Skip to main content

FIXED SHUNT REACTOR

Fixed Shunt Reactors have been traditionally used in transmission and distribution systems for many years. The reason that it is called Fixed Shunt Reactor is that its rated reactive power consumption is approximately constant; in other words, it has a fixed reactance (XR). The inductive reactive power which is consumed by Reactor can be calculated as follows:
Where:
QIR is the 3‐phase inductive reactive power consumed by the Shunt Reactor in VAR
is the phase‐to‐phase voltage at the point the reactor is connected to the network in Volts
Xis the total inductive reactance of the Shunt Reactor in Ohms
Lis the equivalent inductance of the Shunt Reactor in Henry,
Iis the flowing current into the Reactor’s branch in Amperes

As seen in equation 6-1, the consumed reactive power is only a function of the line voltage and is not affected by the load current of the line. The Reactor is characterized by the following. 
  • Rated power
  • Rated system voltage
  • Power frequency
  • Number of phases 
  • Insulation level 
  • Temperature rise 
  • Sound Level 
  • Linearity characteristic
In order to design a Shunt Reactor, the required rated power (QIR) and the rated system voltage (V) are specified; so according to equation 6-1, all that should be done is to implement a certain reactance (XR) to have the desired reactive power consumption. 

There are two general types of Shunt Reactors. First one is dry-type Reactor of an air-core or core-less design. Second one is oil-immersed Shunt Reactor. 

Dry-type Shunt Reactors are limited to voltages up to 34.5kV and are often installed on the tertiary of a transformer (Figure 6-5) or are used in SVC installations.

Figure 6-5: An old design air-core Shunt Reactor (A) and a modern air-core Shunt Reactor (B), connected to the tertiary winding of a large transmission network transformer
Figure 6-6 illustrates a three-phase core-less Shunt Reactor (dry-type) which is installed in a distribution substation. As seen, there is no iron at all in the core-less concept.

Figure 6-6: A 3-phase core-less or air-core Shunt Reactor
On the other hand, oil-immersed Shunt Reactors are used for higher voltage levels (higher than 40kV) and are the most compact and cost efficient Reactors. Regarding the core design, two different ways has been used in building oil-immersed Shunt Reactors. First one is referred to as core-type or gapped core, and the second one is called shell-type design. 

It is desired to implement a certain reactance (XR) in the reactor in order to consume the required level of reactive power. Since it is needed to take a relatively large current in Shunt Reactors to have considerable reactive power consumption, the equivalent reactance in Shunt Reactors should be small compare to a power transformer magnetizing impedance. Therefore the magnetic permeability of the core (μ) should be reduced in Reactors. A good way to reduce the magnetic permeability and the resulting reactance (XR) is to create air-gap in the core. One way is to create one big air-gap and adjust the gap length in order to achieve a certain level of reactance. However, having one big gap results in large losses. 

Basically, the choice between single or 3-phase shunt reactors is exactly the same as transformers. It should be a balance between cost savings and risk costs when large 3-phase reactors are used instead of three single phase units. 

One 3-phase Shunt Reactor has cost advantages compare to three single phase units. To explain, the price of a 3-phase reactor is lower than three single phase units. In addition, the total power loss is also lower in a 3-phase unit. Moreover, the size of substation decreases and additional savings can be made in civil works and related substation equipment. 

On the other hand, when using three single phase shunt reactors, it is economically reasonable to keep a fourth single phase unit as spare. However utilities seldom keep a spare 3-phase Reactor due to cost reasons; for this reason, the reliability of 3-phase Shunt Reactors is very important. A well-designed and well-manufactured Shunt Reactor should have the same or better reliability as a transformer and should also have low levels of sound and vibrations. It should be noted that the reliability of a 3-phase Shunt Reactor should be the same as a single phase one.

Comments

Popular posts from this blog

PRIMARY SECONDARY AND TERTIARY FREQUENCY CONTROL IN POWER SYSTEMS

Primary, Secondary and Tertiary Frequency Control in Power Systems Author: Engr. Aneel Kumar Keywords: frequency control, primary frequency control, automatic generation control (AGC), tertiary control, load-frequency control, grid stability. Frequency control keeps the power grid stable by balancing generation and load. When generation and demand drift apart, system frequency moves away from its nominal value (50 or 60 Hz). Grids rely on three hierarchical control layers — Primary , Secondary (AGC), and Tertiary — to arrest frequency deviation, restore the set-point and optimize generation dispatch. Related: Power System Stability — causes & mitigation Overview of primary, secondary and tertiary frequency control in power systems. ⚡ Primary Frequency Control (Droop Control) Primary control is a fast, local response implemented by generator governors (dro...

Advantages of Per Unit System in Power System Analysis | Electrical Engineering

  Advantages of Per Unit System in Power System Analysis In electrical power engineering, the per unit (p.u.) system is one of the most widely used techniques for analyzing and modeling power systems. It is a method of expressing electrical quantities — such as voltage, current, power, and impedance — as fractions of chosen base values rather than their actual numerical magnitudes. This normalization technique provides a universal language for system calculations, minimizing errors, simplifying transformer modeling, and enabling consistency across multiple voltage levels. Because of these benefits, the per unit system is essential in fault analysis, load flow studies, transformer testing, and short-circuit calculations . ⚡ What is the Per Unit System? The per unit system is defined as: Q u a n t i t y ( p u ) = A c t u a l   V a l u e B a s e   V a l u e Quantity_{(pu)} = \dfrac{Actual \ Value}{Base \ Value} Q u an t i t y ( p u ) ​ = B a se   ...

CASCADED TRANSFORMERS METHOD FOR GENERATING AC HIGH VOLTAGE

High-Frequency AC High Voltage Generation Using Cascaded Transformers Author: Engr. Aneel Kumar Figure 1: Infographic representation of cascaded transformers method for generating high AC voltages. Introduction In high voltage engineering , generating very high alternating current (AC) voltages is essential for testing equipment like insulators, circuit breakers, power cables, and other apparatus. One common and effective method for producing such voltages is the cascaded transformers method . This technique uses a series connection of specially designed test transformers , where the secondary of one transformer feeds the primary of the next. In this way, voltages are built up step by step, achieving levels in the range of hundreds of kilovolts (kV) or even megavolts (MV). Working Principle The principle of cascaded connection relies on the fact that each...

ADVANTAGES AND DISADVANTAGES OF CORONA EFFECT IN TRANSMISSION LINES | ELECTRICAL ENGINEERING GUIDE

Advantages and Disadvantages of Corona Effect in Power Systems In high-voltage overhead transmission lines , the corona effect plays a critical role in system performance. Corona occurs when the air around a conductor becomes ionized due to high electric stress. While often seen as a drawback because of power losses and interference , it also provides certain engineering benefits . This article explains the advantages and disadvantages of corona effect in detail, with examples relevant to modern electrical power systems. ✅ Advantages of Corona Effect Increase in Virtual Conductor Diameter Due to corona formation, the surrounding air becomes partially conductive, increasing the virtual diameter of the conductor. This reduces electrostatic stress between conductors and minimizes insulation breakdown risks. Related Reading: Electrostatic Fields in High Voltage Engineering Reduction of Transient Surges Corona acts like a natural cushion for sudden ...

ADVANTAGES OF INTERCONNECTED GRID SYSTEM

Interconnected Grid System: Working, Advantages, Disadvantages, and Comparison with Isolated Grids Author: Engr. Aneel Kumar Figure 1: Infographic showing key advantages of an interconnected grid system. Introduction An interconnected grid system refers to a network of multiple power generation sources, transmission lines, substations, and distribution systems that are linked across regions, states, or even countries. Unlike an isolated grid (or islanded grid) which operates independently, an interconnected grid allows electricity to flow between interconnected nodes, enabling numerous benefits and some trade-offs. In today’s energy landscape—where demand, renewable generation, reliability, and cost pressure are all increasing—understanding how an interconnected grid works, what factors are essential, and what its advantages and disadvantages are is critical for utility planners, reg...

Control Strategies for TCSC: Techniques for Dynamic Power Flow Management

Introduction As power transmission networks grow more complex, real-time voltage and impedance control becomes essential for ensuring grid reliability. Thyristor Controlled Series Capacitors (TCSC) play a key role in dynamically adjusting transmission line reactance, but their effectiveness depends on advanced control strategies . Different control methodologies —ranging from open-loop and closed-loop systems to AI-driven predictive models —allow TCSC to optimize power flow, improve stability, and enhance energy efficiency . In this article, we will explore: ✅ Different types of TCSC control strategies ✅ The role of real-time monitoring in optimizing power flow ✅ How AI and machine learning improve TCSC performance Keywords:   AI-Based Power Flow Control,  TCSC Dynamic Impedance Regulation,  Real-Time Voltage Stabilization,  Smart Grid FACTS Controllers Understanding TCSC Control Strategies A TCSC regulates transmission line reactance by adjusting thyristor switch...

DIFFERENCE BETWEEN GRID STATION AND SUB STATION

An electrical power substation is a conversion point between transmission level voltages (such as 138 KV) and distribution level voltages (such as 11 KV). A substation has one or more step-down transformers and serves a regional area such as part of a city or neighborhood. Substations are connected to each other by the transmission ring circuit. An electrical grid station is an interconnection point between two transmission ring circuits, often between two geographic regions. They might have a transformer, depending on the possibly different voltages, so that the voltage levels can be adjusted as needed. The interconnected network of grid stations is called the grid, and may ultimately represent an entire multi-state region. In this configuration, loss of a small section, such as loss of a power station, does not impact the grid as a whole, nor does it impact the more localized neighborhoods, as the grid simply shifts its power flow to compensate, giving the power station o...