Skip to main content

TYPES OF SUBSYNCHRONOUS RESONANCE INTERACTIONS

There are several ways in which the system and the generator may interact with subsynchronous effects. A few of these interactions are basic in concept and have been given special names which are discussed here.

•Induction generator effect
• Torsional interaction
• Transient torque

1) INDUCTION GENERATOR EFFECT:
Induction generator effect (IGE) is caused by self-excitation of the electrical network. The resistance of the generator to subsynchronous current, viewed looking into the generator at the armature terminals, is a negative resistance over much of the subsynchronous frequency range. This is typical of any voltage source in any electric network. The network also presents-a resistance to these same currents that is a positive resistance. However, if the negative resistance of the generator is greater in magnitude than the positive resistance of the network at one of the network natural frequencies, growing subsynchronous currents can be expected. This is the condition known as the induction generator effect. Should this condition occur, the generator may experience subsynchronous torques at or near a natural shaft frequency, which may cause large and sustained oscillations that could be damaging to the shaft.

2) TORSIONAL INTERACTION:
Torsional interaction occurs when a generator is connected to a series compensated network, which has one or more natural frequencies that are synchronous frequency complements of one or more of the torsional natural modes of the turbine-generator shaft. When this happens, generator rotor oscillations will build up and this motion will induce armature voltage components at both subsynchronous and super-synchronous frequencies. Moreover, the induced subsynchronous frequency voltage is phased to sustain the subsynchronous torque. If this torque equals or exceeds the inherent mechanical damping of the rotating system, the system will become self-excited. This phenomenon is called torsional interaction (TI).
The network may be capable of many different subsynchronous natural frequencies, depending on the number of lines with series compensation and the degree of compensation installed on each line. Moreover, switching of the network lines can cause these natural frequencies, as viewed from the generator, to change. The engineer must evaluate the network frequencies under all possible switching conditions to determine all possible conditions that may be threatening to the generators. Another condition that can greatly increase the number of discrete network subsynchronous frequencies is the outage of series capacitor segments. The series compensation in high-voltage systems usually consists of several capacitor segments that are connected in series, with each series segment consisting of parallel capacitors as required to carry the line current. This permits individual segments to be removed from service for maintenance and still permit nearly normal loading of the lines. However, individual segments can fail, thereby changing the network natural frequencies and greatly increasing the number of possible frequencies that can be observed from an individual generator. This increases the work required to document and analyze the network frequencies as seen by each generating station.

Another possible source of subsynchronous currents is the presence in the network of HVDC converter stations. The controls of these converters are very fast in their control of the power, but the controls can have other modes of oscillation that may be close to a natural mode of oscillation of a nearby generator. Systems that include HVDC converters also must be carefully checked to see if these controls might induce subsynchronous currents in the generator stators, leading to torsional interaction.

3) TRANSIENT TORQUES:
Transient torques are torques that result from large system disturbances, such as faults. System disturbances cause sudden changes in the network, resulting in sudden changes in currents with components that oscillate at the natural frequencies of the network. In a transmission system without series capacitors, these transients are always de transients, which decay to zero with a time constant that depends on the ratio of inductance to resistance. For networks that contain series capacitors, the transient currents will contain one or more oscillatory frequencies that depend on the network capacitance as well as the inductance and resistance. In a simple radial R-L-C system, there will be only one such natural frequency. If any of these frequencies coincide with the complement of one of the natural modes of shaft oscillation, there can be peak torques that are quite large and these torques are directly proportional to the magnitude of the oscillating current. Currents due to short circuits, therefore, can produce very large shaft torques both when the fault is applied and also when it is cleared. In a real power system there may be many different subsynchronous frequencies involved and the analysis is quite complex.

Of the three different types of interactions described above, the first two, IGE and TI, may be considered as small disturbance conditions, at least initially. The third type, transient torque, is definitely not a small disturbance and nonlinearities of the system also enter into the analysis. From the viewpoint of analysis, it is important to note that the induction generator and torsional interaction effects may be analyzed using linear methods. Eigenvalue analysis is appropriate for the study of these problems and the results of eigenvalue studies give both the frequencies of oscillation and also the damping of each oscillatory mode. The other method used for linear analysis is called the frequency scan method, where the network seen by the generator is also modeled as a function of frequency and the frequency is varied over a wide range of subsynchronous values. This requires that the generator be represented as a tabulation of generator impedance as a function of subsynchronous frequency, which must be provided by the generator manufacturer. This is considered the best model of the generator performance at subsynchronous frequencies, and is often the preferred method of analysis, with eigenvalue analysis used as a complementary check on the frequency scan results.

Comments

Popular posts from this blog

PRIMARY SECONDARY AND TERTIARY FREQUENCY CONTROL IN POWER SYSTEMS

Primary, Secondary and Tertiary Frequency Control in Power Systems Author: Engr. Aneel Kumar Keywords: frequency control, primary frequency control, automatic generation control (AGC), tertiary control, load-frequency control, grid stability. Frequency control keeps the power grid stable by balancing generation and load. When generation and demand drift apart, system frequency moves away from its nominal value (50 or 60 Hz). Grids rely on three hierarchical control layers — Primary , Secondary (AGC), and Tertiary — to arrest frequency deviation, restore the set-point and optimize generation dispatch. Related: Power System Stability — causes & mitigation Overview of primary, secondary and tertiary frequency control in power systems. ⚡ Primary Frequency Control (Droop Control) Primary control is a fast, local response implemented by generator governors (dro...

CASCADED TRANSFORMERS METHOD FOR GENERATING AC HIGH VOLTAGE

High-Frequency AC High Voltage Generation Using Cascaded Transformers Author: Engr. Aneel Kumar Figure 1: Infographic representation of cascaded transformers method for generating high AC voltages. Introduction In high voltage engineering , generating very high alternating current (AC) voltages is essential for testing equipment like insulators, circuit breakers, power cables, and other apparatus. One common and effective method for producing such voltages is the cascaded transformers method . This technique uses a series connection of specially designed test transformers , where the secondary of one transformer feeds the primary of the next. In this way, voltages are built up step by step, achieving levels in the range of hundreds of kilovolts (kV) or even megavolts (MV). Working Principle The principle of cascaded connection relies on the fact that each...

ADVANTAGES AND DISADVANTAGES OF CORONA EFFECT IN TRANSMISSION LINES | ELECTRICAL ENGINEERING GUIDE

Advantages and Disadvantages of Corona Effect in Power Systems In high-voltage overhead transmission lines , the corona effect plays a critical role in system performance. Corona occurs when the air around a conductor becomes ionized due to high electric stress. While often seen as a drawback because of power losses and interference , it also provides certain engineering benefits . This article explains the advantages and disadvantages of corona effect in detail, with examples relevant to modern electrical power systems. ✅ Advantages of Corona Effect Increase in Virtual Conductor Diameter Due to corona formation, the surrounding air becomes partially conductive, increasing the virtual diameter of the conductor. This reduces electrostatic stress between conductors and minimizes insulation breakdown risks. Related Reading: Electrostatic Fields in High Voltage Engineering Reduction of Transient Surges Corona acts like a natural cushion for sudden ...

ADVANTAGES OF INTERCONNECTED GRID SYSTEM

Interconnected Grid System: Working, Advantages, Disadvantages, and Comparison with Isolated Grids Author: Engr. Aneel Kumar Figure 1: Infographic showing key advantages of an interconnected grid system. Introduction An interconnected grid system refers to a network of multiple power generation sources, transmission lines, substations, and distribution systems that are linked across regions, states, or even countries. Unlike an isolated grid (or islanded grid) which operates independently, an interconnected grid allows electricity to flow between interconnected nodes, enabling numerous benefits and some trade-offs. In today’s energy landscape—where demand, renewable generation, reliability, and cost pressure are all increasing—understanding how an interconnected grid works, what factors are essential, and what its advantages and disadvantages are is critical for utility planners, reg...

INTERLINE POWER FLOW CONTROLLER IPFC

Recent developments of FACTS research have led to a new device: the Interline Power Flow Controller (IPFC) . This element consists of two (or more) series voltage source converter-based devices (SSSCs) installed in two (or more) lines and connected at their DC terminals. Thus, in addition to serially compensating the reactive power , each SSSC can provide real power to the common DC link from its own line. The IPFC gives them the possibility to solve the problem of controlling different transmission lines at a determined substation . In fact, the under-utilized lines make available a surplus power which can be used by other lines for real power control. This capability makes it possible to equalize both real and reactive power flow between the lines, to transfer power demand from overloaded to underloaded lines, to compensate against resistive line voltage drops and the corresponding reactive line power, and to increase the effectiveness of a compensating system for dynamic disturbanc...

REACTIVE POWER AND ITS SOURCES

REACTIVE POWER: Reactive power is a concept used by engineers to describe the background energy movement in an Alternating Current (AC) system arising from the production of electric and magnetic fields. These fields store energy which changes through each AC cycle. Devices which store energy by virtue of a magnetic field produced by a flow of current are said to absorb reactive power; those which store energy by virtue of electric fields are said to generate reactive power. Power flows, both actual and potential, must be carefully controlled for a power system to operate within acceptable voltage limits. Reactive power flows can give rise to substantial voltage changes across the system, which means that it is necessary to maintain reactive power balances between sources of generation and points of demand on a 'zonal basis'. Unlike system frequency, which is consistent throughout an interconnected system, voltages experienced at points across the system form a "voltage ...

Advantages of Per Unit System in Power System Analysis | Electrical Engineering

  Advantages of Per Unit System in Power System Analysis In electrical power engineering, the per unit (p.u.) system is one of the most widely used techniques for analyzing and modeling power systems. It is a method of expressing electrical quantities — such as voltage, current, power, and impedance — as fractions of chosen base values rather than their actual numerical magnitudes. This normalization technique provides a universal language for system calculations, minimizing errors, simplifying transformer modeling, and enabling consistency across multiple voltage levels. Because of these benefits, the per unit system is essential in fault analysis, load flow studies, transformer testing, and short-circuit calculations . ⚡ What is the Per Unit System? The per unit system is defined as: Q u a n t i t y ( p u ) = A c t u a l   V a l u e B a s e   V a l u e Quantity_{(pu)} = \dfrac{Actual \ Value}{Base \ Value} Q u an t i t y ( p u ) ​ = B a se   ...