Skip to main content

FIXED SHUNT REACTOR

Fixed Shunt Reactors have been traditionally used in transmission and distribution systems for many years. The reason that it is called Fixed Shunt Reactor is that its rated reactive power consumption is approximately constant; in other words, it has a fixed reactance (XR). The inductive reactive power which is consumed by Reactor can be calculated as follows:
Where:
QIR is the 3‐phase inductive reactive power consumed by the Shunt Reactor in VAR
is the phase‐to‐phase voltage at the point the reactor is connected to the network in Volts
Xis the total inductive reactance of the Shunt Reactor in Ohms
Lis the equivalent inductance of the Shunt Reactor in Henry,
Iis the flowing current into the Reactor’s branch in Amperes

As seen in equation 6-1, the consumed reactive power is only a function of the line voltage and is not affected by the load current of the line. The Reactor is characterized by the following. 
  • Rated power
  • Rated system voltage
  • Power frequency
  • Number of phases 
  • Insulation level 
  • Temperature rise 
  • Sound Level 
  • Linearity characteristic
In order to design a Shunt Reactor, the required rated power (QIR) and the rated system voltage (V) are specified; so according to equation 6-1, all that should be done is to implement a certain reactance (XR) to have the desired reactive power consumption. 

There are two general types of Shunt Reactors. First one is dry-type Reactor of an air-core or core-less design. Second one is oil-immersed Shunt Reactor. 

Dry-type Shunt Reactors are limited to voltages up to 34.5kV and are often installed on the tertiary of a transformer (Figure 6-5) or are used in SVC installations.

Figure 6-5: An old design air-core Shunt Reactor (A) and a modern air-core Shunt Reactor (B), connected to the tertiary winding of a large transmission network transformer
Figure 6-6 illustrates a three-phase core-less Shunt Reactor (dry-type) which is installed in a distribution substation. As seen, there is no iron at all in the core-less concept.

Figure 6-6: A 3-phase core-less or air-core Shunt Reactor
On the other hand, oil-immersed Shunt Reactors are used for higher voltage levels (higher than 40kV) and are the most compact and cost efficient Reactors. Regarding the core design, two different ways has been used in building oil-immersed Shunt Reactors. First one is referred to as core-type or gapped core, and the second one is called shell-type design. 

It is desired to implement a certain reactance (XR) in the reactor in order to consume the required level of reactive power. Since it is needed to take a relatively large current in Shunt Reactors to have considerable reactive power consumption, the equivalent reactance in Shunt Reactors should be small compare to a power transformer magnetizing impedance. Therefore the magnetic permeability of the core (μ) should be reduced in Reactors. A good way to reduce the magnetic permeability and the resulting reactance (XR) is to create air-gap in the core. One way is to create one big air-gap and adjust the gap length in order to achieve a certain level of reactance. However, having one big gap results in large losses. 

Basically, the choice between single or 3-phase shunt reactors is exactly the same as transformers. It should be a balance between cost savings and risk costs when large 3-phase reactors are used instead of three single phase units. 

One 3-phase Shunt Reactor has cost advantages compare to three single phase units. To explain, the price of a 3-phase reactor is lower than three single phase units. In addition, the total power loss is also lower in a 3-phase unit. Moreover, the size of substation decreases and additional savings can be made in civil works and related substation equipment. 

On the other hand, when using three single phase shunt reactors, it is economically reasonable to keep a fourth single phase unit as spare. However utilities seldom keep a spare 3-phase Reactor due to cost reasons; for this reason, the reliability of 3-phase Shunt Reactors is very important. A well-designed and well-manufactured Shunt Reactor should have the same or better reliability as a transformer and should also have low levels of sound and vibrations. It should be noted that the reliability of a 3-phase Shunt Reactor should be the same as a single phase one.

Comments

Popular posts from this blog

Advantages of Per Unit System in Power System Analysis | Electrical Engineering

  Advantages of Per Unit System in Power System Analysis In electrical power engineering, the per unit (p.u.) system is one of the most widely used techniques for analyzing and modeling power systems. It is a method of expressing electrical quantities — such as voltage, current, power, and impedance — as fractions of chosen base values rather than their actual numerical magnitudes. This normalization technique provides a universal language for system calculations, minimizing errors, simplifying transformer modeling, and enabling consistency across multiple voltage levels. Because of these benefits, the per unit system is essential in fault analysis, load flow studies, transformer testing, and short-circuit calculations . ⚡ What is the Per Unit System? The per unit system is defined as: Q u a n t i t y ( p u ) = A c t u a l   V a l u e B a s e   V a l u e Quantity_{(pu)} = \dfrac{Actual \ Value}{Base \ Value} Q u an t i t y ( p u ) ​ = B a se   ...

Breaker Schemes in Substations

Breaker Schemes in Substations — Types, Design, Advantages, Disadvantages, and Comparison Author: Engr. Aneel Kumar Figure 1: Infographic overview of breaker schemes commonly used in substations. Introduction The breaker scheme or busbar arrangement in a substation defines how incoming feeders, outgoing feeders, and power transformers are connected to the bus. The choice of scheme has a direct impact on system reliability, maintainability, safety, and cost . A simple bus scheme is economical but vulnerable to outages, while advanced schemes such as breaker-and-a-half or double-bus/double-breaker provide very high reliability but at much higher cost and design complexity. Engineers select breaker schemes considering fault tolerance, maintenance needs, space requirements, expansion possibilities, protection coordination, and capital investment . Below, we explain eac...

TYPES OF DATA FLOW IN COMMUNICATION SYSTEM

Communication between two devices can be simplex, half-duplex, or full-duplex. SIMPLEX : In simplex mode, the communication is unidirectional, as on a one-way street. Only one of the two devices on a link can transmit; the other can only receive. Keyboards and traditional monitors are examples of simplex devices. The keyboard can only introduce input; the monitor can only accept output. The simplex mode can use the entire capacity of the channel to send data in one direction. HALF-DUPLEX : In half-duplex mode, each station can both transmit and receive, but not at the same time. When one device is sending, the other can only receive, and vice versa The half-duplex mode is like a one-lane road with traffic allowed in both directions. When cars are traveling in one direction, cars going the other way must wait. In a half-duplex transmission, the entire capacity of a channel is taken over by whichever of the two devices is transmitting at the time. Walkie-talkies and CB (...

PRINCIPLE OF OPERATION OF UNIFIED POWER FLOW CONTROLLER UPFC

UPFC consist of two back to back converters named VSC1 and VSC2, are operated from a DC link provided by a dc storage capacitor. These arrangements operate as an ideal ac to ac converter in which the real power can freely flow either in direction between the ac terminals of the two converts and each converter can independently generate or absorb reactive power as its own ac output terminal. Figure: Basic UPFC scheme One VSC is connected to in shunt to the transmission line via a shunt transformer and other one is connected in series through a series transformer. The DC terminal of two VSCs is coupled and this creates a path for active power exchange between the converters. VSC provide the main function of UPFC by injecting a voltage with controllable magnitude and phase angle in series with the line via an injection transformer. This injected voltage act as a synchronous ac voltage source. The transmission line current flows through this voltage source resulting in reactive an...

CLASSIFICATION OF POWER SYSTEM BUSES

Each bus in the system has four variables: voltage magnitude, voltage angle, real power and reactive power. During the operation of the power system, each bus has two known variables and two unknowns. Generally, the bus must be classified as one of the following bus types: 1. SLACK OR SWING BUS This bus is considered as the reference bus. It must be connected to a generator of high rating relative to the other generators. During the operation, the voltage of this bus is always specified and remains constant in magnitude and angle. In addition to the generation assigned to it according to economic operation, this bus is responsible for supplying the losses of the system. 2. GENERATOR OR VOLTAGE CONTROLLED BUS During the operation the voltage magnitude at this the bus is kept constant. Also, the active power supplied is kept constant at the value that satisfies the economic operation of the system. Most probably, this bus is connected to a generator where the voltage i...

AC Transmission Line and Reactive Power Compensation: A Detailed Overview

  Introduction The efficient operation of modern power systems depends significantly on the management of AC transmission lines and reactive power. Reactive power compensation is a vital technique for maintaining voltage stability, improving power transfer capability, and reducing system losses. This article explores the principles of AC transmission lines, the need for reactive power compensation, and its benefits in power systems. Keywords: Reactive Power Compensation Benefits, STATCOM vs SVC Efficiency, Power Transmission Stability Solutions, Voltage Stability in Long-Distance Grids, Dynamic Reactive Power Compensation.      Fundamentals of AC Transmission Lines AC transmission lines are the backbone of modern power systems, connecting generation stations to distribution networks. They have distributed electrical parameters such as resistance ( R R R ), inductance ( L L ), capacitance ( C C ), and conductance ( G G ) along their length. These parameters influence ...

PRIMARY SECONDARY AND TERTIARY FREQUENCY CONTROL IN POWER SYSTEMS

Primary, Secondary and Tertiary Frequency Control in Power Systems Author: Engr. Aneel Kumar Keywords: frequency control, primary frequency control, automatic generation control (AGC), tertiary control, load-frequency control, grid stability. Frequency control keeps the power grid stable by balancing generation and load. When generation and demand drift apart, system frequency moves away from its nominal value (50 or 60 Hz). Grids rely on three hierarchical control layers — Primary , Secondary (AGC), and Tertiary — to arrest frequency deviation, restore the set-point and optimize generation dispatch. Related: Power System Stability — causes & mitigation Overview of primary, secondary and tertiary frequency control in power systems. ⚡ Primary Frequency Control (Droop Control) Primary control is a fast, local response implemented by generator governors (dro...