auto-transformer and remains in the closed position under normal operation. In the normal operation, there is no inductive voltage drop across the auto-transformer. Referring to Figure, it is clear that with switch 5 closed, minimum secondary turns are in the circuit and hence the output voltage will be the lowest. On the other hand, the output voltage will be maximum when switch 1 is closed. Suppose now it is desired to alter the tapping point from position 5 to position 4 in order to raise the output voltage. For this purpose, short-circuiting switch S is opened, switch 4 is closed, then switch 5 is op...

COMPONENTS OF HIGH VOLTAGE DC TRANSMISSION SYSTEM

Figure: A schematic of a bipolar HVDC system identifying main components

PLUG REVERSING OF CAPACITOR START MOTORS

The capacitor start motors suffer from the disadvantage that they are not easily reversible due to the centrifugal switch connected in the auxiliary winding. The motor cannot be instantaneously reversed by simple control as the auxiliary winding remains disconnected till the motor comes near to zero speed. However, by proper design of the control circuit the motor can be made instantly reversible. This is accomplished by using an electromagnetic relay along with a special two contact centrifugal switch as shown in Figure. The circuit shown in Figure is for a small hoist using a capacitor start motor. The upper and lower limits of travel are controlled by two limit switches viz. LSU and LSD. When UP-push button is pressed, contactor U gets energized. Its contacts U 1  and U 2  energies the main winding. Closing of its contact U 3  causes relay R to get energized through the centrifugal switch contacts A—B. After the energization of relay R auxiliary winding gets ene...

BENEFITS OF UTILIZING FACTS DEVICES

The advantages of using FACTS devices in electrical transmission systems are described below. 1. MORE UTILIZATION OF EXISTING TRANSMISSION SYSTEM In all the countries, the power demand is increasing day by day to transfer the electrical power and controlling the load flow of the transmission system is very necessary this can be achieved by more load centers which can change frequently. Addition of new transmission line is very costly to take the increased load on the system; in that case FACTS devices are much economical to meet the increased load on the same transmission lines. 2. MORE INCREASED TRANSIENT AND DYNAMIC STABILITY OF THE SYSTEM The Long transmission lines are inter-connected with grids to absorb the changing the loading of the transmission line and it is also seen that there should be no line fault creates in the line / transmission system. By doing this the power flow is reduced and transmission line can be trip. By the use of FACTS devices high power t...

PRIMARY SECONDARY AND TERTIARY FREQUENCY CONTROL IN POWER SYSTEMS

Primary, Secondary and Tertiary Frequency Control in Power Systems Author: Engr. Aneel Kumar Keywords: frequency control, primary frequency control, automatic generation control (AGC), tertiary control, load-frequency control, grid stability. Frequency control keeps the power grid stable by balancing generation and load. When generation and demand drift apart, system frequency moves away from its nominal value (50 or 60 Hz). Grids rely on three hierarchical control layers — Primary , Secondary (AGC), and Tertiary — to arrest frequency deviation, restore the set-point and optimize generation dispatch. Related: Power System Stability — causes & mitigation Overview of primary, secondary and tertiary frequency control in power systems. ⚡ Primary Frequency Control (Droop Control) Primary control is a fast, local response implemented by generator governors (dro...

AC Transmission Line and Reactive Power Compensation: A Detailed Overview

  Introduction The efficient operation of modern power systems depends significantly on the management of AC transmission lines and reactive power. Reactive power compensation is a vital technique for maintaining voltage stability, improving power transfer capability, and reducing system losses. This article explores the principles of AC transmission lines, the need for reactive power compensation, and its benefits in power systems. Keywords: Reactive Power Compensation Benefits, STATCOM vs SVC Efficiency, Power Transmission Stability Solutions, Voltage Stability in Long-Distance Grids, Dynamic Reactive Power Compensation.      Fundamentals of AC Transmission Lines AC transmission lines are the backbone of modern power systems, connecting generation stations to distribution networks. They have distributed electrical parameters such as resistance ( R R R ), inductance ( L L ), capacitance ( C C ), and conductance ( G G ) along their length. These parameters influence ...

Breaker Schemes in Substations

Breaker Schemes in Substations — Types, Design, Advantages, Disadvantages, and Comparison Author: Engr. Aneel Kumar Figure 1: Infographic overview of breaker schemes commonly used in substations. Introduction The breaker scheme or busbar arrangement in a substation defines how incoming feeders, outgoing feeders, and power transformers are connected to the bus. The choice of scheme has a direct impact on system reliability, maintainability, safety, and cost . A simple bus scheme is economical but vulnerable to outages, while advanced schemes such as breaker-and-a-half or double-bus/double-breaker provide very high reliability but at much higher cost and design complexity. Engineers select breaker schemes considering fault tolerance, maintenance needs, space requirements, expansion possibilities, protection coordination, and capital investment . Below, we explain eac...