OPERATION OF GENERATOR

The stator, also called the armature, carries the three-phase AC winding. The rotor, also called the field, carries the DC excitation or field winding. The field winding therefore rotates at the shaft speed and sets up the main magnetic flux in the machine.

The fundamental magnetic action between the stator and rotor is one of tangential pulling. In a generator, the rotor pole pulls the corresponding stator pole flux around with it. In a motor, the stator pole pulls the rotor pole flux around with it. The action is analogous to stretching a spring, the greater the power developed, the greater the pull and greater the corresponding distance that is created between the rotor and stator flux axes.

When a machine is not connected to the three-phase supply but is running at rated speed and with rated terminal voltage at the stator, there exists rated flux in the iron circuit and across the air gap. This flux cuts the stator winding and induces rated emf in winding and hence rated voltage at the main terminals. Consider what happens in a generator. Let the generator be connected to a load, or the live switchboard bus bars. Stator current is caused to flow. The current in the stator winding causes a stator flux to be created which tends to counteract the air-gap flux that is produced by the excitation. This reduction of air-gap flux causes the terminal voltage to fall. The terminal voltage can be restored by increasing the rotor excitation current and hence the flux. So the demagnetizing effect of the stator current can be compensated by increasing the field excitation current. This demagnetizing effect of the stator current is called ‘armature reaction’ and gives rise to what is known as the synchronous reactance, which is also called a ‘derived’ reactance.

Steady State Armature Reaction

The rotating field in the air gap of a synchronous machine is generally considered to be free of space harmonics, when the basic operation of the machine is being considered. In an actual machine there are space harmonics present in the air gap, more in salient pole machines than a cylindrical rotor machine. It is acceptable to ignore the effects of space harmonics when considering armature reaction and the associated reactance. Therefore the flux wave produced by the rotating field winding can be assumed to be distributed sinusoidally in space around the poles of the rotor and across the air gap.

If the stator winding, which consists of many coils that are basically connected as a series circuit, is not connected to a load then the resulting emf from all the coils is the open circuit emf of the phase winding. Closing the circuit on to a load causes a steady state current to flow in the stator coils. Each coil creates a flux and their total flux opposes the field flux from the rotor. The resulting flux in the air gap is reduced. The emf corresponding to the air-gap flux drives the stator current through the leakage reactance and conductor resistance of the stator coils. The voltage dropped across this winding impedance is small in relation to the air-gap voltage. Deducting this voltage drop from the air-gap voltage gives the terminal voltage of the loaded generator. In the circumstance described thus far the reduction in air-gap flux is called armature reaction and the resulting flux is much smaller than its value when the stator is open circuit. Restoring air gap and terminal voltage requires the field current to be increased, which is the necessary function of the automatic voltage regulator and the exciter.

When the rotor pole axis coincides with the axis of the stator coils the magnetic circuit seen by the stator has minimum reluctance. The reactance corresponding to the armature reaction in this rotor position is called the direct axis synchronous reactance Xsd . If the stator winding leakage reactance, Xa, is deducted from Xsd the resulting reactance is called the direct axis reactance Xd .

A similar situation occurs when the rotor pole axis is at right angles to the axis of the stator coils. Here the magnetic reluctance is at its maximum value due to the widest part of the air gap facing the stator coils. The complete reactance in this position is called the quadrature axis synchronous reactance Xsq . Deducting Xa results in the quadrature axis reactance Xq .

Transient State Armature Reaction

Assume the generator is loaded and operating in a steady state. If the peak-to-peak or rms value of the stator current changes in magnitude then its corresponding change in magneto-motive force (mmf) will try to change the air-gap flux by armature reaction. Relatively slow changes will allow the change in flux to penetrate into the rotor. When this occurs an emf is induced in the field winding. This emf drives a transient current around a circuit consisting of the field winding itself and the exciter that is supplying the winding. The induction of current is by transformer action. An increase in stator current will be matched by an increase in field current during the transient state. A voltage drop will occur in the machine due to the armature reaction and the reduction in air-gap flux. Reactance is associated with this type of armature reaction.

When the rotor poles are coincident with the stator coils axis the armature reaction is a maximum and the reactance is called the direct axis transient reactance Xd .

The situation is different when the rotor poles are at right angles to the stator coils. There is no induction in the field circuit and the reluctance is high, being almost the same as for the steady state condition. In this situation the corresponding quadrature axis transient reactance X approximately equals the reactance Xq . Cylindrical rotors of two-pole high speed generators have a nearly uniform rotor diameter and almost constant air gap all around the periphery. Hence the reactance Xq is almost equal to Xd .

Sub-Transient State Armature Reaction

Again assume that the generator is loaded and operating in a steady state. In this situation the magnitude of the stator current is allowed to change rapidly, as in the case of a short circuit in the stator circuit. The additional flux produced by the stator winding will try to penetrate the surface of the rotor poles. Most oil industry generators are provided with damper bars to reduce the excursions in rotor speed during major disturbances. The bars are made of copper or copper alloy and placed longitudinally in the face of the rotor poles. They function in a manner similar to a squirrel cage induction motor when there is a transient change in rotor speed relative to the synchronous speed. As soon as the additional flux passes through the pole faces it will induce currents in the damper bars and the solid pole tips, by the process of transformer induction. These induced currents will set up flux in opposition in order to maintain constant flux linkages with the stator.

During this transient condition, or more appropriately called a sub-transient condition, the additional flux is forced to occupy a region consisting of air and the surface of the rotor poles. This is a high reluctance condition which gives rise to reactances of low values.

Some generators have the damper bars connected to a ring at either end of the pole structure, which provides some damping action from the quadrature axis. This provides a set of short-circuited coils in the quadrature axis, which are air cored and able to repel the flux that is attempting to enter their region.

By the same reasoning as for the ‘transient’ reactances so the sub-transient reactances are derived, and are called the direct axis sub-transient reactance X’’d and the quadrature axis subtransient reactance X’’q.

Comments

Popular posts from this blog

BREAKDOWN VOLTAGE AND DIELECTRIC STRENGTH

An insulator or dielectric is a substance within which there are no mobile electrons necessary for electric conduction. However, when the voltage applied to such an insulator exceeds a certain value, then it breaks down and allows a heavy electric current (much larger than the usual leakage current) to flow through it. If the insulator is a solid medium, it gets punctured or cracked. The disruptive or breakdown voltage of an insulator is the minimum voltage required to break it down. Dielectric strength of an insulator or dielectric medium is given by the maximum potential difference which a unit thickness of the medium can withstand without breaking down. In other words, the dielectric strength is given by the potential gradient necessary to cause breakdown of an insulator. Its unit is volt/meter (V/m) although it is usually expressed in KV/mm. For example, when we say that the dielectric strength of air is 3 KV/mm, then it means that the maximum PD which one mm thickness of ...

EQUIPMENT OF STEAM POWER STATION

A modern steam power station is highly complex and has numerous equipment and auxiliaries. However, the most important constituents of a steam power station are: 1. Steam generating equipment 2. Condenser 3. Prime mover 4. Water treatment plant 5. Electrical equipment. 1. STEAM GENERATING EQUIPMENT: This is an important part of steam power station. It is concerned with the generation of superheated steam and includes such items as boiler, boiler furnace, super heater, economizer, air pre-heater and other heat reclaiming devices. (I) BOILER : A boiler is closed vessel in which water is converted into steam by utilizing the heat of coal combustion. Steam boilers are broadly classified into the following two types: (a) Water tube boilers (b) Fire tube boilers In a water tube boiler, water flows through the tubes and the hot gases of combustion flow over these tubes. On the other hand, in a fire tube boiler, the hot products of combustion pass through the tubes surrounded by water. Wate...

TYPES OF SINGLE PHASE MOTORS

Single phase motors are manufactured in fractional kilowatt range to be operated on single phase supply and for use in numerous applications like ceiling fans, refrigerators, food mixers, hair driers, portable drills, vacuum cleaners, washing machines, sewing machines, electric shavers, office machinery etc. Single phase motors are manufactured in different types to meet the requirements of various applications. Single phase motors are classified on the basis of their construction and starting methods employed. The main types of single phase motors are: (a) Induction motors (b) Synchronous motors (c) Commutator motors The various types of motors under each class are shown as under: Repulsion, repulsion induction and reluctance start motors are not used these days, they have been largely replaced by split phase motors with special capacitors which can be designed to perform equally well as repulsion types. In addition they offer such advantages as lower cost and trouble fr...

Advantages of Per Unit System in Power System Analysis | Electrical Engineering

  Advantages of Per Unit System in Power System Analysis In electrical power engineering, the per unit (p.u.) system is one of the most widely used techniques for analyzing and modeling power systems. It is a method of expressing electrical quantities — such as voltage, current, power, and impedance — as fractions of chosen base values rather than their actual numerical magnitudes. This normalization technique provides a universal language for system calculations, minimizing errors, simplifying transformer modeling, and enabling consistency across multiple voltage levels. Because of these benefits, the per unit system is essential in fault analysis, load flow studies, transformer testing, and short-circuit calculations . ⚡ What is the Per Unit System? The per unit system is defined as: Q u a n t i t y ( p u ) = A c t u a l   V a l u e B a s e   V a l u e Quantity_{(pu)} = \dfrac{Actual \ Value}{Base \ Value} Q u an t i t y ( p u ) ​ = B a se   ...

PRIMARY SECONDARY AND TERTIARY FREQUENCY CONTROL IN POWER SYSTEMS

Primary, Secondary and Tertiary Frequency Control in Power Systems Author: Engr. Aneel Kumar Keywords: frequency control, primary frequency control, automatic generation control (AGC), tertiary control, load-frequency control, grid stability. Frequency control keeps the power grid stable by balancing generation and load. When generation and demand drift apart, system frequency moves away from its nominal value (50 or 60 Hz). Grids rely on three hierarchical control layers — Primary , Secondary (AGC), and Tertiary — to arrest frequency deviation, restore the set-point and optimize generation dispatch. Related: Power System Stability — causes & mitigation Overview of primary, secondary and tertiary frequency control in power systems. ⚡ Primary Frequency Control (Droop Control) Primary control is a fast, local response implemented by generator governors (dro...

ELECTRIC MOTOR PRINCIPLES

The electric motor in its simplest terms is a converter of electrical energy to useful mechanical energy. The electric motor has played a leading role in the high productivity of modern industry, and it is therefore directly responsible for the high standard of living being enjoyed throughout the industrialized world. An electric motor’s principle of operation is based on the fact that a current- carrying conductor, when placed in a magnetic field, will have a force exerted on the conductor proportional to the current flowing in the conductor and to the strength of the magnetic field. In alternating current motors, the windings placed in the laminated stator core produce the magnetic field. The aluminum bars in the laminated rotor core are the current carrying conductors upon which the force acts. The resultant action is the rotary motion of the rotor and shaft, which can then be coupled to various devices to be driven and produce the output. Many types of motors are produced today. Un...

FUEL INJECTION SYSTEM OF DIESEL ENGINE

Fuel injection is a system for mixing fuel with air in an internal combustion engine. A fuel injection system is designed and calibrated specifically for the type of fuel it will handle. Most fuel injection systems are for diesel applications. With the advent of electronic fuel injection (EFI), the diesel gasoline hardware has become similar. EFI’s programmable firmware has permitted common hardware to be used with different fuels. Carburetors were the predominant method used to meter fuel before the widespread use of fuel injection. A variety of injection systems have existed since the earliest usage of the internal combustion engine. The primary difference between carburetors and fuel injection is that fuel injection atomizes the fuel by forcibly pumping it through a small nozzle under high pressure, while a carburetor relies on low pressure created by intake air rushing through it to add the fuel to the air stream. The fuel injector is only a nozzle and a valve: the power to inj...