Skip to main content

COOLING METHODS OF POWER TRANSFORMER

As the size and capacity of the transformer increased, the associated cooling arrangement become more powerful and sophisticated. So, by definition, the transformer cooling system is such arrangement for power transformers, which limits the generated heat into a safe value by means of proper dissipation of generated heat. Different cooling system is used for different types of transformers, and they are discussed as follows.

Generally, two types of transformers are there according to the use of insulating oil, namely Dry Type Transformers and Oil Immersed Type Transformers. In oil immersed type, the transformer core is immersed into the transformer oil. Different types of cooling are needed for these two categories. In dry type transformers, air is used as the coolant medium but in oil immersed transformer (as the size and ratings both are high), both air and transformer oil are used as the coolant medium.
Dry Type Transformers
       Oil Immersed Transformers
            Air Natural Type
  Oil Natural Air Natural type (ONAN)
            Air forced Type
  Oil Natural Air forced Type (ONAf)
  Oil forced Air forced Type (OfAf)
  Oil Directed Air forced Type (ODAf)
  Oil forced Water forced Type (OfWf)

Air Natural Type:

This cooling method is used in dry type transformer with smaller ratings. As the name implies, the natural circulation of atmospheric air is used in this technique. This type of transformers is also referred as self-cooled transformer. When the transformer is operated in full load, then the temperature of the transformer becomes greater than the ambient air temperature. So, by convection process, the light and heated air gets replaced by the heavy and comparatively cool surrounding air. In this way, the generated heat is dissipated via the natural air circulation process. But this type of cooling arrangement provides satisfactory operation for low voltage transformers only.

Air forced type:

This cooling method is also used in dry type transformer but the application is also implemented in oil immersed transformers. As the name implies, in addition with natural air circulation, cool air with high velocity is provided to the core. High speed fans are provided with the transformer, and by the rotation of this fan high velocity of air is subjected to the transformer. This additional air force ensures quicker heat dissipation of the transformers. The fans are automatically controlled, that is when the temperature of the transformer core goes beyond the safe limit than all the fans are switched ON. Air forced cooling method provides better performance than natural air cooling, but additional cost is associated for the fans.

Oil Natural Air Natural (ONAN) Cooling Of Transformer:

This cooling system is used in oil immersed type transformers. This is the simplest way of cooling of oil immersed transformers. We know that, the transformer core is immersed in transformer oil. When the transformer is heated up, then temperature of oil near to the transformer core is also raised. So, the light and heated oil flows in upward direction and comparatively cool and heavy oil takes the vacuum places by natural convection process. And the heated oil releases its temperature into the atmosphere. In this way, a natural oil circulation cycle is generated and this cycle continues until the transformer temperature is tapped into a safe limit. In this method, the surface area of the oil tank is usually larger, as more surface area provides more quick heat dissipation process. But to provide more surface areas, several hollows tubular plates are attached with the transformer and they are termed as radiator. When the hot oils are circulating through the radiators, they get more surface area so the cooling rate is much higher. Also the light and heated air gets replaced by the heavy and comparatively cool surrounding air by natural process. In this way, the generated heat is dissipated via the natural air circulation process as well as natural oil circulation.

Oil Natural Air forced (ONAF) Cooling of Transformer:

The word ‘forced’ signifies that, air is forcefully applied to the transformer. High speed fans are provided with this type of cooling system. In larger rated oil immersed transformers, natural air and oil cooling is not sufficient. So, additional air force is applied to the radiator by means of those fans and this method provides quicker heat dissipation of the transformers as compared to natural oil and air cooling. All fans are automatically controlled, whenever the temperature of the transformer goes beyond the safe limit than all the fans are switched ON. But here the oil circulation process made by natural convection, that is no oil pumps are provided for this type of cooling. This method provides better performance than natural oil and air cooling, but there is an additional cost due to the fans.

Oil forced Air forced (OfAf) Cooling of Transformer:

Actually, for very large rated oil immersed transformers, heat generated is quite high. Therefore, some special cooling techniques are applied in order to provide sufficient heat dissipation. In Oil forced Air forced cooling system, both oil and air are circulated at high speed by some additional configuration. High speed fans are connected to provide additional air flow of high velocity and oil pumps are provided to circulate the oil at high velocity. So, hot oil is circulated inside the main transformer tank at larger velocity, so the rate of cooling is further increased. Therefore, in oil forced air forced cooling system; both the oil and air are forcefully applied to achieve more fast cooling process.

Oil Directed Air forced Cooling of Transformer:

This is the updated version of Oil forced Air forced cooling method. Here the Oil and Air both are applied forcefully, but the hot oil follows a specific route for flowing. Convection channels are made closer to the winding of the transformer and the transformer oil is passed through those channels. In this way, superior heat dissipation is occurred.

Oil forced Water forced Cooling of Transformer:

Water is far better coolant than atmospheric air. So, in this method water is used as the oil coolant instead of natural air. Here, the flow of hot oil is directed to a heat ex-changer where water shower is applied. So, here the oil is cooled at faster rate than natural air cooling.

Therefore, from the above discussion, we understood the necessity of transformer cooling and also learned about the various types of transformer cooling.

Comments

Nice post! Thanks for sharing!

Popular posts from this blog

PRIMARY SECONDARY AND TERTIARY FREQUENCY CONTROL IN POWER SYSTEMS

Primary, Secondary and Tertiary Frequency Control in Power Systems Author: Engr. Aneel Kumar Keywords: frequency control, primary frequency control, automatic generation control (AGC), tertiary control, load-frequency control, grid stability. Frequency control keeps the power grid stable by balancing generation and load. When generation and demand drift apart, system frequency moves away from its nominal value (50 or 60 Hz). Grids rely on three hierarchical control layers — Primary , Secondary (AGC), and Tertiary — to arrest frequency deviation, restore the set-point and optimize generation dispatch. Related: Power System Stability — causes & mitigation Overview of primary, secondary and tertiary frequency control in power systems. ⚡ Primary Frequency Control (Droop Control) Primary control is a fast, local response implemented by generator governors (dro...

Breaker Schemes in Substations

Breaker Schemes in Substations — Types, Design, Advantages, Disadvantages, and Comparison Author: Engr. Aneel Kumar Figure 1: Infographic overview of breaker schemes commonly used in substations. Introduction The breaker scheme or busbar arrangement in a substation defines how incoming feeders, outgoing feeders, and power transformers are connected to the bus. The choice of scheme has a direct impact on system reliability, maintainability, safety, and cost . A simple bus scheme is economical but vulnerable to outages, while advanced schemes such as breaker-and-a-half or double-bus/double-breaker provide very high reliability but at much higher cost and design complexity. Engineers select breaker schemes considering fault tolerance, maintenance needs, space requirements, expansion possibilities, protection coordination, and capital investment . Below, we explain eac...

SYMMETRICAL COMPONENT ANALYSIS

Unbalanced three phase systems can be split into three balanced components, namely Positive Sequence (balanced and having the same phase sequence as the unbalanced supply), Negative Sequence (balanced and having the opposite phase sequence to the unbalanced supply) and Zero Sequence (balanced but having the same phase and hence no phase sequence). These are known as the Symmetrical Components or the Sequence Components and are shown in figure 2.10. The phase components are the addition of the symmetrical components and can be written as follows.  a = a 1 + a 2 + a 0 b = b 1 + b 2 + b 0 c = c 1 + c 2 + c 0 The unknown unbalanced system has three unknown magnitudes and three unknown angles with respect to the reference direction. Similarly, the combination of the 3 sequence components will also have three unknown magnitudes and three unknown angles with respect to the reference direction. Thus the original unbalanced system effectively has 3 complex unknown quan...

TYPES OF ELECTRIC LOADS

Devices that are connected to the power system are referred to as electrical loads. Toasters, refrigerators, bug zappers, and so on are considered electrical loads. There are three types of electrical loads. They vary according to their leading or lagging time relationship between voltage and current. The three load types are resistive, inductive, and capacitive. Each type has specific characteristics that make them unique. Understanding the differences between these load types will help explain how power systems can operate efficiently. Power system engineers, system operators, maintenance personnel, and others try to maximize system efficiency on a continuous basis by having a good understanding of the three types of loads. They understand how having them work together can minimize system losses, provide additional equipment capacity, and maximize system reliability. The three different types of load are summarized below. 1) RESISTIVE LOAD: The resistance in a wire (i.e., cond...

SOLIDLY GROUNDED NEUTRAL SYSTEMS

Solidly grounded systems are usually used in low voltage applications at 600 volts or less. In solidly grounded system, the neutral point is connected to earth. Solidly Neutral Grounding slightly reduces the problem of transient over voltages found on the ungrounded system and provided path for the ground fault current is in the range of 25 to 100% of the system three phase fault current.. However, if the reactance of the generator or transformer is too great, the problem of transient over voltages will not be solved. While solidly grounded systems are an improvement over ungrounded systems, and speed up the location of faults, they lack the current limiting ability of resistance grounding and the extra protection this provides. To maintain systems health and safe, Transformer neutral is grounded and grounding conductor must be extend from the source to the furthest point of the system within the same raceway or conduit. Its purpose is to maintain very low impedance to ground faults so...

ESSENTIAL ELEMENTS OF DIESEL POWER PLANT

FUEL SUPPLY SYSTEM OF DIESEL POWER PLANT It consists of storage tank, strainers, fuel transfer pump and all day fuel tanks. The fuel oil is supplied at the plant site by rail or road. The oil is stored in the storage tank. From the storage tank, oil is pumped to smaller all day tank at daily or short intervals. From this tank, fuel oil is passed through strainers to remove suspended impurities. The clean oil is injected into the engine by fuel injection pump. AIR INTAKE SYSTEM OF DIESEL POWER PLANT This system supplies necessary air to the engine for fuel combustion. It consists of pipes for the supply of fresh air to the engine manifold. Filters are provided to remove dust particles from air which may act as abrasive in the engine cylinder. Because a diesel engine requires close tolerances to achieve its compression ratio, and because most diesel engines are either turbocharged or supercharged, the air entering the engine must be clean, free of debris, and as cool as possible. ...

ADVANTAGES AND DISADVANTAGES OF CORONA EFFECT IN TRANSMISSION LINES | ELECTRICAL ENGINEERING GUIDE

Advantages and Disadvantages of Corona Effect in Power Systems In high-voltage overhead transmission lines , the corona effect plays a critical role in system performance. Corona occurs when the air around a conductor becomes ionized due to high electric stress. While often seen as a drawback because of power losses and interference , it also provides certain engineering benefits . This article explains the advantages and disadvantages of corona effect in detail, with examples relevant to modern electrical power systems. ✅ Advantages of Corona Effect Increase in Virtual Conductor Diameter Due to corona formation, the surrounding air becomes partially conductive, increasing the virtual diameter of the conductor. This reduces electrostatic stress between conductors and minimizes insulation breakdown risks. Related Reading: Electrostatic Fields in High Voltage Engineering Reduction of Transient Surges Corona acts like a natural cushion for sudden ...