Skip to main content

TURN TO TURN PROTECTION SCHEMES OF SHUNT REACTOR

Turn-to-turn faults in shunt reactor present a formidable challenge to the protection engineer. The current and the voltage changes encountered during such fault are very small and therefore sensitive and reliable protection against turn-to-turn faults is difficult to achieve. At the same time the longitudinal differential protection offers no protection at all for such faults. Hence special protection schemes shall be employed.

One such scheme, often used in certain countries, utilizes a fact that the HV shunt reactor winding is often made of two half-windings connected in parallel (i.e. the HV lead is brought out at the mid point of the winding, and the two neutral leads at the bottom and the top of the winding). This gives the opportunity to install two CTs in the winding star point (i.e. one in each winding part). Then so-called split phase differential protection can be utilized to detect turn-to-turn faults. However this protection scheme have the following drawbacks:

• this special CT arrangement typically causes reactor manufacturing problems

• typically low CT ratio is required, which can cause longitudinal differential protection problems during reactor switching in, if the same CTs are used for both differential protections

• this scheme can be only used if the shunt reactor is specifically ordered with these CTs

Second turn-to-turn protection scheme for shunt reactors, successfully used in some other counties, utilize the following facts:

• HV power system voltages are well balanced during normal load conditions

• Modern HV, oil immersed shunt reactors have very small manufacturing asymmetry between individual phases

• Shunt reactor winding impedance is approximately proportional to the square of the number of active turns

• Short circuit between some number of turns will cause the decrease of the winding impedance only in the faulty phase and corresponding small raise of the shunt reactor neutral point current

• Currents during turn-to-turn fault are of the small magnitude and they will not produce any sufficient unbalance voltage

• Any external cause of neutral point current (i.e. external phase to ground fault) will cause appearance of unbalance voltage which can be used to block the operation of turn-to-turn protection scheme

• In case of a bigger winding turn-to-turn fault which might cause the sufficient voltage unbalance, sensitive directional zero sequence relay connected on the shunt reactor HV side and set to look into the reactor shall be capable to detect such fault This protection scheme was developed even before multifunctional numerical relays were available. To implement such shunt reactor turn-to-turn protection scheme within multi-functional numerical relay utilizing its graphical configuration facilities, and readily available logical gates, timers etc. shall not be a big problem for a protection engineer.

In order to verify above statements, shunt reactor behavior, for phase A winding 1% turn-to-turn faults, is verified by an ATP simulation and it is shown in Figures 21 & 22. From these figures is obvious that the above-described scheme can be successfully implemented if the power system itself is well balanced.

Figure 21: Internal Phase A Winding turn-to-turn fault, Phase Currents
Figure 22: Internal Phase A Winding turn-to-turn fault, Zero-sequence Quantities

Comments

Popular posts from this blog

PRIMARY SECONDARY AND TERTIARY FREQUENCY CONTROL IN POWER SYSTEMS

Primary, Secondary and Tertiary Frequency Control in Power Systems Author: Engr. Aneel Kumar Keywords: frequency control, primary frequency control, automatic generation control (AGC), tertiary control, load-frequency control, grid stability. Frequency control keeps the power grid stable by balancing generation and load. When generation and demand drift apart, system frequency moves away from its nominal value (50 or 60 Hz). Grids rely on three hierarchical control layers — Primary , Secondary (AGC), and Tertiary — to arrest frequency deviation, restore the set-point and optimize generation dispatch. Related: Power System Stability — causes & mitigation Overview of primary, secondary and tertiary frequency control in power systems. ⚡ Primary Frequency Control (Droop Control) Primary control is a fast, local response implemented by generator governors (dro...

ADVANTAGES AND DISADVANTAGES OF CORONA EFFECT IN TRANSMISSION LINES | ELECTRICAL ENGINEERING GUIDE

Advantages and Disadvantages of Corona Effect in Power Systems In high-voltage overhead transmission lines , the corona effect plays a critical role in system performance. Corona occurs when the air around a conductor becomes ionized due to high electric stress. While often seen as a drawback because of power losses and interference , it also provides certain engineering benefits . This article explains the advantages and disadvantages of corona effect in detail, with examples relevant to modern electrical power systems. ✅ Advantages of Corona Effect Increase in Virtual Conductor Diameter Due to corona formation, the surrounding air becomes partially conductive, increasing the virtual diameter of the conductor. This reduces electrostatic stress between conductors and minimizes insulation breakdown risks. Related Reading: Electrostatic Fields in High Voltage Engineering Reduction of Transient Surges Corona acts like a natural cushion for sudden ...

CASCADED TRANSFORMERS METHOD FOR GENERATING AC HIGH VOLTAGE

High-Frequency AC High Voltage Generation Using Cascaded Transformers Author: Engr. Aneel Kumar Figure 1: Infographic representation of cascaded transformers method for generating high AC voltages. Introduction In high voltage engineering , generating very high alternating current (AC) voltages is essential for testing equipment like insulators, circuit breakers, power cables, and other apparatus. One common and effective method for producing such voltages is the cascaded transformers method . This technique uses a series connection of specially designed test transformers , where the secondary of one transformer feeds the primary of the next. In this way, voltages are built up step by step, achieving levels in the range of hundreds of kilovolts (kV) or even megavolts (MV). Working Principle The principle of cascaded connection relies on the fact that each...

ADVANTAGES OF INTERCONNECTED GRID SYSTEM

Interconnected Grid System: Working, Advantages, Disadvantages, and Comparison with Isolated Grids Author: Engr. Aneel Kumar Figure 1: Infographic showing key advantages of an interconnected grid system. Introduction An interconnected grid system refers to a network of multiple power generation sources, transmission lines, substations, and distribution systems that are linked across regions, states, or even countries. Unlike an isolated grid (or islanded grid) which operates independently, an interconnected grid allows electricity to flow between interconnected nodes, enabling numerous benefits and some trade-offs. In today’s energy landscape—where demand, renewable generation, reliability, and cost pressure are all increasing—understanding how an interconnected grid works, what factors are essential, and what its advantages and disadvantages are is critical for utility planners, reg...

REVERSING DIRECTION OF ROTATION OF UNIVERSAL MOTOR

The direction of rotation of a universal motor can be changed by either: (i) Reversing the field connection with respect to those of armature; or (ii) By using two field windings wound on the core in opposite directions so that the one connected in series with armature gives clockwise rotation, while the other in series with the armature gives counterclockwise rotation. The second method, i.e, the two field method is used in applications such as motor operated rheostats and servo systems. This method has somewhat simpler connections than the first method. For simple applications like portable drills etc. manual switches are frequently used for reversing the direction of rotation of the motor. Figure  1 (a and b) shows how a DPDT (Double Pole Double Throw) switch and a three position switch may be used for reversing the direction of rotation of single field and double field type of motors respectively. Figure 1 Reversing of a universal motor (a) Armature re...

Factors Affecting Corona in Overhead Transmission Lines

Factors Affecting Corona in Overhead Transmission Lines Author: Engr. Aneel Kumar Figure 1: Infographic illustrating the factors influencing corona discharge in transmission lines. Introduction The corona effect in overhead transmission lines is a phenomenon that occurs when the electric field intensity around conductors exceeds a critical value, causing ionization of the surrounding air. This ionization produces bluish light, hissing sound, power loss, and ozone gas. While corona may seem undesirable, it also has a few advantages such as reducing overvoltages by absorbing surges. Corona directly impacts power system efficiency, transmission losses, equipment life, and design cost . Therefore, engineers must understand the factors affecting corona in detail to ensure efficient and reliable design of high-voltage transmission systems. 1. Conductor Size (Diameter) ...

Control Strategies for TCSC: Techniques for Dynamic Power Flow Management

Introduction As power transmission networks grow more complex, real-time voltage and impedance control becomes essential for ensuring grid reliability. Thyristor Controlled Series Capacitors (TCSC) play a key role in dynamically adjusting transmission line reactance, but their effectiveness depends on advanced control strategies . Different control methodologies —ranging from open-loop and closed-loop systems to AI-driven predictive models —allow TCSC to optimize power flow, improve stability, and enhance energy efficiency . In this article, we will explore: ✅ Different types of TCSC control strategies ✅ The role of real-time monitoring in optimizing power flow ✅ How AI and machine learning improve TCSC performance Keywords:   AI-Based Power Flow Control,  TCSC Dynamic Impedance Regulation,  Real-Time Voltage Stabilization,  Smart Grid FACTS Controllers Understanding TCSC Control Strategies A TCSC regulates transmission line reactance by adjusting thyristor switch...