Skip to main content

ELECTRICAL POWER BALANCING AUTHORITIES AND ITS RESPONSIBILITIES

Balancing authorities are responsible for the performance of the electric system is to ensure that at every moment of time there is sufficient generation to reliably supply the customer requirements and all associated delivery system losses. The process is complicated by the fact that the customer load changes continuously and, therefore, the generation must adjust immediately, either up or down, to accommodate the load change. Since electric power cannot be stored, the generation change must be accomplished by a physical adjustment of the equipment generating the electricity.

The Balancing Authority Areas vary greatly in both geographic size and the amount of generation/ load they control.

AREA CONTROL

Each Balancing Authority is responsible for maintaining its own load/generation balance, including its scheduled interchange, either purchases or sales. A Balancing Authority can consist of a generator or group of generators, an individual company, or a portion of a company or a group of companies, providing that it meets certain certification criteria. Since minute-by-minute customer load changes are not known in advance, a system has been developed whereby generation changes are made in response to load changes. This system is based on the concept of the area control error. The sum of the internal generation within a Balancing Area and the net flow on its interties is equal to the customer load and all transmission losses within the area. The net power flow into/out of the area should be equal to the net of all transactions between parties in the area and parties outside the area. To determine the net schedule transactions, the various commercial interests that are within the area are required to notify the Balancing Authority personnel (via the Interchange Coordinator) of their bilateral contractual arrangements on an ongoing basis for either sales or purchases of electricity with entities outside the area’s boundaries. Additionally, neighboring operating entities engaged in transactions that will cause power to flow through the Balancing Area are required to notify the Balancing Authority (through the Interchange Authority) and to make provision for the attendant transmission losses.

With this information, the Balancing Authorities can compare the total scheduled interchange into or out of the control area with the actual interchange. If the flow into the area exceeds the schedule for that time period, internal generation must be increased. Conversely, if the net flow is below the schedule, generation within the area must be reduced. Operationally, this is an ongoing process conducted every few seconds. Since these adjustments are going on simultaneously in all balancing areas, the adjustments balance out.

Each Balancing Authority also participates in maintaining the average system frequency at 50 or 60 hertz. The system frequency can deviate from normal when a large generating unit or block of load is lost. In addition to adjustments made because of variations of tie flows from schedule, another adjustment is made to correct frequency deviations. Each Balancing Authority is required to have an adjustment factor related to frequency in its control logic. The term is called the tie-line frequency bias (expressed in mW/0.1 Hz).

Additionally, since the control process is responsive, there can be a drift in average system frequency, which, in turn, affects the accuracy of any electric clocks. This variation is monitored and for a period of time the target frequency reference is adjusted to produce the required compensation. This process is called time error correction.

OPERATING RESERVES

Each Balancing Authority must provide operating reserves to restore its tie flows to schedule within 15 minutes following the loss of a generator within the area. Operating reserves consist of spinning and non-spinning reserves. Spinning reserve is generation that is synchronized and available to supply incremental load in a specified time period. Non-spinning reserve is not synchronized but can be made available within a short period of time. Interruptible load disconnection and coordinated adjustments to interchange schedules can be considered as part of operating reserve.

With the restructuring of the industry; the emergence of merchant power plant owners; the development of ISOs, RTOs, and for-profit transmission companies; and the implementation of retail access in some regulatory jurisdictions, assigning all reliability responsibilities to balancing authorities made the job of defining and applying standards more and more complicated. This was further complicated since some balancing areas are acting as transmission service providers.

The ongoing adjustments to generation levels within each balancing area are, of course, done by computer-based control systems that send signals to generators that provide needed adjustments (i.e., regulation), either up or down.

Comments

Popular posts from this blog

PRIMARY SECONDARY AND TERTIARY FREQUENCY CONTROL IN POWER SYSTEMS

Primary, Secondary and Tertiary Frequency Control in Power Systems Author: Engr. Aneel Kumar Keywords: frequency control, primary frequency control, automatic generation control (AGC), tertiary control, load-frequency control, grid stability. Frequency control keeps the power grid stable by balancing generation and load. When generation and demand drift apart, system frequency moves away from its nominal value (50 or 60 Hz). Grids rely on three hierarchical control layers — Primary , Secondary (AGC), and Tertiary — to arrest frequency deviation, restore the set-point and optimize generation dispatch. Related: Power System Stability — causes & mitigation Overview of primary, secondary and tertiary frequency control in power systems. ⚡ Primary Frequency Control (Droop Control) Primary control is a fast, local response implemented by generator governors (dro...

Advantages of Per Unit System in Power System Analysis | Electrical Engineering

  Advantages of Per Unit System in Power System Analysis In electrical power engineering, the per unit (p.u.) system is one of the most widely used techniques for analyzing and modeling power systems. It is a method of expressing electrical quantities — such as voltage, current, power, and impedance — as fractions of chosen base values rather than their actual numerical magnitudes. This normalization technique provides a universal language for system calculations, minimizing errors, simplifying transformer modeling, and enabling consistency across multiple voltage levels. Because of these benefits, the per unit system is essential in fault analysis, load flow studies, transformer testing, and short-circuit calculations . ⚡ What is the Per Unit System? The per unit system is defined as: Q u a n t i t y ( p u ) = A c t u a l   V a l u e B a s e   V a l u e Quantity_{(pu)} = \dfrac{Actual \ Value}{Base \ Value} Q u an t i t y ( p u ) ​ = B a se   ...

CASCADED TRANSFORMERS METHOD FOR GENERATING AC HIGH VOLTAGE

High-Frequency AC High Voltage Generation Using Cascaded Transformers Author: Engr. Aneel Kumar Figure 1: Infographic representation of cascaded transformers method for generating high AC voltages. Introduction In high voltage engineering , generating very high alternating current (AC) voltages is essential for testing equipment like insulators, circuit breakers, power cables, and other apparatus. One common and effective method for producing such voltages is the cascaded transformers method . This technique uses a series connection of specially designed test transformers , where the secondary of one transformer feeds the primary of the next. In this way, voltages are built up step by step, achieving levels in the range of hundreds of kilovolts (kV) or even megavolts (MV). Working Principle The principle of cascaded connection relies on the fact that each...

ADVANTAGES AND DISADVANTAGES OF CORONA EFFECT IN TRANSMISSION LINES | ELECTRICAL ENGINEERING GUIDE

Advantages and Disadvantages of Corona Effect in Power Systems In high-voltage overhead transmission lines , the corona effect plays a critical role in system performance. Corona occurs when the air around a conductor becomes ionized due to high electric stress. While often seen as a drawback because of power losses and interference , it also provides certain engineering benefits . This article explains the advantages and disadvantages of corona effect in detail, with examples relevant to modern electrical power systems. ✅ Advantages of Corona Effect Increase in Virtual Conductor Diameter Due to corona formation, the surrounding air becomes partially conductive, increasing the virtual diameter of the conductor. This reduces electrostatic stress between conductors and minimizes insulation breakdown risks. Related Reading: Electrostatic Fields in High Voltage Engineering Reduction of Transient Surges Corona acts like a natural cushion for sudden ...

ADVANTAGES OF INTERCONNECTED GRID SYSTEM

Interconnected Grid System: Working, Advantages, Disadvantages, and Comparison with Isolated Grids Author: Engr. Aneel Kumar Figure 1: Infographic showing key advantages of an interconnected grid system. Introduction An interconnected grid system refers to a network of multiple power generation sources, transmission lines, substations, and distribution systems that are linked across regions, states, or even countries. Unlike an isolated grid (or islanded grid) which operates independently, an interconnected grid allows electricity to flow between interconnected nodes, enabling numerous benefits and some trade-offs. In today’s energy landscape—where demand, renewable generation, reliability, and cost pressure are all increasing—understanding how an interconnected grid works, what factors are essential, and what its advantages and disadvantages are is critical for utility planners, reg...

Control Strategies for TCSC: Techniques for Dynamic Power Flow Management

Introduction As power transmission networks grow more complex, real-time voltage and impedance control becomes essential for ensuring grid reliability. Thyristor Controlled Series Capacitors (TCSC) play a key role in dynamically adjusting transmission line reactance, but their effectiveness depends on advanced control strategies . Different control methodologies —ranging from open-loop and closed-loop systems to AI-driven predictive models —allow TCSC to optimize power flow, improve stability, and enhance energy efficiency . In this article, we will explore: ✅ Different types of TCSC control strategies ✅ The role of real-time monitoring in optimizing power flow ✅ How AI and machine learning improve TCSC performance Keywords:   AI-Based Power Flow Control,  TCSC Dynamic Impedance Regulation,  Real-Time Voltage Stabilization,  Smart Grid FACTS Controllers Understanding TCSC Control Strategies A TCSC regulates transmission line reactance by adjusting thyristor switch...

DIFFERENCE BETWEEN GRID STATION AND SUB STATION

An electrical power substation is a conversion point between transmission level voltages (such as 138 KV) and distribution level voltages (such as 11 KV). A substation has one or more step-down transformers and serves a regional area such as part of a city or neighborhood. Substations are connected to each other by the transmission ring circuit. An electrical grid station is an interconnection point between two transmission ring circuits, often between two geographic regions. They might have a transformer, depending on the possibly different voltages, so that the voltage levels can be adjusted as needed. The interconnected network of grid stations is called the grid, and may ultimately represent an entire multi-state region. In this configuration, loss of a small section, such as loss of a power station, does not impact the grid as a whole, nor does it impact the more localized neighborhoods, as the grid simply shifts its power flow to compensate, giving the power station o...