Skip to main content

CURRENT LIMITING REACTOR

CLR is a well-known fault current limiting technique. Compared with many other methods, it is more economical. In addition its effect on the reliability of substation is negligible. However, it occupies a relatively large area in the substation, due to safety considerations. More- over, it may degrade both voltage stability and transient stability of the system.

TYPE OF CLR

Dry type CLR and oil type CLR are the two well-known types of CLR. Dry type is an air-core reactor with copper or aluminum windings. Generally, iron cores are not used in CLRs, due to the possibility of saturation. Since this device is installed in series with the main circuit, possibility of iron core saturation, specially, during short circuit conditions, is high. Therefore, dry type air-core re- actor is the common type of CLR, used in power systems. One of the main problems, associated with this device, is the safety problem due to the magnetic flux distributed through the space around CLR. Therefore, air-core CLRs require proper fencing due to the personnel safety considerations.

Characteristics of oil type reactors are mainly similar to the dry type. However, the oil type is specifically designed for the heavily polluted environments. Moreover, oil type CLR has got the following advantages:
  • Dielectric constant of oil is greater than air. This will result in the smaller size of oil type CLR, compared with the dry type. 
  • Heat transfer capability of oil is higher the air. This will result in some advantages and savings during the design stage. 

TECHNICAL SPECIFICATIONS OF CLR

Important technical parameters of CLRs may be listed as follows:
  • Nominal voltage; 
  • Nominal frequency; 
  • Short circuit capacity of the system; 
  • Basic insulation level; 
  • Continuous operating current; 
  • Rated inductance; 
  • Type (dry or oil); 
  • Class (indoor or outdoor). 

PRACTICAL CONSIDERATIONS OF CLR

CLRs may significantly reduce short circuit level. However, some practical restrictions must be considered, before installing CLRs.

VOLTAGE DROP: CLRs may affect voltage profile of the system. Hence, when CLR is recommended for a system, voltage stability studies of the system should be repeated.

TRANSIENT STABILITY: in addition to voltage stability, CLR may also degrade transient stability of the system.

ENERGY CONSUMPTION: since the main current of power system is continuously passing through the CLR, energy consumption of the device might be significant. This issue must be considered in the CLR design stage.

DISTRIBUTED MAGNETIC FLUX: required safety clearances around the CLR should be double-checked, in order to consider the high magnetic flux, distributed through the space. This will necessitate careful fencing.

TRANSIENT RECOVERY VOLTAGE: when the circuit breakers interrupt short circuit or even normal load current, a transient voltage appears across the opened contacts. This voltage is known as Transient Recovery Voltage. TRV and its rate of rise, known as Rate of Rise of Recovery Voltage are considered as important parameters for the circuit breaker manufacturers. If either TRV or RRRV exceeds the circuit breaker capability, possibility of secondary arc will be increased. This will impose a significant stress on the circuit breaker and other equipment.

CLR affects both TRV and RRRV in the following manner:
  • It reduces the peak of TRV. This is an advantage of CLR. 
  • It increases RRRV. This is a disadvantage of CLR. Unfortunately, RRRV is more critical than TRV. Therefore, prior to the installation of CLR, accurate transient studies are required.

Comments

Popular posts from this blog

AUTO TRANSFORMER TAP CHANGING

Figure shows diagrammatically auto-transformer tap changing. Here, a mid-tapped auto-transformer or reactor is used. One of the lines is connected to its mid-tapping. One end, say a of this transformer is connected to a series of switches across the odd tappings and the other end b is connected to switches across even tappings. A short-circuiting switch S is connected across the auto-transformer and remains in the closed position under normal operation. In the normal operation, there is no inductive voltage drop across the auto-transformer. Referring to Figure, it is clear that with switch 5 closed, minimum secondary turns are in the circuit and hence the output voltage will be the lowest. On the other hand, the output voltage will be maximum when switch 1 is closed. Suppose now it is desired to alter the tapping point from position 5 to position 4 in order to raise the output voltage. For this purpose, short-circuiting switch S is opened, switch 4 is closed, then switch 5 is op...

PLUG REVERSING OF CAPACITOR START MOTORS

The capacitor start motors suffer from the disadvantage that they are not easily reversible due to the centrifugal switch connected in the auxiliary winding. The motor cannot be instantaneously reversed by simple control as the auxiliary winding remains disconnected till the motor comes near to zero speed. However, by proper design of the control circuit the motor can be made instantly reversible. This is accomplished by using an electromagnetic relay along with a special two contact centrifugal switch as shown in Figure. The circuit shown in Figure is for a small hoist using a capacitor start motor. The upper and lower limits of travel are controlled by two limit switches viz. LSU and LSD. When UP-push button is pressed, contactor U gets energized. Its contacts U 1  and U 2  energies the main winding. Closing of its contact U 3  causes relay R to get energized through the centrifugal switch contacts A—B. After the energization of relay R auxiliary winding gets ene...

COMPONENTS OF HIGH VOLTAGE DC TRANSMISSION SYSTEM

Figure: A schematic of a bipolar HVDC system identifying main components

BENEFITS OF UTILIZING FACTS DEVICES

The advantages of using FACTS devices in electrical transmission systems are described below. 1. MORE UTILIZATION OF EXISTING TRANSMISSION SYSTEM In all the countries, the power demand is increasing day by day to transfer the electrical power and controlling the load flow of the transmission system is very necessary this can be achieved by more load centers which can change frequently. Addition of new transmission line is very costly to take the increased load on the system; in that case FACTS devices are much economical to meet the increased load on the same transmission lines. 2. MORE INCREASED TRANSIENT AND DYNAMIC STABILITY OF THE SYSTEM The Long transmission lines are inter-connected with grids to absorb the changing the loading of the transmission line and it is also seen that there should be no line fault creates in the line / transmission system. By doing this the power flow is reduced and transmission line can be trip. By the use of FACTS devices high power t...

AC Transmission Line and Reactive Power Compensation: A Detailed Overview

  Introduction The efficient operation of modern power systems depends significantly on the management of AC transmission lines and reactive power. Reactive power compensation is a vital technique for maintaining voltage stability, improving power transfer capability, and reducing system losses. This article explores the principles of AC transmission lines, the need for reactive power compensation, and its benefits in power systems. Keywords: Reactive Power Compensation Benefits, STATCOM vs SVC Efficiency, Power Transmission Stability Solutions, Voltage Stability in Long-Distance Grids, Dynamic Reactive Power Compensation.      Fundamentals of AC Transmission Lines AC transmission lines are the backbone of modern power systems, connecting generation stations to distribution networks. They have distributed electrical parameters such as resistance ( R R R ), inductance ( L L ), capacitance ( C C ), and conductance ( G G ) along their length. These parameters influence ...

PRIMARY SECONDARY AND TERTIARY FREQUENCY CONTROL IN POWER SYSTEMS

Primary, Secondary and Tertiary Frequency Control in Power Systems Author: Engr. Aneel Kumar Keywords: frequency control, primary frequency control, automatic generation control (AGC), tertiary control, load-frequency control, grid stability. Frequency control keeps the power grid stable by balancing generation and load. When generation and demand drift apart, system frequency moves away from its nominal value (50 or 60 Hz). Grids rely on three hierarchical control layers — Primary , Secondary (AGC), and Tertiary — to arrest frequency deviation, restore the set-point and optimize generation dispatch. Related: Power System Stability — causes & mitigation Overview of primary, secondary and tertiary frequency control in power systems. ⚡ Primary Frequency Control (Droop Control) Primary control is a fast, local response implemented by generator governors (dro...

REVERSING DIRECTION OF ROTATION OF UNIVERSAL MOTOR

The direction of rotation of a universal motor can be changed by either: (i) Reversing the field connection with respect to those of armature; or (ii) By using two field windings wound on the core in opposite directions so that the one connected in series with armature gives clockwise rotation, while the other in series with the armature gives counterclockwise rotation. The second method, i.e, the two field method is used in applications such as motor operated rheostats and servo systems. This method has somewhat simpler connections than the first method. For simple applications like portable drills etc. manual switches are frequently used for reversing the direction of rotation of the motor. Figure  1 (a and b) shows how a DPDT (Double Pole Double Throw) switch and a three position switch may be used for reversing the direction of rotation of single field and double field type of motors respectively. Figure 1 Reversing of a universal motor (a) Armature re...