NAVIGATION AIDS

Navigation aids consist of the following equipment:

1. Flashing marker lights.
2. Fog horns.
3. Platform nameplates.
4. Aircraft hazard lights.
5. Helideck landing facilities.
6. Radio communications and beacons.
7. Radar.
8. Echo-sounding and sonar.

1) FLASHING MARKER LIGHTS

A typical requirement is that recommended by the British Department of Trade document ‘Standard Making Schedule for Offshore Installations’,

1. White and red lights flashing the Morse letters ‘U’ every 15 seconds as follows:

Eclipse 1.00 s
Flash 1.00 s
Eclipse 1.00 s
Flash 3.00 s
Eclipse 8.00 s
Total Period 15.00 s

2. Fog signals sounding the ‘U’ every 30 seconds as follows:

Blast 0.75 s
Silent 1.00 s
Blast 0.75 s
Silent 1.00 s
Blast 2.50 s
Silent 24.00 s
Total Period 30.00 s

3. Illuminated identification panels.
4. Navigation buoys.

2) WHITE AND RED FLASHING LIGHTS

The ‘normal’ range and ‘apparent intensity’ of these flashing lights should be in accordance with the local requirements, e.g. for UK waters, IALA publication ‘Recommendations for the Notation of Luminous Intensity and Range of Lights’.

a) MAIN LIGHTS

The main white lights should have a ‘nominal’ range of 15 miles and be visible in every direction of approach; there should normally be a minimum of two and a maximum of four main white lights.

b) SUBSIDIARY LIGHTS

Subsidiary red lights of 3 miles ‘nominal’ range should be positioned to mark the horizontal extremities of the structure, in positions not occupied by white lights, to indicate any irregular projections of the complex.

c) SECONDARY LIGHTS

Secondary white lights of 10 miles ‘nominal’ range and visible in every direction of approach should automatically come into operation in the event of failure of the 15 mile main white lights; these are normally mounted in similar location to the main white lights.

d) OPERATION AND CONTROL OF LIGHTING SYSTEMS

Navigation lighting systems can be fitted with a device to automatically switch on 15 minutes before sunset until sunrise or whenever the visibility is less than 2 sea miles. There can also be a manual override device to enable the navigation aids to be switched on during unusual conditions or for maintenance and testing etc.

Failure of any of the navigation lights can be indicated in the central control room and in the radio room.

In the event of failure of the main white lights control equipment, control should automatically be transferred to the secondary system, which would cause the secondary and the main lights to flash in synchronism, and generate an alarm in the central control room and the radio room.

All subsidiary lights should operate in synchronism.

The secondary and subsidiary lights can be equipped with an automatic lamp changer or multiple filament bulbs. This provides a minimum of one standby lamp or filament which will be automatically activated in the event of a filament failure. Filament failure should produce an alarm in the central control room and the radio room until a defective bulb is replaced.

On long narrow structures or structures linked by bridges where lights may otherwise be several hundred metres apart, intermediary 3 mile red lights should be mounted in positions to deter vessel from colliding with the central sections of the structure of bridges.

The secondary and subsidiary lights should be capable of operating for 96 hours from a battery power source which is independent of the main supply. The equipment would normally operate on the main AC supply, with automatic switching to an alternative AC supply in the event of main supply failure, and automatic switching to battery supplies when no AC supply is available.

3) NAVIGATION BUOYS

Navigation marker buoys can be wave or solar powered or alternatively fitted with batteries. They would be retained in a position to facilitate quick manual launching, and provision should be made for ready inspection and maintenance of batteries.

4) IDENTIFICATION PANELS

The structure identification panels usually consist of black letter and figures one metre high on a yellow background with illumination or be on a retro-reflective background.

5) AIRCRAFT HAZARD LIGHTING

Hazard lighting should be provided on all projections from the structure which could present a danger to helicopters approaching the platform. Positions where it would be impractical to fit red lights due to the possibility of damage or difficulty of maintenance caused by high temperature, such as flare towers and exhaust stacks, would be flood lit from convenient locations.

In the event of main supply failure the hazard lighting would be supplied from an emergency generator or battery supply.

No form of lighting on the structure should be capable of creating a hazard to helicopters by night-blinding the pilot due to dazzle or glare.

6) HELICOPTER LANDING FACILITIES

Helideck markings and illumination should be in accordance with appropriate standards.

A high frequency radio beacon with a minimum range of 30 miles can be provided for the guidance of approaching helicopters, and VHF/AM radio would be provided for communication with pilots to comply with the appropriate standards, for the location.

The structure would also be equipped with suitable devices for ascertaining the wind speed and direction, air temperature, barometric pressure, visibility and cloud cover.

7) RADAR

Radar is not used on all offshore platforms. Its use is determined by the nature of the platform and the frequency and type of local sea traffic. When surveillance radar is installed precautions should be adopted to ensure the minimum of danger to personnel from high energy radiation and dangers associated with rotating aerial scanners, interference with electronic instruments and communication, and the elimination of ignition in hazardous atmosphere in accordance with the standards e.g. BS3192 and 4992.

All of the equipment and interconnecting cables should be located in a safe area. The transmitters and aerials should not be located near telecommunication equipment, electronic instruments and similar equipment which could suffer interference or damage due to high energy radio frequency radiation. The aerials must be positioned to prevent the creation of high energy radio frequency fields in hazardous areas where they could cause ignition.

The aerials should be installed in such a manner and location as to allow reasonable safe access for at least two people for servicing and maintenance, whilst preventing access to un-authorized personnel.

Emergency stop switches could be provided in a safe position, adjacent to the aerials, to switch off the scanners and transmitters.

8) RADIO DIRECTION-FINDER

Platforms that are permanently manned would require equipment for obtained bearings on radio navigation beacons and survival craft transmitting on international distress frequencies. If the equipment is of a type approved by the British Department of Trade (or similar national standard) in accordance with SOLAS (1974) Regulation 12, then the SOLAS requirements could also be supplemented as follows:

• The equipment should be located in the radio room.
• The aerials and feeder cables should be located in a safe area as close as possible to the radio room.
• An emergency power supply should provide a minimum of 6 hours duration, and minimum of 3 hours of this supply should be from batteries. The batteries, charger and supply cables should be in a safe area as close as possible to the radio room.

9) SONAR DEVICES

If echo-sounding equipment is required then it should be of a type approved by the Department of Trade, or similar national authority appropriate to the location, in accordance with SOLAS (1974). The installation of sonar devices should be in accordance with appropriate standards, and particular regard should be directed towards the dangers that high-powered underwater sonar transmissions may present during diving operations.

Comments

Popular posts from this blog

PRIMARY SECONDARY AND TERTIARY FREQUENCY CONTROL IN POWER SYSTEMS

Primary, Secondary and Tertiary Frequency Control in Power Systems Author: Engr. Aneel Kumar Keywords: frequency control, primary frequency control, automatic generation control (AGC), tertiary control, load-frequency control, grid stability. Frequency control keeps the power grid stable by balancing generation and load. When generation and demand drift apart, system frequency moves away from its nominal value (50 or 60 Hz). Grids rely on three hierarchical control layers — Primary , Secondary (AGC), and Tertiary — to arrest frequency deviation, restore the set-point and optimize generation dispatch. Related: Power System Stability — causes & mitigation Overview of primary, secondary and tertiary frequency control in power systems. ⚡ Primary Frequency Control (Droop Control) Primary control is a fast, local response implemented by generator governors (dro...

Breaker Schemes in Substations

Breaker Schemes in Substations — Types, Design, Advantages, Disadvantages, and Comparison Author: Engr. Aneel Kumar Figure 1: Infographic overview of breaker schemes commonly used in substations. Introduction The breaker scheme or busbar arrangement in a substation defines how incoming feeders, outgoing feeders, and power transformers are connected to the bus. The choice of scheme has a direct impact on system reliability, maintainability, safety, and cost . A simple bus scheme is economical but vulnerable to outages, while advanced schemes such as breaker-and-a-half or double-bus/double-breaker provide very high reliability but at much higher cost and design complexity. Engineers select breaker schemes considering fault tolerance, maintenance needs, space requirements, expansion possibilities, protection coordination, and capital investment . Below, we explain eac...

SYMMETRICAL COMPONENT ANALYSIS

Unbalanced three phase systems can be split into three balanced components, namely Positive Sequence (balanced and having the same phase sequence as the unbalanced supply), Negative Sequence (balanced and having the opposite phase sequence to the unbalanced supply) and Zero Sequence (balanced but having the same phase and hence no phase sequence). These are known as the Symmetrical Components or the Sequence Components and are shown in figure 2.10. The phase components are the addition of the symmetrical components and can be written as follows.  a = a 1 + a 2 + a 0 b = b 1 + b 2 + b 0 c = c 1 + c 2 + c 0 The unknown unbalanced system has three unknown magnitudes and three unknown angles with respect to the reference direction. Similarly, the combination of the 3 sequence components will also have three unknown magnitudes and three unknown angles with respect to the reference direction. Thus the original unbalanced system effectively has 3 complex unknown quan...

TYPES OF ELECTRIC LOADS

Devices that are connected to the power system are referred to as electrical loads. Toasters, refrigerators, bug zappers, and so on are considered electrical loads. There are three types of electrical loads. They vary according to their leading or lagging time relationship between voltage and current. The three load types are resistive, inductive, and capacitive. Each type has specific characteristics that make them unique. Understanding the differences between these load types will help explain how power systems can operate efficiently. Power system engineers, system operators, maintenance personnel, and others try to maximize system efficiency on a continuous basis by having a good understanding of the three types of loads. They understand how having them work together can minimize system losses, provide additional equipment capacity, and maximize system reliability. The three different types of load are summarized below. 1) RESISTIVE LOAD: The resistance in a wire (i.e., cond...

SOLIDLY GROUNDED NEUTRAL SYSTEMS

Solidly grounded systems are usually used in low voltage applications at 600 volts or less. In solidly grounded system, the neutral point is connected to earth. Solidly Neutral Grounding slightly reduces the problem of transient over voltages found on the ungrounded system and provided path for the ground fault current is in the range of 25 to 100% of the system three phase fault current.. However, if the reactance of the generator or transformer is too great, the problem of transient over voltages will not be solved. While solidly grounded systems are an improvement over ungrounded systems, and speed up the location of faults, they lack the current limiting ability of resistance grounding and the extra protection this provides. To maintain systems health and safe, Transformer neutral is grounded and grounding conductor must be extend from the source to the furthest point of the system within the same raceway or conduit. Its purpose is to maintain very low impedance to ground faults so...

ESSENTIAL ELEMENTS OF DIESEL POWER PLANT

FUEL SUPPLY SYSTEM OF DIESEL POWER PLANT It consists of storage tank, strainers, fuel transfer pump and all day fuel tanks. The fuel oil is supplied at the plant site by rail or road. The oil is stored in the storage tank. From the storage tank, oil is pumped to smaller all day tank at daily or short intervals. From this tank, fuel oil is passed through strainers to remove suspended impurities. The clean oil is injected into the engine by fuel injection pump. AIR INTAKE SYSTEM OF DIESEL POWER PLANT This system supplies necessary air to the engine for fuel combustion. It consists of pipes for the supply of fresh air to the engine manifold. Filters are provided to remove dust particles from air which may act as abrasive in the engine cylinder. Because a diesel engine requires close tolerances to achieve its compression ratio, and because most diesel engines are either turbocharged or supercharged, the air entering the engine must be clean, free of debris, and as cool as possible. ...

ADVANTAGES AND DISADVANTAGES OF CORONA EFFECT IN TRANSMISSION LINES | ELECTRICAL ENGINEERING GUIDE

Advantages and Disadvantages of Corona Effect in Power Systems In high-voltage overhead transmission lines , the corona effect plays a critical role in system performance. Corona occurs when the air around a conductor becomes ionized due to high electric stress. While often seen as a drawback because of power losses and interference , it also provides certain engineering benefits . This article explains the advantages and disadvantages of corona effect in detail, with examples relevant to modern electrical power systems. ✅ Advantages of Corona Effect Increase in Virtual Conductor Diameter Due to corona formation, the surrounding air becomes partially conductive, increasing the virtual diameter of the conductor. This reduces electrostatic stress between conductors and minimizes insulation breakdown risks. Related Reading: Electrostatic Fields in High Voltage Engineering Reduction of Transient Surges Corona acts like a natural cushion for sudden ...