Skip to main content

SUBSTATION EQUIPMENT

There are a number of designs used for substations. However, there are elements common to all:
>> A BUS: is the physical structure to which all lines and transformers are connected. Buses are of two generic types: open air and enclosed. Enclosed buses are used when substations are located in buildings or outdoors where space is at a premium. They involve the use of an insulating gas such as sulfur hexafluoride (SF6) to allow reduced spacing between energized phases. Bus structures are designed to withstand the large mechanical forces that can result from fields produced by high short-circuit currents. These forces vary with the third power of the current. A bus section is the part of a bus to which a single line or transformer is connected.



>> PROTECTIVE RELAYS: are devices that continuously monitor the voltages and currents associated with the line and its terminals to detect failures or malfunctions in the line or equipment. Such failures are called faults and involve contact between phases or between one or more phases and ground. The relays actuate circuit breakers.

>> CIRCUIT BREAKERS: are devices that are capable of interrupting the flow of electricity to isolate either a line or a transformer. They do so by opening the circuit and extinguishing the arc that forms, using a variety of technologies such as oil, vacuum, air blast, or sulfur hexafluoride (SF6). Breakers may be in series with the line or transformer or may be installed on both sides of the bus section where the line connects. They allow individual lines or transformers to be removed from service (de-energized) automatically when equipment (protective relays) detects operating conditions outside a safe range. They must be capable of interrupting the very high currents that occur during fault conditions and are rated by the amount of current they can interrupt. These fault current levels can be 20 or 30 times larger than the current flow under normal operating conditions, that is, thousands of amperes.

To minimize the impact of electrical shocks to the transmission system, minimizing the total time for the relay to detect the condition and the circuit breaker to open the circuit is a critical design issue. Circuit breakers also allow lines or transformers to be removed from service for maintenance. Circuit breakers normally interrupt all three phases simultaneously, although in certain special applications, single-phase circuit breakers can be employed that will open only the phase with a problem.

>> TRANSFORMERS: are devices that are used to connect facilities operating at two different voltage levels. The transformer connects to all three phases of the bus. Physically, the transformers can include all three phases within one tank or there can be three separate tanks, one per phase. Larger capacity units may have three separate tanks because their size and weight may be a limiting factor because of transportation issues.

Transformers can be designed with two mechanisms to adjust the voltage ratio. One mechanism is the provision of more than one fixed tap position on one side of the transformer. For example, a transformer might have a nominal turns ratio of 345/138, with fixed taps on the 345 kV winding of 327.8, 336.7, 345, 353.6, and 362.3. The transformer must be de-energized to adjust the fixed tap ratio. Another mechanism is called tap changing under load (TCUL). In this mechanism, the ratio can be adjusted while the transformer is energized, providing greater operating flexibility. Some transformers have both types of mechanisms, with a fixed tap adjustment in the high voltage winding and the TCUL adjustment in the low voltage winding.

Another type transformer is an autotransformer, which is used when facilities at nearly the same voltage are to be connected, such as 138 kV to 115 kV. Rather than having two separate paths for the electricity, connected only by the magnetic flux through the transformer as in a conventional unit, the winding of autotransformer involves a tap on the higher voltage winding which supplies the lower voltage.

All larger transformers have mechanisms to remove the heat generated within the tank, involving some manner of circulating the transformer insulating/cooling oil through an external heat exchanger with fins mounted on the side of the transformer and fans to circulate air across the fins to maximize heat dissipation.

>> DISCONNECT SWITCHES: are used to open a circuit when only charging current is present. These would be used primarily to connect or disconnect circuit breakers or transformers which are not carrying load current. They are also used in conjunction with circuit breakers to provide another level of safety for workers by inserting a second opening between station equipment out of service for work and the still energized section of line or bus.

>> LIGHTNING ARRESTERS: are used to protect transformers and switchgear from the effects of high voltage due to lightning strikes or switching operations. They are designed to flashover when the voltage at the transformer exceeds a preselected level that is chosen by the station design engineers to coordinate with the basic insulation level of the transformer (BIL).

>> METERING EQUIPMENT: is provided to measure line and transformer loadings and bus voltages so operating personnel can ensure that these facilities are within acceptable limits. Metering equipment also is provided at some locations to measure the flow of energy for the billing that is required for sales and purchases of energy between various participants in the electric energy market.

>> SCADA: is an acronym for system control and data acquisition. It covers the measurement, telecommunications, and computing technologies that allow more and more automation of substation operations.

Depending on the electrical characteristics of a particular part of the transmission system, other types of equipment that may be located at a substation are:

>> SHUNT REACTORS: (reactors connected from the energized bus to ground) are installed to control high voltages that occur especially at night due to the capacitive effect of lightly loaded transmission lines. These reactors can be energized always or they can be energized only at specific times. Shunt reactors are also used to reduce or control the high voltages that can occur when a sudden loss of a block of customer load occurs. The windings, insulation, and the external tank are similar to those used for transformers.

>> SERIES REACTORS: are installed in a transmission line to increase the impedance of the line, to decrease current levels in the event of short circuits, or to reduce its loading under various operating conditions.

>> SHUNT CAPACITORS: are installed to provide mVArs to the system to help support voltage levels.

>> SERIES CAPACITORS: are installed to reduce the effective impedance of a transmission line. These would be installed in very long transmission lines to effectively reduce the electrical angle between the sending and the receiving parts of the system, enabling more power to flow over the line and increasing stability limits.

>> PHASE ANGLE REGULATING TRANSFORMERS: are installed to control power flow through a transmission line, causing more or less power to flow over desired lines. They use a variant on the design of a normal transformer, in which, due to the specialized way they are wound, they electrically inject an angular phase shift into the line. The angle can be made to either increase or decrease power flow on the line. Since they are expensive, they are usually used only on cable systems where, because of the cost and limited capacity of cables, maximum utilization of all parallel cable capacity is essential. In recent years, many of them are being installed in transmission lines to control parallel path flow, when power flows over paths in other systems not involved in transactions or which do not have adequate capacity.

>> FACTS (FLEXIBLE AC TRANSMISSION SYSTEMS): is a generic name used for a variety of devices intended to dynamically control voltage, impedance, or phase angle of HVAC lines.

These devices mirror and extend the benefits of the fixed series and shunt inductors and capacitors previously discussed in that the FACTS devices allow rapid and precise adjustments. Depending on the device, they provide a number of benefits: increased power transfer capability, rapid voltage control, improved system stability, and mitigation of sub-synchronous resonance. There are many devices made by many manufacturers, some of which are in the development stage and a few of which are in service. The names of the devices vary somewhat, depending on the manufacturer. The following lists some of the devices:

>> STATIC VAR COMPENSATORS (SVCS): These devices employ fixed banks of capacitors, controlled with thyristors, which can switch them on and off rapidly. In many instances, there are also thyristor-switched inductors to prevent system resonance.

>> THYRISTOR CONTROLLED SERIES COMPENSATORS (OR SERIES CAPACITORS) (TCSCS): A thyristor controlled reactor is placed in parallel with a series capacitor, allowing for a continuous and rapidly variable series compensation system.

>> STATIC COMPENSATORS (STATCOMS): These are gate turn-off type thyristor (GTO)-based SVCs. They are solid-state synchronous voltage generators that consist of a multi-pulsed, voltage-sourced inverter connected in shunt with a transmission line. They do not require capacitor banks and shunt reactors but rely on electronic processing of voltage and current waveforms to provide inductive or capacitive reactive power. They have the added advantage of output that is not seriously impacted by low system voltage.

>> UNIFIED POWER FLOW CONTROLLER (UPFC): This device has a shunt-connected STATCOM with an additional series branch in the transmission line supplied by the STATCOM’s DC circuit. The device is comparable to a phase shifting transformer. It can control all three basic power transfer parameters: voltage, impedance, and phase angle.

>> SVC LIGHT STATCOM: This is based on voltage source converter technology equipped with insulated gate bipolar transistors (IGBTs), which are power switching components. It provides reactive power as well as absorption purely by means of electronic processing of voltage and current waveforms.

Comments

Popular posts from this blog

PRIMARY SECONDARY AND TERTIARY FREQUENCY CONTROL IN POWER SYSTEMS

Primary, Secondary and Tertiary Frequency Control in Power Systems Author: Engr. Aneel Kumar Keywords: frequency control, primary frequency control, automatic generation control (AGC), tertiary control, load-frequency control, grid stability. Frequency control keeps the power grid stable by balancing generation and load. When generation and demand drift apart, system frequency moves away from its nominal value (50 or 60 Hz). Grids rely on three hierarchical control layers — Primary , Secondary (AGC), and Tertiary — to arrest frequency deviation, restore the set-point and optimize generation dispatch. Related: Power System Stability — causes & mitigation Overview of primary, secondary and tertiary frequency control in power systems. ⚡ Primary Frequency Control (Droop Control) Primary control is a fast, local response implemented by generator governors (dro...

Breaker Schemes in Substations

Breaker Schemes in Substations — Types, Design, Advantages, Disadvantages, and Comparison Author: Engr. Aneel Kumar Figure 1: Infographic overview of breaker schemes commonly used in substations. Introduction The breaker scheme or busbar arrangement in a substation defines how incoming feeders, outgoing feeders, and power transformers are connected to the bus. The choice of scheme has a direct impact on system reliability, maintainability, safety, and cost . A simple bus scheme is economical but vulnerable to outages, while advanced schemes such as breaker-and-a-half or double-bus/double-breaker provide very high reliability but at much higher cost and design complexity. Engineers select breaker schemes considering fault tolerance, maintenance needs, space requirements, expansion possibilities, protection coordination, and capital investment . Below, we explain eac...

SYMMETRICAL COMPONENT ANALYSIS

Unbalanced three phase systems can be split into three balanced components, namely Positive Sequence (balanced and having the same phase sequence as the unbalanced supply), Negative Sequence (balanced and having the opposite phase sequence to the unbalanced supply) and Zero Sequence (balanced but having the same phase and hence no phase sequence). These are known as the Symmetrical Components or the Sequence Components and are shown in figure 2.10. The phase components are the addition of the symmetrical components and can be written as follows.  a = a 1 + a 2 + a 0 b = b 1 + b 2 + b 0 c = c 1 + c 2 + c 0 The unknown unbalanced system has three unknown magnitudes and three unknown angles with respect to the reference direction. Similarly, the combination of the 3 sequence components will also have three unknown magnitudes and three unknown angles with respect to the reference direction. Thus the original unbalanced system effectively has 3 complex unknown quan...

TYPES OF ELECTRIC LOADS

Devices that are connected to the power system are referred to as electrical loads. Toasters, refrigerators, bug zappers, and so on are considered electrical loads. There are three types of electrical loads. They vary according to their leading or lagging time relationship between voltage and current. The three load types are resistive, inductive, and capacitive. Each type has specific characteristics that make them unique. Understanding the differences between these load types will help explain how power systems can operate efficiently. Power system engineers, system operators, maintenance personnel, and others try to maximize system efficiency on a continuous basis by having a good understanding of the three types of loads. They understand how having them work together can minimize system losses, provide additional equipment capacity, and maximize system reliability. The three different types of load are summarized below. 1) RESISTIVE LOAD: The resistance in a wire (i.e., cond...

SOLIDLY GROUNDED NEUTRAL SYSTEMS

Solidly grounded systems are usually used in low voltage applications at 600 volts or less. In solidly grounded system, the neutral point is connected to earth. Solidly Neutral Grounding slightly reduces the problem of transient over voltages found on the ungrounded system and provided path for the ground fault current is in the range of 25 to 100% of the system three phase fault current.. However, if the reactance of the generator or transformer is too great, the problem of transient over voltages will not be solved. While solidly grounded systems are an improvement over ungrounded systems, and speed up the location of faults, they lack the current limiting ability of resistance grounding and the extra protection this provides. To maintain systems health and safe, Transformer neutral is grounded and grounding conductor must be extend from the source to the furthest point of the system within the same raceway or conduit. Its purpose is to maintain very low impedance to ground faults so...

ESSENTIAL ELEMENTS OF DIESEL POWER PLANT

FUEL SUPPLY SYSTEM OF DIESEL POWER PLANT It consists of storage tank, strainers, fuel transfer pump and all day fuel tanks. The fuel oil is supplied at the plant site by rail or road. The oil is stored in the storage tank. From the storage tank, oil is pumped to smaller all day tank at daily or short intervals. From this tank, fuel oil is passed through strainers to remove suspended impurities. The clean oil is injected into the engine by fuel injection pump. AIR INTAKE SYSTEM OF DIESEL POWER PLANT This system supplies necessary air to the engine for fuel combustion. It consists of pipes for the supply of fresh air to the engine manifold. Filters are provided to remove dust particles from air which may act as abrasive in the engine cylinder. Because a diesel engine requires close tolerances to achieve its compression ratio, and because most diesel engines are either turbocharged or supercharged, the air entering the engine must be clean, free of debris, and as cool as possible. ...

ADVANTAGES AND DISADVANTAGES OF CORONA EFFECT IN TRANSMISSION LINES | ELECTRICAL ENGINEERING GUIDE

Advantages and Disadvantages of Corona Effect in Power Systems In high-voltage overhead transmission lines , the corona effect plays a critical role in system performance. Corona occurs when the air around a conductor becomes ionized due to high electric stress. While often seen as a drawback because of power losses and interference , it also provides certain engineering benefits . This article explains the advantages and disadvantages of corona effect in detail, with examples relevant to modern electrical power systems. ✅ Advantages of Corona Effect Increase in Virtual Conductor Diameter Due to corona formation, the surrounding air becomes partially conductive, increasing the virtual diameter of the conductor. This reduces electrostatic stress between conductors and minimizes insulation breakdown risks. Related Reading: Electrostatic Fields in High Voltage Engineering Reduction of Transient Surges Corona acts like a natural cushion for sudden ...