Skip to main content

HETEROPOLAR DC GENERATORS

In the case of a hetero-polar generator the induced emf in a conductor goes through a cyclic change in voltage as it passes under north and south pole polarity alternately. The induced emf in the conductor therefore is not a constant but alternates in magnitude. For a constant velocity of sweep the induced emf is directly proportional to the flux density under which it is moving. If the flux density variation is sinusoidal in space, then a sine wave voltage is generated. This principle is used in the a.c generators. In the case of dc generators our aim is to get a steady d.c. voltage at the terminals of the winding and not the shape of the emf in the conductors. This is achieved by employing an external element, which is called a commutator, with the winding.


Fig. 5 shows an elementary hetero-polar, 2-pole machine and one-coil arma- ture. The ends of the coil are connected to a split ring which acts like a commutator. As the polarity of the induced voltages changes the connection to the brush also gets switched so that the voltage seen at the brushes has a unidirectional polarity. This idea is further developed in the modern day machines with the use of commutators. The brushes are placed on the commutator. Connection to the winding is made through the commutator only. The idea of a commutator is an ingenious one. Even though the instantaneous value of the induced emf in each conductor varies as a function of the flux density under which it is moving, the value of this emf is a constant at any given position of the conductor as the field is stationary. Similarly the sum of a set of coils also remains a constant. This thought is the one which gave birth to the commutator. The coils connected between the two brushes must be ”similarly located” with respect to the poles irrespective of the actual position of the rotor.

This can be termed as the condition of symmetry. If a winding satisfies this condition then it is suitable for use as an armature winding of a d.c. machine. The ring winding due to Gramme is one such. It is easy to follow the action of the d.c. machine using a ring winding, hence it is taken up here for explanation.

Fig. 6 shows a 2-pole, 12 coil, and ring wound armature of a machine. The 12 coils are placed at uniform spacing around the rotor. The junction of each coil with its neighbor is connected to a commutator segment. Each commutator segment is insulated from its neighbor by a mica separator. Two brushes A and B are placed on the commutator which looks like a cylinder. If one traces the connection from brush A to brush B one finds that there are two paths. In each path a set of voltages get added up. The sum of the emfs is constant (nearly). The constancy of this magnitude is altered by a small value corresponding to the coil short circuited by the brush. As we wish to have a maximum value for the output voltage, the choice of position for the brushes would be at the neutral axis of the field. If the armature is turned by a distance of one slot pitch the sum of emfs is seen to be constant even though a different set of coils participate in the addition. The coil which gets short circuited has nearly zero voltage induced in the same and hence the sum does not change substantially. This variation in the output voltage is called the ’ripple’. More the number of coils participating in the sum lesser would be the ’percentage’ ripple.

Another important observation from the working principle of a heterogeneous generator is that the actual shape of the flux density curve does not matter as long as the integral of the flux entering the rotor is held constant; which means that for a given flux per pole the voltage will be constant even if the shape of this flux density curve changes (speed and other conditions remaining unaltered). This is one reason why an average flux density over the entire pole pitch is taken and flux density curve is assumed to be rectangular.

A rectangular flux density wave form has some advantages in the derivation of the voltage between the brushes. Due to this form of the flux density curve, the induced emf in each turn of the armature becomes constant and equal to each other. With this back ground the emf induced between the brushes can be derived. The value of the induced in one conductor is given by

Ec = Bav.L.v  Volts ---------------- 7

where

Bav = Average flux density over a pole pitch, Tesla.
L = Length of the active conductor, m.
v = Velocity of sweep of conductor, m/sec.

If there are Z conductors on the armature and they form b pairs of parallel circuits between the brushes by virtue of their connections, then number of conductors in a series path is Z/2b. The induced emf between the brushes is

E = Ec ( Z/2B ) -------------------- 8 

E = Bav . L . v ( Z/2B )  Volts ----- 9

But v = (2p).Y.n where p is the pairs of poles Y is the pole pitch, in meters, and n is the number of revolutions made by the armature per second.

Also Bav can be written in terms of pole pitch Y , core length L, and flux per pole as

Bav =  phi / (L.Y)  Tesla -------- 10

Substituting in equation Eqn. 9,

=  [phi / (L.Y)] . L . ( 2p . Y .n ) . ( Z/2b ) 
E= phi . p . Zn / b  Volts ---------------- 11

The number of pairs of parallel paths is a function of the type of the winding chosen.

Comments

Popular posts from this blog

PRIMARY SECONDARY AND TERTIARY FREQUENCY CONTROL IN POWER SYSTEMS

Primary, Secondary and Tertiary Frequency Control in Power Systems Author: Engr. Aneel Kumar Keywords: frequency control, primary frequency control, automatic generation control (AGC), tertiary control, load-frequency control, grid stability. Frequency control keeps the power grid stable by balancing generation and load. When generation and demand drift apart, system frequency moves away from its nominal value (50 or 60 Hz). Grids rely on three hierarchical control layers — Primary , Secondary (AGC), and Tertiary — to arrest frequency deviation, restore the set-point and optimize generation dispatch. Related: Power System Stability — causes & mitigation Overview of primary, secondary and tertiary frequency control in power systems. ⚡ Primary Frequency Control (Droop Control) Primary control is a fast, local response implemented by generator governors (dro...

Breaker Schemes in Substations

Breaker Schemes in Substations — Types, Design, Advantages, Disadvantages, and Comparison Author: Engr. Aneel Kumar Figure 1: Infographic overview of breaker schemes commonly used in substations. Introduction The breaker scheme or busbar arrangement in a substation defines how incoming feeders, outgoing feeders, and power transformers are connected to the bus. The choice of scheme has a direct impact on system reliability, maintainability, safety, and cost . A simple bus scheme is economical but vulnerable to outages, while advanced schemes such as breaker-and-a-half or double-bus/double-breaker provide very high reliability but at much higher cost and design complexity. Engineers select breaker schemes considering fault tolerance, maintenance needs, space requirements, expansion possibilities, protection coordination, and capital investment . Below, we explain eac...

SYMMETRICAL COMPONENT ANALYSIS

Unbalanced three phase systems can be split into three balanced components, namely Positive Sequence (balanced and having the same phase sequence as the unbalanced supply), Negative Sequence (balanced and having the opposite phase sequence to the unbalanced supply) and Zero Sequence (balanced but having the same phase and hence no phase sequence). These are known as the Symmetrical Components or the Sequence Components and are shown in figure 2.10. The phase components are the addition of the symmetrical components and can be written as follows.  a = a 1 + a 2 + a 0 b = b 1 + b 2 + b 0 c = c 1 + c 2 + c 0 The unknown unbalanced system has three unknown magnitudes and three unknown angles with respect to the reference direction. Similarly, the combination of the 3 sequence components will also have three unknown magnitudes and three unknown angles with respect to the reference direction. Thus the original unbalanced system effectively has 3 complex unknown quan...

TYPES OF ELECTRIC LOADS

Devices that are connected to the power system are referred to as electrical loads. Toasters, refrigerators, bug zappers, and so on are considered electrical loads. There are three types of electrical loads. They vary according to their leading or lagging time relationship between voltage and current. The three load types are resistive, inductive, and capacitive. Each type has specific characteristics that make them unique. Understanding the differences between these load types will help explain how power systems can operate efficiently. Power system engineers, system operators, maintenance personnel, and others try to maximize system efficiency on a continuous basis by having a good understanding of the three types of loads. They understand how having them work together can minimize system losses, provide additional equipment capacity, and maximize system reliability. The three different types of load are summarized below. 1) RESISTIVE LOAD: The resistance in a wire (i.e., cond...

SOLIDLY GROUNDED NEUTRAL SYSTEMS

Solidly grounded systems are usually used in low voltage applications at 600 volts or less. In solidly grounded system, the neutral point is connected to earth. Solidly Neutral Grounding slightly reduces the problem of transient over voltages found on the ungrounded system and provided path for the ground fault current is in the range of 25 to 100% of the system three phase fault current.. However, if the reactance of the generator or transformer is too great, the problem of transient over voltages will not be solved. While solidly grounded systems are an improvement over ungrounded systems, and speed up the location of faults, they lack the current limiting ability of resistance grounding and the extra protection this provides. To maintain systems health and safe, Transformer neutral is grounded and grounding conductor must be extend from the source to the furthest point of the system within the same raceway or conduit. Its purpose is to maintain very low impedance to ground faults so...

ESSENTIAL ELEMENTS OF DIESEL POWER PLANT

FUEL SUPPLY SYSTEM OF DIESEL POWER PLANT It consists of storage tank, strainers, fuel transfer pump and all day fuel tanks. The fuel oil is supplied at the plant site by rail or road. The oil is stored in the storage tank. From the storage tank, oil is pumped to smaller all day tank at daily or short intervals. From this tank, fuel oil is passed through strainers to remove suspended impurities. The clean oil is injected into the engine by fuel injection pump. AIR INTAKE SYSTEM OF DIESEL POWER PLANT This system supplies necessary air to the engine for fuel combustion. It consists of pipes for the supply of fresh air to the engine manifold. Filters are provided to remove dust particles from air which may act as abrasive in the engine cylinder. Because a diesel engine requires close tolerances to achieve its compression ratio, and because most diesel engines are either turbocharged or supercharged, the air entering the engine must be clean, free of debris, and as cool as possible. ...

ADVANTAGES AND DISADVANTAGES OF CORONA EFFECT IN TRANSMISSION LINES | ELECTRICAL ENGINEERING GUIDE

Advantages and Disadvantages of Corona Effect in Power Systems In high-voltage overhead transmission lines , the corona effect plays a critical role in system performance. Corona occurs when the air around a conductor becomes ionized due to high electric stress. While often seen as a drawback because of power losses and interference , it also provides certain engineering benefits . This article explains the advantages and disadvantages of corona effect in detail, with examples relevant to modern electrical power systems. ✅ Advantages of Corona Effect Increase in Virtual Conductor Diameter Due to corona formation, the surrounding air becomes partially conductive, increasing the virtual diameter of the conductor. This reduces electrostatic stress between conductors and minimizes insulation breakdown risks. Related Reading: Electrostatic Fields in High Voltage Engineering Reduction of Transient Surges Corona acts like a natural cushion for sudden ...