Factors Affecting Corona in Overhead Transmission Lines

Factors Affecting Corona in Overhead Transmission Lines

Author: Engr. Aneel Kumar

Factors affecting corona discharge in transmission lines infographic
Figure 1: Infographic illustrating the factors influencing corona discharge in transmission lines.

Introduction

The corona effect in overhead transmission lines is a phenomenon that occurs when the electric field intensity around conductors exceeds a critical value, causing ionization of the surrounding air. This ionization produces bluish light, hissing sound, power loss, and ozone gas. While corona may seem undesirable, it also has a few advantages such as reducing overvoltages by absorbing surges.

Corona directly impacts power system efficiency, transmission losses, equipment life, and design cost. Therefore, engineers must understand the factors affecting corona in detail to ensure efficient and reliable design of high-voltage transmission systems.

1. Conductor Size (Diameter)

The diameter of the conductor plays a crucial role in corona formation. A larger conductor size results in lower surface electric field intensity, which increases the corona inception voltage and decreases the chances of corona discharge. This is why bundled conductors are extensively used in EHV (Extra High Voltage) and UHV (Ultra High Voltage) systems.

For example, a 400 kV line with a single conductor may produce heavy corona, but the same line using bundled conductors will experience significantly less corona discharge. This reduces corona loss, audible noise, and radio interference.

2. Spacing Between Conductors

The spacing between conductors directly influences the electric field intensity. If conductors are placed close to each other, the field intensity increases and corona is more likely. By increasing conductor spacing, the disruptive critical voltage can be raised, thus reducing corona.

However, excessive spacing is not desirable because it increases tower size, cost, and right-of-way requirements. Therefore, an optimal balance between mechanical design and electrical performance must be achieved.

3. System Voltage

Corona effect is directly proportional to system voltage. At low voltages (below 30 kV), corona is negligible. However, at 220 kV, 400 kV, and higher transmission lines, corona becomes a major consideration in design. Engineers design lines such that the operating voltage is kept well below the corona inception voltage under fair weather conditions.

If the operating voltage is too close to the critical disruptive voltage, corona becomes continuous, leading to severe power losses and interference.

4. Atmospheric Conditions

The atmospheric conditions significantly affect corona performance. In rain, fog, snow, and dust, the conductor surface becomes irregular due to moisture or particles, which reduces the corona inception voltage. This results in a higher intensity of corona discharge.

In fair weather, corona is less severe and often negligible for properly designed systems. Thus, engineers design lines considering worst-case weather scenarios.

5. Conductor Surface Condition

The surface condition of conductors is another critical factor. Smooth, polished conductors maintain uniform electric field distribution, while rough or stranded conductors intensify the electric field at certain points, leading to early corona onset.

Corrosion, dust deposition, and aging of conductors worsen this effect. This is why transmission companies prefer conductors with protective coatings and periodic maintenance to keep surfaces clean.

6. Line Frequency

The frequency of the supply system also impacts corona. Corona loss increases with frequency because ionized particles oscillate more rapidly. Since most power systems operate at 50 Hz or 60 Hz, this factor remains constant; however, HVDC systems are immune to corona loss due to frequency effects.

7. Air Density and Pressure

The air density factor (δ) depends on altitude, temperature, and pressure. At higher altitudes, the air is thinner and offers less insulation strength, reducing the corona inception voltage. This makes corona more prominent in hilly or mountainous regions compared to coastal or plain regions.

Engineers apply correction factors while designing transmission lines for different altitudes to account for this variation.

Comparative Table: Factors vs. Effect on Corona

Factor Influence on Corona
Conductor SizeLarger diameter reduces corona effect by lowering surface electric field intensity.
Conductor SpacingIncreased spacing raises corona inception voltage and reduces corona discharge.
System VoltageHigher operating voltage increases corona intensity and losses.
Atmospheric ConditionsRain, fog, snow, and dust lower inception voltage, increasing corona.
Conductor Surface ConditionRough, dirty, or corroded surfaces intensify electric fields and promote corona.
Line FrequencyCorona loss increases with frequency; HVDC is immune to this effect.
Air DensityLow air density at high altitudes reduces inception voltage, increasing corona.

Advantages of Corona

  • Reduces the severity of voltage surges and transients.
  • Acts as a natural regulator by limiting voltage peaks.
  • Provides a visible and audible warning of over-voltage conditions.

Disadvantages of Corona

  • Causes corona loss, reducing transmission efficiency.
  • Produces radio interference and audible noise.
  • Generates ozone and nitrous oxides, which deteriorate insulation.
  • Leads to power quality issues in nearby communication systems.
  • Reduce transmission line efficiency.
  • Leads to audible hissing and visual glow - undesirable in populated areas.

Conclusion

The corona effect is an inevitable phenomenon in high-voltage transmission lines, but its severity can be minimized through careful design, choice of conductor, optimal spacing, weather considerations, and maintenance. While it has certain advantages such as surge absorption, its disadvantages like power loss and interference outweigh the benefits in most cases.

By understanding the factors affecting corona, engineers can design transmission systems that balance reliability, efficiency, and cost-effectiveness, ensuring long-term stability of the power grid.

Popular posts from this blog

PRIMARY SECONDARY AND TERTIARY FREQUENCY CONTROL IN POWER SYSTEMS

Primary, Secondary and Tertiary Frequency Control in Power Systems Author: Engr. Aneel Kumar Keywords: frequency control, primary frequency control, automatic generation control (AGC), tertiary control, load-frequency control, grid stability. Frequency control keeps the power grid stable by balancing generation and load. When generation and demand drift apart, system frequency moves away from its nominal value (50 or 60 Hz). Grids rely on three hierarchical control layers — Primary , Secondary (AGC), and Tertiary — to arrest frequency deviation, restore the set-point and optimize generation dispatch. Related: Power System Stability — causes & mitigation Overview of primary, secondary and tertiary frequency control in power systems. ⚡ Primary Frequency Control (Droop Control) Primary control is a fast, local response implemented by generator governors (dro...

ADVANTAGES AND DISADVANTAGES OF CORONA EFFECT IN TRANSMISSION LINES | ELECTRICAL ENGINEERING GUIDE

Advantages and Disadvantages of Corona Effect in Power Systems In high-voltage overhead transmission lines , the corona effect plays a critical role in system performance. Corona occurs when the air around a conductor becomes ionized due to high electric stress. While often seen as a drawback because of power losses and interference , it also provides certain engineering benefits . This article explains the advantages and disadvantages of corona effect in detail, with examples relevant to modern electrical power systems. ✅ Advantages of Corona Effect Increase in Virtual Conductor Diameter Due to corona formation, the surrounding air becomes partially conductive, increasing the virtual diameter of the conductor. This reduces electrostatic stress between conductors and minimizes insulation breakdown risks. Related Reading: Electrostatic Fields in High Voltage Engineering Reduction of Transient Surges Corona acts like a natural cushion for sudden ...

CASCADED TRANSFORMERS METHOD FOR GENERATING AC HIGH VOLTAGE

High-Frequency AC High Voltage Generation Using Cascaded Transformers Author: Engr. Aneel Kumar Figure 1: Infographic representation of cascaded transformers method for generating high AC voltages. Introduction In high voltage engineering , generating very high alternating current (AC) voltages is essential for testing equipment like insulators, circuit breakers, power cables, and other apparatus. One common and effective method for producing such voltages is the cascaded transformers method . This technique uses a series connection of specially designed test transformers , where the secondary of one transformer feeds the primary of the next. In this way, voltages are built up step by step, achieving levels in the range of hundreds of kilovolts (kV) or even megavolts (MV). Working Principle The principle of cascaded connection relies on the fact that each...

Breaker Schemes in Substations

Breaker Schemes in Substations — Types, Design, Advantages, Disadvantages, and Comparison Author: Engr. Aneel Kumar Figure 1: Infographic overview of breaker schemes commonly used in substations. Introduction The breaker scheme or busbar arrangement in a substation defines how incoming feeders, outgoing feeders, and power transformers are connected to the bus. The choice of scheme has a direct impact on system reliability, maintainability, safety, and cost . A simple bus scheme is economical but vulnerable to outages, while advanced schemes such as breaker-and-a-half or double-bus/double-breaker provide very high reliability but at much higher cost and design complexity. Engineers select breaker schemes considering fault tolerance, maintenance needs, space requirements, expansion possibilities, protection coordination, and capital investment . Below, we explain eac...

Advantages of Per Unit System in Power System Analysis | Electrical Engineering

  Advantages of Per Unit System in Power System Analysis In electrical power engineering, the per unit (p.u.) system is one of the most widely used techniques for analyzing and modeling power systems. It is a method of expressing electrical quantities — such as voltage, current, power, and impedance — as fractions of chosen base values rather than their actual numerical magnitudes. This normalization technique provides a universal language for system calculations, minimizing errors, simplifying transformer modeling, and enabling consistency across multiple voltage levels. Because of these benefits, the per unit system is essential in fault analysis, load flow studies, transformer testing, and short-circuit calculations . ⚡ What is the Per Unit System? The per unit system is defined as: Q u a n t i t y ( p u ) = A c t u a l   V a l u e B a s e   V a l u e Quantity_{(pu)} = \dfrac{Actual \ Value}{Base \ Value} Q u an t i t y ( p u ) ​ = B a se   ...

SYMMETRICAL COMPONENT ANALYSIS

Unbalanced three phase systems can be split into three balanced components, namely Positive Sequence (balanced and having the same phase sequence as the unbalanced supply), Negative Sequence (balanced and having the opposite phase sequence to the unbalanced supply) and Zero Sequence (balanced but having the same phase and hence no phase sequence). These are known as the Symmetrical Components or the Sequence Components and are shown in figure 2.10. The phase components are the addition of the symmetrical components and can be written as follows.  a = a 1 + a 2 + a 0 b = b 1 + b 2 + b 0 c = c 1 + c 2 + c 0 The unknown unbalanced system has three unknown magnitudes and three unknown angles with respect to the reference direction. Similarly, the combination of the 3 sequence components will also have three unknown magnitudes and three unknown angles with respect to the reference direction. Thus the original unbalanced system effectively has 3 complex unknown quan...