Skip to main content

FIXED SHUNT REACTOR

Fixed Shunt Reactors have been traditionally used in transmission and distribution systems for many years. The reason that it is called Fixed Shunt Reactor is that its rated reactive power consumption is approximately constant; in other words, it has a fixed reactance (XR). The inductive reactive power which is consumed by Reactor can be calculated as follows:
Where:
QIR is the 3‐phase inductive reactive power consumed by the Shunt Reactor in VAR
is the phase‐to‐phase voltage at the point the reactor is connected to the network in Volts
Xis the total inductive reactance of the Shunt Reactor in Ohms
Lis the equivalent inductance of the Shunt Reactor in Henry,
Iis the flowing current into the Reactor’s branch in Amperes

As seen in equation 6-1, the consumed reactive power is only a function of the line voltage and is not affected by the load current of the line. The Reactor is characterized by the following. 
  • Rated power
  • Rated system voltage
  • Power frequency
  • Number of phases 
  • Insulation level 
  • Temperature rise 
  • Sound Level 
  • Linearity characteristic
In order to design a Shunt Reactor, the required rated power (QIR) and the rated system voltage (V) are specified; so according to equation 6-1, all that should be done is to implement a certain reactance (XR) to have the desired reactive power consumption. 

There are two general types of Shunt Reactors. First one is dry-type Reactor of an air-core or core-less design. Second one is oil-immersed Shunt Reactor. 

Dry-type Shunt Reactors are limited to voltages up to 34.5kV and are often installed on the tertiary of a transformer (Figure 6-5) or are used in SVC installations.

Figure 6-5: An old design air-core Shunt Reactor (A) and a modern air-core Shunt Reactor (B), connected to the tertiary winding of a large transmission network transformer
Figure 6-6 illustrates a three-phase core-less Shunt Reactor (dry-type) which is installed in a distribution substation. As seen, there is no iron at all in the core-less concept.

Figure 6-6: A 3-phase core-less or air-core Shunt Reactor
On the other hand, oil-immersed Shunt Reactors are used for higher voltage levels (higher than 40kV) and are the most compact and cost efficient Reactors. Regarding the core design, two different ways has been used in building oil-immersed Shunt Reactors. First one is referred to as core-type or gapped core, and the second one is called shell-type design. 

It is desired to implement a certain reactance (XR) in the reactor in order to consume the required level of reactive power. Since it is needed to take a relatively large current in Shunt Reactors to have considerable reactive power consumption, the equivalent reactance in Shunt Reactors should be small compare to a power transformer magnetizing impedance. Therefore the magnetic permeability of the core (μ) should be reduced in Reactors. A good way to reduce the magnetic permeability and the resulting reactance (XR) is to create air-gap in the core. One way is to create one big air-gap and adjust the gap length in order to achieve a certain level of reactance. However, having one big gap results in large losses. 

Basically, the choice between single or 3-phase shunt reactors is exactly the same as transformers. It should be a balance between cost savings and risk costs when large 3-phase reactors are used instead of three single phase units. 

One 3-phase Shunt Reactor has cost advantages compare to three single phase units. To explain, the price of a 3-phase reactor is lower than three single phase units. In addition, the total power loss is also lower in a 3-phase unit. Moreover, the size of substation decreases and additional savings can be made in civil works and related substation equipment. 

On the other hand, when using three single phase shunt reactors, it is economically reasonable to keep a fourth single phase unit as spare. However utilities seldom keep a spare 3-phase Reactor due to cost reasons; for this reason, the reliability of 3-phase Shunt Reactors is very important. A well-designed and well-manufactured Shunt Reactor should have the same or better reliability as a transformer and should also have low levels of sound and vibrations. It should be noted that the reliability of a 3-phase Shunt Reactor should be the same as a single phase one.

Comments

Popular posts from this blog

PRIMARY SECONDARY AND TERTIARY FREQUENCY CONTROL IN POWER SYSTEMS

Primary, Secondary and Tertiary Frequency Control in Power Systems Author: Engr. Aneel Kumar Keywords: frequency control, primary frequency control, automatic generation control (AGC), tertiary control, load-frequency control, grid stability. Frequency control keeps the power grid stable by balancing generation and load. When generation and demand drift apart, system frequency moves away from its nominal value (50 or 60 Hz). Grids rely on three hierarchical control layers — Primary , Secondary (AGC), and Tertiary — to arrest frequency deviation, restore the set-point and optimize generation dispatch. Related: Power System Stability — causes & mitigation Overview of primary, secondary and tertiary frequency control in power systems. ⚡ Primary Frequency Control (Droop Control) Primary control is a fast, local response implemented by generator governors (dro...

CASCADED TRANSFORMERS METHOD FOR GENERATING AC HIGH VOLTAGE

High-Frequency AC High Voltage Generation Using Cascaded Transformers Author: Engr. Aneel Kumar Figure 1: Infographic representation of cascaded transformers method for generating high AC voltages. Introduction In high voltage engineering , generating very high alternating current (AC) voltages is essential for testing equipment like insulators, circuit breakers, power cables, and other apparatus. One common and effective method for producing such voltages is the cascaded transformers method . This technique uses a series connection of specially designed test transformers , where the secondary of one transformer feeds the primary of the next. In this way, voltages are built up step by step, achieving levels in the range of hundreds of kilovolts (kV) or even megavolts (MV). Working Principle The principle of cascaded connection relies on the fact that each...

Advantages of Per Unit System in Power System Analysis | Electrical Engineering

  Advantages of Per Unit System in Power System Analysis In electrical power engineering, the per unit (p.u.) system is one of the most widely used techniques for analyzing and modeling power systems. It is a method of expressing electrical quantities — such as voltage, current, power, and impedance — as fractions of chosen base values rather than their actual numerical magnitudes. This normalization technique provides a universal language for system calculations, minimizing errors, simplifying transformer modeling, and enabling consistency across multiple voltage levels. Because of these benefits, the per unit system is essential in fault analysis, load flow studies, transformer testing, and short-circuit calculations . ⚡ What is the Per Unit System? The per unit system is defined as: Q u a n t i t y ( p u ) = A c t u a l   V a l u e B a s e   V a l u e Quantity_{(pu)} = \dfrac{Actual \ Value}{Base \ Value} Q u an t i t y ( p u ) ​ = B a se   ...

ADVANTAGES OF INTERCONNECTED GRID SYSTEM

Interconnected Grid System: Working, Advantages, Disadvantages, and Comparison with Isolated Grids Author: Engr. Aneel Kumar Figure 1: Infographic showing key advantages of an interconnected grid system. Introduction An interconnected grid system refers to a network of multiple power generation sources, transmission lines, substations, and distribution systems that are linked across regions, states, or even countries. Unlike an isolated grid (or islanded grid) which operates independently, an interconnected grid allows electricity to flow between interconnected nodes, enabling numerous benefits and some trade-offs. In today’s energy landscape—where demand, renewable generation, reliability, and cost pressure are all increasing—understanding how an interconnected grid works, what factors are essential, and what its advantages and disadvantages are is critical for utility planners, reg...

FACTORS AFFECTING BATTERY PERFORMANCE

Batteries have limited life, usually showing a slow degradation of capacity until they reach 80 percent of their initial rating, followed by a comparatively rapid failure. Regardless of how or where a UPS is deployed, and what size it is, there are four primary factors that affect battery life: ambient temperature, battery chemistry, cycling and service. 1) AMBIENT TEMPERATURE The rated capacity of a battery is based on an ambient temperature of 25°C (77°F). It’s important to realize that any variation from this operating temperature can alter the battery’s performance and shorten its expected life. To help determine battery life in relation to temperature, remember that for every 8.3°C (15°F) average annual temperature above 25°C (77°F), the life of the battery is reduced by 50 percent. 2) BATTERY CHEMISTRY UPS batteries are electro-chemical devices whose ability to store and deliver power slowly decreases over time. Even if you follow all the guidelines for proper storage, us...

ADVANTAGES AND DISADVANTAGES OF CORONA EFFECT IN TRANSMISSION LINES | ELECTRICAL ENGINEERING GUIDE

Advantages and Disadvantages of Corona Effect in Power Systems In high-voltage overhead transmission lines , the corona effect plays a critical role in system performance. Corona occurs when the air around a conductor becomes ionized due to high electric stress. While often seen as a drawback because of power losses and interference , it also provides certain engineering benefits . This article explains the advantages and disadvantages of corona effect in detail, with examples relevant to modern electrical power systems. ✅ Advantages of Corona Effect Increase in Virtual Conductor Diameter Due to corona formation, the surrounding air becomes partially conductive, increasing the virtual diameter of the conductor. This reduces electrostatic stress between conductors and minimizes insulation breakdown risks. Related Reading: Electrostatic Fields in High Voltage Engineering Reduction of Transient Surges Corona acts like a natural cushion for sudden ...

AC Transmission Line and Reactive Power Compensation: A Detailed Overview

  Introduction The efficient operation of modern power systems depends significantly on the management of AC transmission lines and reactive power. Reactive power compensation is a vital technique for maintaining voltage stability, improving power transfer capability, and reducing system losses. This article explores the principles of AC transmission lines, the need for reactive power compensation, and its benefits in power systems. Keywords: Reactive Power Compensation Benefits, STATCOM vs SVC Efficiency, Power Transmission Stability Solutions, Voltage Stability in Long-Distance Grids, Dynamic Reactive Power Compensation.      Fundamentals of AC Transmission Lines AC transmission lines are the backbone of modern power systems, connecting generation stations to distribution networks. They have distributed electrical parameters such as resistance ( R R R ), inductance ( L L ), capacitance ( C C ), and conductance ( G G ) along their length. These parameters influence ...