Skip to main content

CAUSES OF ELECTRICAL POWER OUTAGES

Interruptions in the supply of electricity to customers can occur at any hour of the day or night and can last from fractions of a second to many hours or even days. Interruptions can be caused by disturbances to or malfunctions of any of the three components of the power system: generation, transmission, or distribution. They can also be caused by the unavailability of adequate resources to supply the customer load. These two attributes of reliability are characterized by NERC as security and adequacy.

Data shows that over 90% of customer outages are caused by problems originating on the local distribution system. Although generation and transmission-related outages are less common than those related to the distribution system, they often have much more serious consequences because of the number of customers affected and the duration of the outage.



Disturbances can be initiated by:

1) External events such as:
  • Environmental factors, including wind, rain, lightening, ice, fire, floods, and earthquakes
  • Accidents such as cars hitting poles
  • Sabotage (sadly)
2) Internal events such as
  • Insufficient resources
  • Failure of equipment due to electrical or mechanical stresses
  • Operating errors or decisions
Lack of resources can be due to:

1) Insufficient generation caused by
  • Low load forecasts
  • Shortages of fuel due to supply disruptions or delivery/transportation problems
  • Opposition to the construction of required new generating capacity
  • Failure of equipment due to electrical or mechanical stresses poor planning
  • Excessive maintenance outages
  • Regulatory actions restricting the operation of power plants
  • Transmission constraints
  • Generation being retired because it is noncompetitive in the new competitive market
2) Insufficient transmission or distribution caused by:
  • Low load forecasts
  • Opposition to the construction of required new transmission or distribution lines
  • Failure of equipment due to electrical or mechanical stresses
  • Poor planning
  • Intentional outages required because of other infrastructure work, such as the widening of roads
The duration of the interruption will be affected by the severity of the disturbance, the power system facilities affected, the redundancy or reserve built into the system, and the preparedness of the involved operating entities to respond. Some interruptions are of very short duration because the disturbance is transient and the system self-corrects. Some interruptions, such as those caused by tornadoes or ice storms, damage significant portions of the system, requiring many days to restore service. When there are insufficient generation resources, the outages may be of a controlled and rotating nature. Their duration might be only during peak load hours.

The extent of the interruption will be determined by the initiating disturbances and the facilities affected. For example, cascading outages caused by a fault occurring when a system is operating above a safe level can involve many states, as can a widespread ice storm. Conversely, a distribution pole damaged by a car may affect only a few homes.

An increasingly important aspect of power system reliability is the quality of service or power quality. With the increasing importance of computers and new electronic communication procedures, imperfections in electric service become increasingly important to the customer. Such imperfections include:
  • Momentary interruptions
  • Voltages outside of acceptable limits
  • Voltage dips of very short duration
Protection against power quality imperfections can often be handled by the consumer. Pressure is mounting, however, for the supplier to improve quality. This raises the question of the responsibility for such improvements in a deregulated power industry with separate companies providing distribution, transmission, and power supply services

Comments

Popular posts from this blog

PRIMARY SECONDARY AND TERTIARY FREQUENCY CONTROL IN POWER SYSTEMS

Primary, Secondary and Tertiary Frequency Control in Power Systems Author: Engr. Aneel Kumar Keywords: frequency control, primary frequency control, automatic generation control (AGC), tertiary control, load-frequency control, grid stability. Frequency control keeps the power grid stable by balancing generation and load. When generation and demand drift apart, system frequency moves away from its nominal value (50 or 60 Hz). Grids rely on three hierarchical control layers — Primary , Secondary (AGC), and Tertiary — to arrest frequency deviation, restore the set-point and optimize generation dispatch. Related: Power System Stability — causes & mitigation Overview of primary, secondary and tertiary frequency control in power systems. ⚡ Primary Frequency Control (Droop Control) Primary control is a fast, local response implemented by generator governors (dro...

Breaker Schemes in Substations

Breaker Schemes in Substations — Types, Design, Advantages, Disadvantages, and Comparison Author: Engr. Aneel Kumar Figure 1: Infographic overview of breaker schemes commonly used in substations. Introduction The breaker scheme or busbar arrangement in a substation defines how incoming feeders, outgoing feeders, and power transformers are connected to the bus. The choice of scheme has a direct impact on system reliability, maintainability, safety, and cost . A simple bus scheme is economical but vulnerable to outages, while advanced schemes such as breaker-and-a-half or double-bus/double-breaker provide very high reliability but at much higher cost and design complexity. Engineers select breaker schemes considering fault tolerance, maintenance needs, space requirements, expansion possibilities, protection coordination, and capital investment . Below, we explain eac...

SYMMETRICAL COMPONENT ANALYSIS

Unbalanced three phase systems can be split into three balanced components, namely Positive Sequence (balanced and having the same phase sequence as the unbalanced supply), Negative Sequence (balanced and having the opposite phase sequence to the unbalanced supply) and Zero Sequence (balanced but having the same phase and hence no phase sequence). These are known as the Symmetrical Components or the Sequence Components and are shown in figure 2.10. The phase components are the addition of the symmetrical components and can be written as follows.  a = a 1 + a 2 + a 0 b = b 1 + b 2 + b 0 c = c 1 + c 2 + c 0 The unknown unbalanced system has three unknown magnitudes and three unknown angles with respect to the reference direction. Similarly, the combination of the 3 sequence components will also have three unknown magnitudes and three unknown angles with respect to the reference direction. Thus the original unbalanced system effectively has 3 complex unknown quan...

TYPES OF ELECTRIC LOADS

Devices that are connected to the power system are referred to as electrical loads. Toasters, refrigerators, bug zappers, and so on are considered electrical loads. There are three types of electrical loads. They vary according to their leading or lagging time relationship between voltage and current. The three load types are resistive, inductive, and capacitive. Each type has specific characteristics that make them unique. Understanding the differences between these load types will help explain how power systems can operate efficiently. Power system engineers, system operators, maintenance personnel, and others try to maximize system efficiency on a continuous basis by having a good understanding of the three types of loads. They understand how having them work together can minimize system losses, provide additional equipment capacity, and maximize system reliability. The three different types of load are summarized below. 1) RESISTIVE LOAD: The resistance in a wire (i.e., cond...

SOLIDLY GROUNDED NEUTRAL SYSTEMS

Solidly grounded systems are usually used in low voltage applications at 600 volts or less. In solidly grounded system, the neutral point is connected to earth. Solidly Neutral Grounding slightly reduces the problem of transient over voltages found on the ungrounded system and provided path for the ground fault current is in the range of 25 to 100% of the system three phase fault current.. However, if the reactance of the generator or transformer is too great, the problem of transient over voltages will not be solved. While solidly grounded systems are an improvement over ungrounded systems, and speed up the location of faults, they lack the current limiting ability of resistance grounding and the extra protection this provides. To maintain systems health and safe, Transformer neutral is grounded and grounding conductor must be extend from the source to the furthest point of the system within the same raceway or conduit. Its purpose is to maintain very low impedance to ground faults so...

ESSENTIAL ELEMENTS OF DIESEL POWER PLANT

FUEL SUPPLY SYSTEM OF DIESEL POWER PLANT It consists of storage tank, strainers, fuel transfer pump and all day fuel tanks. The fuel oil is supplied at the plant site by rail or road. The oil is stored in the storage tank. From the storage tank, oil is pumped to smaller all day tank at daily or short intervals. From this tank, fuel oil is passed through strainers to remove suspended impurities. The clean oil is injected into the engine by fuel injection pump. AIR INTAKE SYSTEM OF DIESEL POWER PLANT This system supplies necessary air to the engine for fuel combustion. It consists of pipes for the supply of fresh air to the engine manifold. Filters are provided to remove dust particles from air which may act as abrasive in the engine cylinder. Because a diesel engine requires close tolerances to achieve its compression ratio, and because most diesel engines are either turbocharged or supercharged, the air entering the engine must be clean, free of debris, and as cool as possible. ...

ADVANTAGES AND DISADVANTAGES OF CORONA EFFECT IN TRANSMISSION LINES | ELECTRICAL ENGINEERING GUIDE

Advantages and Disadvantages of Corona Effect in Power Systems In high-voltage overhead transmission lines , the corona effect plays a critical role in system performance. Corona occurs when the air around a conductor becomes ionized due to high electric stress. While often seen as a drawback because of power losses and interference , it also provides certain engineering benefits . This article explains the advantages and disadvantages of corona effect in detail, with examples relevant to modern electrical power systems. ✅ Advantages of Corona Effect Increase in Virtual Conductor Diameter Due to corona formation, the surrounding air becomes partially conductive, increasing the virtual diameter of the conductor. This reduces electrostatic stress between conductors and minimizes insulation breakdown risks. Related Reading: Electrostatic Fields in High Voltage Engineering Reduction of Transient Surges Corona acts like a natural cushion for sudden ...